TROUBLESHOOTING

GE Lighting Controls, 

41 Woodford Ave., Plainville, CT 06062

Made in U.S.A.

Emergency Manual ON

An override jumper is located underneath the touchplate. This
jumper should remain in place at all times, except in the event
of unit malfunction. Remove the jumper to bypass the sensor
and turn the lights on.

LED Will Not Go On

Verify that the lighting circuit has power. Verify that the sensor
is properly adjusted. Press the touchplate to turn on the lights
manually. If the LED does not light, replace the RSEN-W12.

Lights Will Not Turn ON

• If the lights will not turn on automatically after someone

enters the room, press the touchplate to see if lights will
turn on. If so, the RSEN-W12 could be set to Manual ON
mode. Check under the touchplate to verify the setting.

• If set to Automatic ON mode, the sensor may have been

overridden by someone pressing the touchplate; allow the
RSEN-W12 to time out to verify normal operation.

• If the lights do not turn on after pressing the touchplate,

confirm that no other switches or equipment are interrupt-
ing or bypassing power to the sensor or the load.

• If lights still do not turn on, replace the RSEN-W12.

Lights Will Not Turn OFF

• If lights will not turn off after the set time delay, and the

LED has not lit during the time period, press the touchplate
to turn off the lights manually.

• If lights turn off, refer to items 5 and 6 under “Checkout

and Adjustment.”

• If lights do not turn off, verify that the override jumper

under the touchplate has not been removed.

• Confirm that no other switches or equipment are interrupt-

ing or bypassing power to the RSEN-W12 or the load.

• If lights still do not turn off, replace the RSEN-W12.

Emergency Service or Support (888) 852-2778

Содержание IMRSEN-W12

Страница 1: ...o motion is detected the lights will turn off automatically after the pre set time delay Following this a grace period of approximately ten seconds allows lights to be turned on again by motion At any time lights may be turned off while the room is occupied by pressing the touchplate The RSEN W12 is fully self resetting lights turned off manually in Automatic ON mode will stay off while the room r...

Страница 2: ...20 VAC or 277 VAC only Do not use with any other voltage Do not wire to control receptacle circuits Verify that the connected load does not exceed the RSEN W12 ratings Use twist on wire connectors for all connections All installations should be in compliance with the NEC and all state and local electrical codes The RSEN W12 can be wired to control both an exhaust fan and lighting provided the tota...

Страница 3: ...after the lights go out Walk normally back into the room and verify that the lights turn on automatically If not the Entry Range should be increased slightly Do not set higher than necessary 5 If the LED blinks when there is no movement in the room it is possible that the sensor is being activated by air flow from the HVAC system Reduce the Area Range setting until the LED goes off and stays off w...

Страница 4: ...touchplate to verify the setting If set to Automatic ON mode the sensor may have been overridden by someone pressing the touchplate allow the RSEN W12 to time out to verify normal operation If the lights do not turn on after pressing the touchplate confirm that no other switches or equipment are interrupt ing or bypassing power to the sensor or the load If lights still do not turn on replace the R...

Отзывы: