CHAPTER 5: SETTINGS
SYSTEM SETUP
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-143
5
NUMBER OF TERMINALS
— This setting is the number of terminals of the protected line.
NUMBER OF CHANNELS
— This setting corresponds to the communications module installed. If the relay is applied on two
terminal lines with a single communications channel, select "1." For a two-terminal line with a second redundant channel
for increased dependability, or for three terminal line applications, select "2."
CHARGING CURRENT COMPENSATION
— This setting enables and disables the charging current calculations and corrections
of current phasors. The voltage signals used for charging current compensation are taken from the source assigned with
the
CURRENT DIFF SIGNAL SOURCE 1
setting. As such, it is critical to ensure that three-phase line voltage is assigned to this
source. The figure shows possible configurations.
ZERO SEQ CAPACITIVE
REACTANCE: 0.100 k
Ω
Range: 0.100 to 65.535 k
Ω
in steps of 0.001
ZERO SEQ CURRENT
REMOVAL: Disabled
Range: Disabled, Enabled
LOCAL RELAY ID
NUMBER: 0
Range: 0 to 255 in steps of 1
TERMINAL 1 RELAY ID
NUMBER: 0
Range: 0 to 255 in steps of 1
TERMINAL 2 RELAY ID
NUMBER: 0
Range: 0 to 255 in steps of 1
CHNL ASYM COMP:
Off
Range: FlexLogic operand
BLOCK GPS TIME REF:
Off
Range: FlexLogic operand
MAX CHNL ASYMMETRY:
1.5 ms
Range: 0.0 to 10.0 ms in steps of 0.1
ROUND TRIP TIME
CHANGE: 1.5 ms
Range: 0.0 to 10.0 ms in steps of 0.1
LOCAL GPS TROUBLE:
Off
Range: FlexLogic operand
IN-ZONE
TRANSFORMER
Any changes to the L90 power system settings change the protection system configuration. As such, the 87L
protection at all L90 protection system terminals must be temporarily disabled to allow the relays to acknowledge
the new settings.
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...