CHAPTER 5: SETTINGS
FLEXLOGIC
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-203
5
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
5.6.5 FlexLogic equation editor
SETTINGS
FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to ‘1’. Press the
+/–
key when editing
FlexLogic equations to quickly scan through the major parameter types.
5.6.6 FlexLogic timers
SETTINGS
FLEXLOGIC
FLEXLOGIC TIMERS
FLEXLOGIC TIMER 1(32)
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
TIMER 1 TYPE
— Selects the time measurement unit.
TIMER 1 PICKUP DELAY
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
5.6.7 FlexElements
SETTINGS
FLEXLOGIC
FLEXELEMENTS
FLEXELEMENT 1(8)
FLEXLOGIC
EQUATION EDITOR
FLEXLOGIC ENTRY 1:
END
Range: FlexLogic operands
FLEXLOGIC ENTRY 1024:
END
Range: FlexLogic operands
FLEXLOGIC
TIMER 1
TIMER 1
TYPE: millisecond
Range: millisecond, second, minute
TIMER 1 PICKUP
DELAY: 0
Range: 0 to 60000 in steps of 1
TIMER 1 DROPOUT
DELAY: 0
Range: 0 to 60000 in steps of 1
FLEXELEMENT 1
FLEXELEMENT 1
FUNCTION: Disabled
Range: Disabled, Enabled
FLEXELEMENT 1 NAME:
FxE 1
Range: up to six alphanumeric characters
FLEXELEMENT 1 +IN:
Off
Range: Off, any analog actual value parameter
FLEXELEMENT 1 -IN:
Off
Range: Off, any analog actual value parameter
FLEXELEMENT 1 INPUT
MODE: SIGNED
Range: SIGNED, ABSOLUTE
FLEXELEMENT 1 COMP
MODE: LEVEL
Range: LEVEL, DELTA
FLEXELEMENT 1
DIRECTION: OVER
Range: OVER, UNDER
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...