2-2
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT DESCRIPTION
CHAPTER 2: PRODUCT DESCRIPTION
2
62439-3 (clause 4, 2012) when purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
In addition to current differential protection, the relay provides multiple backup protection for phase and ground faults. For
overcurrent protection, the time overcurrent curves can be selected from a selection of standard curve shapes or a
custom FlexCurve™ for optimum co-ordination. Additionally, five zones of phase and ground distance protection with
power swing blocking, out-of-step tripping, line pickup, load encroachment, and six pilot schemes are included.
The L90 incorporates charging current compensation for applications on very long transmission lines without loss of
sensitivity. The line capacitive current is removed from the terminal phasors.
For breaker-and-a-half or ring applications, the L90 design provides secure operation during external faults with possible
current transformation (CT) saturation.
Voltage, current, and power metering are built in as standard features. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only root mean square (RMS) magnitude and angle (phasor).
Settings and actual values can be accessed from the front panel or EnerVista software.
The L90 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device number Function
Device number Function
21G
Ground distance
51_2
Negative-sequence time overcurrent
21P
Phase distance
52
AC circuit breaker
24
Volts per hertz
59C
Compensated overvoltage
25
Synchrocheck
59N
Neutral overvoltage
27P
Phase undervoltage
59P
Phase overvoltage
27X
Auxiliary undervoltage
59X
Auxiliary overvoltage
32N
Wattmetric zero-sequence directional
67N
Neutral directional overcurrent
32R
Sensitive reverse power
67P
Phase directional overcurrent
49
Thermal overload protection
67_2
Negative-sequence directional overcurrent
50BF
Breaker failure
68
Power swing blocking
50DD
Adaptive fault detector
(sensitive current disturbance detector)
78
Out-of-step tripping
79
Automatic recloser
50G
Ground instantaneous overcurrent
81O
Overfrequency
50N
Neutral instantaneous overcurrent
81R
Rate of change of frequency
50P
Phase instantaneous overcurrent
81U
Underfrequency
50_2
Negative-sequence instantaneous overcurrent
87RGF
Restricted ground fault
51G
Ground time overcurrent
87L
Segregated line current differential
51N
Neutral time overcurrent
87LG
Ground line current differential
51P
Phase time overcurrent
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...