CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-305
5
Figure 5-175: Selector switch logic
5.7.5 Trip output
SETTINGS
CONTROL ELEMENTS
TRIP OUTPUT
TRIP OUTPUT
TRIP MODE:
Disabled
Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
TRIP 3-POLE INPUT1:
Off
Range: FlexLogic operand
TRIP 3-POLE INPUT6:
Off
Range: FlexLogic operand
TRIP 1-POLE INPUT1:
Off
Range: FlexLogic operand
TRIP 1-POLE INPUT6:
Off
Range: FlexLogic operand
TRIP RECLOSE INPUT1:
Off
Range: FlexLogic operand
TRIP RECLOSE INPUT6:
Off
Range: FlexLogic operand
TRIP SEAL-IN DELAY:
0.000 s
Range: 0 to 65.535 s in steps of 0.001