Page 33
Intellix
™
BMT 330 User Manual
BMT330UM
v1.0
20-Jun-16
Partial Discharge
Figure 14: Alarm > Partial Discharge tab
Parameter
Suggested Value or Source of Data
1
Default
Allowable range
2
Period to calculate PD trend
24 h
0 to 720
High noise level high
0 (disabled)
0 to 100
PD max level warning
8000 pC
0 to 65000
PD max level alarm
12000 pC
0 to 65000
PD average level warning
1000 pC
0 to 65000
PD average level alarm
2000 pC
0 to 65000
PD average level trend warning 0 (disabled)
0 to 65000
1
Alarm limits and settings must be revised a few weeks after installation by customer depending
on bushing behaviour.
2
Value of zero disables this particular alarm.