5-38
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
PARAMETER
Range: Indicator 1...Indicator 96
Default: Indicator 1...Indicator 96
Read-only field. Up to 96 windows are possible.
CONTENT
Range: Actual, Alarm, Mixed
Default: Alarm
Select if the cell is to be an alarm, an actual value, or a combination thereof, for example consists of a single metered
value (set to “Actual”), contains a single alarm indication (set to “Alarm”), or contains both a metered value and an alarm
indication (set to “Mixed”).
ALARM INPUT
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select a trigger for the alarm, or the input signal connected to the alarm. For example, when set to "FIRST ETHERNET
FAIL" and the Ethernet cable connected to port 1 is removed, the alarm is triggered. (Note that when the Ethernet cable
is inserted into an SFP connector and the SFP connector is removed, the alarm is not triggered.) The field is read-only for
an actual value.
The selectable options are the FlexLogic operands specific to the product.
ALARM TYPE
Range: Acknowledgeable, Self Reset, Latched
Default: Acknowledgeable
Set the alarm type. The field is read-only for an actual value.
Acknowledgeable
— Follow the state transitions, as outlined in the Annunciator section of the Interfaces chapter. The
alarm blinks until acknowledged, then remains on until the condition clears.
Self Reset
— Track the state of the input operand. The alarm turns on when the trigger activates and off when the trigger
clears.
Latched
— Alarm is on until acknowledged/reset individually or until the
RESET
button is pressed.
To acknowledge/reset/unlatch an alarm, use the arrow buttons on the graphical front panel and press the
ENTER
button.
TEXT (LINE 1 to 3)
Range: up to 10 alphanumeric characters
Default:
The text that displays in the annunciator cell. Three lines can be displayed. Note that a specified metering value replaces
the text for the selected line. This means that a line can display text or be set to show an actual metered value. If the text
does not display it is because an actual metered value is over-riding it; change the line for the text or for the actual value.
TEXT COLOR
Range: 24-bit color selector
Default: White
The color to display for the three text or actual value lines specified.
BACK COLOR
Range: 24-bit color selector
Default: Red
The background color to display for any triggered cell, for example when an alarm is triggered.
ACTUAL (Configure)
Range: Configure
Default: Configure
The
Configure
button becomes active when the
CONTENT
field is set to "Actual" or "Mixed." The window specifies the
metering data to display.
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...