GEK-45376 

The  user  must  determine  the  specific  settings  which  will  provide  the  required  protection  for  his 

�achine,  and  select  a  relay  model  having  the  operating  ranges  needed  to  obtain  these  settings. 

With  settings  as  illustrated  in  Figure  9  and  external  connections  shown  in  Figure  10,  the  operation  of 

�"" 

IFC66K  relay  will  be  as  follows: 

1. 

For  motor  overloads  the  time  overcurrent  unit  (51)  will  time  out,  picking  up  an  external  auxiliary 
51X,  which  sounds  an  alarm. 

*2. 

For  the  locked  rotor  condition  the  high-dropout  unit  (50/B)  will  pick  up  instantaneously  and  the 
TOC  unit  (51)  will  pick  up  with  a  time  delay  consistent  with  the  motor  thermal  limit. 

When  both 

units  have  operated  the  breaker  will  be  tripped. 

*3. 

For  a  fault  the  normal  dropout  instantaneous  unit  (50/A)  �ill  pick  up  instantaneously  and  trip  the 

breaker. 

When  used  as  back-up  protection,  the  time  overcurrent  unit  IFC66  should  be  set  to  coordinate  with  down­

stream  protective  devices.  A  minimum  coordinating  time  margin  of  0.2  to  0.4  seconds  will  normally  be  required. 
The  following  factors  must  be  considered  in  determining  a  setting: 

• 

Operating  time  of  the  downstream  relay  and  breaker 

• 

Overtravel  in  the  induction  disk  unit 

• 

A  safety  factor  to  allow  for  variations  in  system  parameters  from  the  values  used  to  determine  the 

relay  setting. 

Relay  overtravel  is  often  considered  to  be  less  than  0. 1  second;  exact  values  can  be  read  from  Figure  11. 

Typical  safety  factors  range  from  0.1  to  0.2  seconds. 

CONSTRUCTION 

The  IFC  induction  disk  relays  consist  of  a  molded  case,  cover,  support  structure  assembly,  and  a  connec­

tion  plug  to  make  up  the  electrical  connection.  See  Cover  Figure  and  Figures  1,  2  and  19.  Figure  2  shows 
the  induction  unit  mounted  to  the  molded  support  structure.  The  disk  is  activated  by  a  current  operating 
cr�,  mounted  on  a  laminated  U-Magnet.  The  disk  and  shaft  assembly  carries  a  moving  contact  which  completes 

larm  or  trip  circuit  when  it  touches  a  stationary  contact.  The  disk  assembly  is  restrained  by  a  spiral 

spr1ng  to  give  the  proper  contact  closing  current.  The  disk's  rotation  is  retarded  by  a  permanent  magnet 
mounted  in  a  molded  housing  on  the  support  structure. 

The  drawout  connection/test  system  for  the  Cl  case,  shown  in  Figure  19,  has  provisions  for  14  connection 

points,  and  a  visible  CT  shorting  bar  located  up  front.  As  the  connection  plug  is  withdrawn,  it  clears  the 

shorter  contact  fingers  in  the  output  contact  circuits  first.  Thus,  the  trip  circuit  is  opened  before  any 
other  circuits  are  disconnected.  Next,  current  circuit  fingers  on  the  case  connection  block  engage  the  short­
ing  bar  (located  at  the  lower  front  of  the  case)  to  short-circuit  external  current  transformer  secondary 

connections.  The  window  provides  visual  confirmation  of  CT  shorting.  The  connection  plug  then  clears  the 
current  circuit  contact  fingers  on  the  case  and  finally  those  on  the  relay  support  structure  to  completely 
de-energize  the  drawout  element. 

There  is  a  Hi-Seismic  target  and  seal-in  unit  mounted  on  the  front  to  the  left  of  the  shaft  of  the  time 

overcurrent  unit,  see  Figure  1.  The  seal-in  unit  has  its  coil  in  series  and  its  contacts  in  parallel  with  the 

contacts  of  the  time  overcurrent  unit  such  that  when  the  induction  unit  contacts  close,  the  seal-in  unit  picks 
up  and  seals  in. 

When  the  seal-in  unit  picks  up,  it  raises  a  target  into  view  which  latches  up  and  remains 

exposed  until  released  by  pressing  a  reset  button  located  on  the  upper  side  of  the  cover. 

The  IFC  "B"  and  "K"  model  relays  in  addition  to  the  above  contain  a  Hi-Seismic  instantaneous  unit,  see 

Figure  1. 

The  instantaneous  unit  is  a  small  hinged  type  unit  which  is  mounted  on  the  front  to  the  right  of 

the  shaft  of  the  time  overcurrent  unit.  Its  contacts  are  normally  connected  in  parallel  with  the  contacts  of 

the  time  overcurrent  unit  and  its  coil  is  connected  in  series  with  the  time  overcurrent  unit.  When  the 

instantaneous  unit  picks  up  it  raises  a  target  which  latches  up  and  remains  exposed  until  it  is  released.  The 
same  reset  button  that  releases  the  target  seal-in  unit  also  releases  the  target  of  the  instantaneous  unit. 

