5-204
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
POS SEQ di/dt FDL SEAL-IN
— This setting defines seal-in time of the FDL function. To equalize the response between all
terminals of the line, the timer is started at the rising edge of the raw di / dt condition.
POS SEQ di/dt FDH PICKUP
— This setting controls pickup of the high set stage of the element used to control the trip
operation. Nominal current of the phase CT bank of the relay is 1pu.
POS SEQ di/dt FDH SEAL-IN
— This setting defines seal-in time of the function. To equalize the response between all terminals
of the line, the timer is started at the rising edge of the raw di / dt condition. In this way, the fault detectors reset
approximately at the same time at all line terminals, regardless of responses of individual raw conditions potentially
different at different line terminals.
POS SEQ FDH SUPV
— This setting provides seal-in control of the FDH function for the symmetrical external three-phase
faults starting as non-symmetrical defined by the
POS SEQ di/dt FDH SEAL-IN
setting time. The overreaching distance
function typically is assigned with this setting.
POS SEQ di/dt BLK
— Note that the fault detector is hard-wired to the 87PC scheme. It can be disabled permanently using
the function setting, or blocked temporarily using this block setting. Select a FlexLogic operand that, if asserted, blocks this
fault detector.
POS SEQ di/dt FD TARGET
— This setting controls targets of the function. These targets operate independently from the 87PC
targets.
POS SEQ di/dt FD EVENTS
— This setting controls event recording of the function. These events are logged independently
from the 87PC events.
Figure 5-102: Positive-sequence current rate of change fault detector logic
5.6.3.7 Negative-sequence overcurrent fault detection
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
ADVANCED FAULT
DETECTORS
NEGATIVE-SEQUENCE CURRENT
NEGATIVE-SEQUENCE
CURRENT
NEG SEQ I_2 FD
FUNCTION: Disabled
Range: Disabled, Enabled
NEG SEQ I_2 FDL
PICKUP: 0.10 pu
Range: 0.02 to 5.00 pu in steps of 0.01
NEG SEQ I_2 FDH
PICKUP: 0.50 pu
Range: 0.05 to 15.00 pu in steps of 0.01
NEG SEQ I_2 BLK:
Off
Range: FlexLogic operand
NEG SEQ I_2 FD
TARGET: Self-reset
Range: Self-Reset, Latched, Disabled
NEG SEQ I_2 FD
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...