7-4
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
COMMANDS MENU
CHAPTER 7: COMMANDS AND TARGETS
7
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to “Yes” and pressing the
ENTER
key. The command setting then automatically
reverts to “No.” The service command is activated by entering a numerical code and pressing the
ENTER
key.
Not all commands display in the software; use the front panel when required.
PERFORM LAMP TEST
— Turns on all front panel LEDs and display pixels for a short duration.
PERFORM LCD TEST
— This command detects either stuck-ON or stuck-OFF pixels (dead pixels) in the display screen on the
graphical front panel. RED/GREEN/BLUE is to display the solid background color in the whole screen. WHITE & TEXT
PATTERN shows the white background and black texts. BLACK & TEXT PATTERN shows the black background and white
texts. TV TEST PATTERN displays a standard television test pattern (SMPTE color bars). The test screen can be cancelled by
pressing any pushbutton or after 30 seconds of inactivity.
PERFORM PUSHBUTTON TEST
— This command tests the pushbuttons on the graphical front panel. During testing, press the
corresponding pushbutton according to the prompt text. A failure message is given if the expected action is not detected
in one minute. Holding the
ESCAPE
button for five seconds to interrupt the test sequence. The designated function of a
specific pushbutton is bypassed in the test.
UPDATE ORDER CODE
— This command causes the relay to scan the backplane for the hardware modules and update the
order code to match. If an update occurs, the following message displays.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
REBOOT RELAY
— Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
made to the configuration settings these changes do not take effect unless the relay is rebooted.
SERVICE COMMAND
— Performs specific L60 service actions. Presently, there are two service actions available. Code "20511"
returns all settings to their factory default value. Code “101” is used to clear factory diagnostic information stored in the
non-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken. Various
self-checking diagnostics are performed in the background while the L60 is running, and diagnostic information is stored
on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is
cleared before the L60 is shipped from the factory, the user can want to clear the diagnostic information for themselves
under certain circumstances. For example, you clear diagnostic information after replacement of hardware. Once the
diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart from
scratch.
SAVE VOLATILE DATA
— Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
recent as possible instead of relying on the periodic timer to save the data.
7.1.5 Security
COMMANDS
SECURITY
UPDATING...
PLEASE WAIT
With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
SECURITY
ADMINISTRATOR
LOGOFF: No
Range: Yes, No
ENGINEER
LOGOFF: No
Range: Yes, No
OPERATOR
LOGOFF: No
Range: Yes, No
CLEAR SECURITY DATA:
No
Range: Yes, No
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...