The  IFC  "K"  model  relays  in  addition  to  the  above  contain  a  Hi-Seismic  dropout  instantaneous  unit. 

The 

high  dropout  instantaneous  unit  is  a  small  hinged  type  mounted  in  the  rear  of  the  relay,  see  Figure  2. 
Unlike  the  Hi-Seismic  instantaneous  unit,  this  unit  does  not  include  a  target  and  therefore  does  not  have  to 

be  rP-set  after  it  operates. 

,� 

magnetic  shield,  depicted  in  Figure  1,  is  mounted  to  the  support  structure,  to  eliminate  the  proximity 

affect  of  external  magnetic  materials. 

- ---------------·---------�-- --�--- - --- - ---·--- ------ ---- �----- -------�-·----� 

• 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание IFC66A

Страница 1: ...6A IFC66B IFC66K INSTRUCTIONS TIME OVERCURRENT RELAYS GENERAL f j ELECTRIC GEK 45376B Supersedes GEK 45376A w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 3: ...MENTS G ENERAL 10 T IME OVERCURRENT UNI T 10 HI SEISM IC INSTANTANEOUS UN IT 11 H IGH D ROPOUT INSTANTANEOUS UNIT 11 H I SE I SM IC TARGET AND SEAL IN UNI T 11 INSTALLATI ON 12 INSTALLATI ON TESTS 12 PER IODIC CHECKS AND ROUTINE MAINTENANCE 13 T IME OVERCURRENT UNI T 13 HI SEISMIC INSTANTANEOUS UNIT 13 H IGH DROPOUT INSTANTANEOUS UN IT 13 HI SEISMIC TARGET AND SEAL IN UN IT 13 CONTACT CLEANING 13 ...

Страница 4: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 5: ... made by using the transient overreach curves in Figure 11 The IFC66A and IFC66B rel ays are also useful for application on the primary of a smal l l ow vol tage l oad center transformer when the secondary main protective device is an insul ated case circuit breaker In such cases the l ong time capabil ity permits the rel ay to be set sel ectivel y with the non adjustabl e l ong time thermal el em...

Страница 6: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 7: ...or 14 connection points and a visible CT shorting bar located up front As the connection plug is withdrawn it clears the shorter contact fingers in the output contact circuits first Thus the trip circuit is opened before any other circuits are disconnected Next current circuit fingers on the case connection block engage the short ing bar located at the lower front of the case to short circuit exte...

Страница 8: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 9: ...atings are listed in Tab l e 3 TABLE 3 Model Time Overcurrent Unit One Second Ratin Any Tap K Amperes Amperes IFC66A B K 2 5 7 5 350 122500 Ratings less than one second may be cal cu l ated according to the formu la I v K T where T is the time in seconds that the current flows The continuous ratings for the time overcurrent unit ar e shown in Table 4 TABLE 4 2 5 7 5 Ampere Range Ratings Mode l I F...

Страница 10: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 11: ...movable lead located in the rear of the relay TABLE 6 Unit Tap Range Continuous One K Position Rating Second Amps Ratin J Amps L 2 4 3 7 2 8 130 16900 H 4 8 4 8 The range is approximate which means that the 2 4 4 8 may be 2 5 4 8 ampere overlap between the maximum L setting and the minimum H setting range since it has the higher continuous rating There will always be at least one Whenever possible...

Страница 12: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 13: ...seal in unit BURDENS Burdens for the time overcurrent unit are given in Table 8 TABLE 8 Min Burdens at Min Burdens in Ohms Z Model Hz Range Tap Pickup Min Tap Times Pickup Amps Ohms R Jx z 3 10 20 IFC66 so 085 307 318 153 081 063 2 5 7 5 2 5 60 102 368 382 183 097 076 Note The impedance values given are those for minimum tap of each range the impedance for other taps at pickup current tap rating v...

Страница 14: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 15: ... 0 25 0 18 0 31 0 21 0 18 0 17 CHARACTERIST ICS Pickup in these relays is defined as the current required to close the contacts from the 0 5 time dial position Current settings are made by means of two movable leads which connect to the tap block at the top of the support structure see Figure 1 The tap block is marked A through M See the nameplate on the relay for tap settings Example The 5 amp ta...

Страница 16: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 17: ...m moisture dust and metallic chips Foreign matter collected en the outside may find its way inside when the cover is removed and cause trouble in the operation of the relay ACCEPTANCE TESTS Immediately upon receipt of the relay an inspection and acceptance test should be made to insure that no damage has been sustained in shipment and that the relay calibrations have not been disturbed If the exam...

