5-8
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
5.3 Product setup
5.3.1 Security
5.3.1.1 Security overview
The following security features are available:
•
Password security — Basic security present by default
•
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
•
CyberSentry security — Advanced security available using a software option. When purchased, the option is
automatically enabled, and the default Password security and EnerVista security are disabled.
Lost password
If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default
values, not just the passwords.
To reset the unit after a lost password:
1.
Email GE customer service at [email protected] with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2.
Enter the reset code on the front panel, under
COMMANDS
RELAY MAINTENANCE
SERVICE COMMAND
.
3.
Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section at the end of the Installation chapter.
Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
•
Password is case-sensitive
•
Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
•
Password must be 8 to 20 characters in length
•
Password must contain characters from all of the following categories:
–
English uppercase characters (A through Z)
–
English lowercase characters (a through z)
–
Base 10 digits (0 through 9)
–
Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
5.3.1.2 Password security
SETTINGS
PRODUCT SETUP
SECURITY
SECURITY
ACCESS LEVEL:
Restricted
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
CHANGE LOCAL
PASSWORDS
CHANGE REMOTE
PASSWORDS
ACCESS
SUPERVISION
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...