5-306
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
There are three neutral overvoltage elements available. The neutral overvoltage element can be used to detect
asymmetrical system voltage condition due to a ground fault or to the loss of one or two phases of the source. The
element responds to the system neutral voltage (3V_0), calculated from the phase voltages. The nominal secondary
voltage of the phase voltage channels entered under
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK
PHASE
VT SECONDARY
is the p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The
NEUTRAL OV1 PICKUP DELAY
setting applies only if the
NEUTRAL OV1 CURVE
setting is “Definite Time.” The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
Figure 5-170: Neutral overvoltage1 logic
5.7.14.5 Auxiliary undervoltage (ANSI 27X, IEC PTUV)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
VOLTAGE ELEMENTS
AUXILIARY UV1(3)
The L90 contains one auxiliary undervoltage element for each VT bank. This element monitors undervoltage conditions of
the auxiliary voltage.
The
AUX UV1 PICKUP
selects the voltage level at which the time undervoltage element starts timing. The nominal secondary
voltage of the auxiliary voltage channel entered under
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY
is the per-unit base used when setting the pickup level.
AUXILIARY UV1
AUX UV1
FUNCTION: Disabled
Range: Disabled, Enabled
AUX UV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
AUX UV1 PICKUP:
0.700 pu
Range: 0.004 to 3.000 pu in steps of 0.001
AUX UV1 CURVE:
Definite Time
Range: Definite Time, Inverse Time
AUX UV1 DELAY:
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
AUX UV1 MINIMUM:
VOLTAGE: 0.100 pu
Range: 0.000 to 3.000 pu in steps of 0.001
AUX UV1 BLOCK:
Off
Range: FlexLogic operand
AUX UV1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
AUX UV1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...