5-412
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
5.8.14 Frequency rate of change (ANSI 81R)
SETTINGS
CONTROL ELEMENTS
FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1(4)
The element responds to rate of change of frequency with voltage, current and frequency supervision.
FREQ RATE 1 TREND
— This setting configures the element to respond to increasing or decreasing frequency, or to frequency
change in either direction.
FREQ RATE 1 PICKUP
— This setting specifies an intended df/dt pickup threshold. For applications monitoring a decreasing
trend, set
FREQ RATE 1 TREND
to “Decreasing” and specify the pickup threshold accordingly. The operating condition is:
-df/dt > Pickup.
For applications monitoring an increasing trend, set
FREQ RATE 1 TREND
to “Increasing” and specify the pickup threshold
accordingly. The operating condition is: df/dt > Pickup.
For applications monitoring rate of change of frequency in any direction set
FREQ RATE 1 TREND
to “Bi-Directional” and
specify the pickup threshold accordingly. The operating condition is: abs (df/dt) > Pickup.
FREQ RATE 1 OV SUPV PICKUP
— This setting defines the minimum voltage level required for operation of the element. The
supervising function responds to the positive-sequence voltage. Use overvoltage supervision to prevent operation under
specific system conditions, such as faults.
FREQ RATE 1 OC SUPV PICKUP
— This setting defines minimum current level required for operation of the element. The
supervising function responds to the positive-sequence current. Typical application includes load shedding. Set the pickup
threshold to 0.020 if no overcurrent supervision is required.
FREQ RATE 1 MIN FREQUENCY
— This setting defines the minimum frequency level required for operation of the element. The
setting can be used to effectively block the feature based on frequency. For example, if the intent is to monitor an
increasing trend but only if the frequency is already above certain level, set this setting to the required frequency level.
FREQUENCY RATE
OF CHANGE 1
FREQ RATE 1
FUNCTION: Disabled
Range: Disabled, Enabled
FREQ RATE 1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
FREQ RATE 1 TREND:
Increasing
Range: Increasing, Decreasing, Bi-directional
FREQ RATE 1 PICKUP:
0.50 Hz/sec
Range: 0.10 to 15.00 Hz/sec in steps of 0.01
FREQ RATE 1 OV SUPV
PICKUP: 0.700 pu
Range: 0.100 to 3.000 pu in steps of 0.001
FREQ RATE 1 OC SUPV
PICKUP: 0.200 pu
Range: 0.020 to 30.000 pu in steps of 0.001
FREQ RATE 1 MIN
FREQUENCY: 45.00 Hz
Range: 20.00 to 80.00 Hz in steps of 0.01
FREQ RATE 1 MAX
FREQUENCY: 65.00 Hz
Range: 20.00 to 80.00 Hz in steps of 0.01
FREQ RATE 1 PICKUP
DELAY: 0.000 s
Range: 0 to 65.535 s in steps of 0.001
FREQ RATE 1 RESET
DELAY: 0.000 s
Range: 0 to 65.535 s in steps of 0.001
FREQ RATE 1 BLOCK:
Off
Range: FlexLogic operand
FREQ RATE 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
FREQ RATE 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...