CHAPTER 4: INTERFACES
FRONT PANEL INTERFACE
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
4-43
4
•
BREAKER 1(2) CLOSED
— The breaker is closed
•
BREAKER 1(2) TROUBLE
— A problem related to the breaker has been detected
•
SYNCHROCHECK NO1(10) IN-SYNCH
— Voltages have satisfied the synchrocheck element
•
RECLOSE ENABLED
— The recloser is operational
•
RECLOSE DISABLED
— The recloser is not operational
•
RECLOSE IN PROGRESS
— A reclose operation is in progress
•
RECLOSE LOCKED OUT
— The recloser is not operational and requires a reset
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in
the next section.
Figure 4-50: LED panel 2 (default labels)
4.2.4.3 Graphical front panel
The graphical front panel has 14 LEDs. LEDs 1 to 5 are fixed status LEDs, and LEDs 6 to 14 are programmable.
Status indicators
•
IN SERVICE
— Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, the
relay’s test mode is disabled, and the relay is in (online) Programmed mode (under
Settings > Product Setup >
Installation
)
•
TROUBLE
— Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under
Actual Values > Records
. For a beta /
pre-release, this LED is always on.
•
TEST MODE
— Indicates that the relay is in Isolated (solid) or Forcible (flashing) test mode. For information, see the Test
Mode section in the Settings chapter.
•
TRIP
— Indicates that the selected FlexLogic operand serving as a trip output has operated. This indicator latches;
initiate the reset command to reset the latch.
•
ALARM
— Indicates that the selected FlexLogic operand serving as an alarm output has operated
Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six setting
groups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting groups. Even
though the LEDs have default labels, they are fully user-programmable.
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...