Страница 18: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...imum current at which the contacts wil l just close is determined by the tap setting in the tap bl ock at the top of the support structure See CHARACTERISTIC section The pickup of the time overcurrent unit for any current tap setting is adjusted by means of a spring adjusting ring See Figure 1 The spring adjusting ring either winds or unwinds the spiral control spring By t rning the ring the opera...

Страница 20: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 21: ...e test circuit of Figure 1 6 Setting The High Dropout Instantaneous Unit The high dropout instantaneous unit has an adjustable core l ocated at the top of the unit as shown in Figure 2 To set the instantaneous unit to a desired pickup l oosen the l ocknut and adjust the core Turning the core cl ockwise decreases the pickup turning the core counterclockwise increas s the pickup Bring up the current...

Страница 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 23: ... 8 and 1 0 INSTALLAT ION TESTS The fol lowing tests are to be performed at the time of instal l ation Time Overcurrcr t Unit Set the tap block to the desired tap setting and the time dial to the 0 5 position Using the test circuit in Figure 15 gradual l y apply current until the contacts just cl ose This value of current is defined as pickup and shoul d be within three percent of tap value Check t...

Страница 24: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 25: ...ngs If deviations are encountered the rel ay must be retested and serviced as describe9 in this manual TIME OVERCURRENT UNil l Perform pickup test as described in the I NSTALLATION section for the tap setting in service 2 Perform the time tests as described in the I NSTALLATI ON section H I SE I SMIC INSTANTANEOUS UNIT l Check that the instantaneous unit picks up at the desired current level as ou...

Страница 26: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 27: ...requency and good waveform having a voltage of 1 1 0 or more with resistance l oad boxes for setting the current See TEST C I RCU IT Figure 1 5 With the tap bl ock set for the l owest tap and the time dial set where contacts are just open adjust the control spring to just close the contacts within the l imits given bel ow which are plus and minus 1 percent of the tao amps See Tab le 1 3 TABLE 1 3 ...

Страница 28: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 29: ...hould be replaced 10 Reinstall the drag magnet assembly and check that the disk has at least 0 0 10 inch clearance from the drag magnet assembly surfaces 11 Tighten the drag magnet assembly mounting screws with 7 10 inch pounds of torque after securely seating thL assembly and positioning it according to the TIME TEST above HI SEISMIC INSTANTANEOUS UNIT AND HIGH DROPOUT INSTANTANEOUS UN IT 1 Both ...

Страница 30: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 31: ...e worn broken or damaged When ordering renewal parts address the nearest Sales Office of the General Electric Company specify quantity required name of the part wanted and the complete model number of the relay for which the part is required i6 I w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 32: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 33: ... STICS OF THE HI SE I SMIC I NSTANTANEOUS UNIT TIME CURRENT CHARACTER I STICS OF THE H I SE I SMIC I NSTANEOUS UNIT TEST CONNECTIONS FOR TESTI NG CT SECONDARY USED WITH THE I FC RELAY TEST CONNECT IONS FOR TEST I NG P I C KUP AND OPERAT ING TIMES OF THE I FC RELAY TIME OVERCURRENT UNIT TEST CONNECTIONS FOR TESTI NG P I C KUP AND OPERAT ING TIMES OF THE IFC R ELAY H I SE I SMIC I NSTANTANEOUS UNIT ...

Страница 34: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 35: ...G RING GEK 45376 INSTANTANEOUS UNIT TIME DIAL MAIN MOVING CONTACT DRAG MAGNET A SSEMBLY FIG 1 8043007 TYPE I FC66K RELAY REMOVED FROM CASE FRONT V I EW 1 8 I 6 I w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 36: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 37: ...GNET AND TAP BLOCK ASSEMBLY TIME OVERCURRENT UNIT esJJ SUPPORT STRUCTURE F IG 2 80430 1 1 TYPE IFC 66K RELAY REMOVED FROM CASE REAR VIEW 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 38: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 39: ..._ UNIT TSI TSI t y 0 0 2 G 5 SHORT FINGER F I G 3 0257A8339 2 I NTERNAL CONNECTI ONS FOR RELAY TYPE IFC66A FRONT V I EW 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 40: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 41: ...GS SET Ll HI TO W FOR HIGH RAHGE AND TO L FOR LOW RANGE LINK SHOWN IN H I GH RANGE POSITION FIG 4 0257A8340 4 INTERNAL CONNECT IONS FOR RELAY TYPE I FC66B FRONT VIEW M4 W ji1 4 C QC P 21 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 42: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 43: ...UNIT GEK 45376 STANDARD JNST UNIT L 4 l 3 5 HI QROPOUT I _ ST SETTlNGS SHOWN IN THE HIGH RANGE CONNECT TERMINAL 6 TO E FOR LOW RANGE 6 1 r 7 10 9 FIG 5 0257A9644 l INTERNAL CONNECT I ONS FOR R ELAY TYPE I FC66K FRONT V I EW 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 44: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 45: ... z r r r 2 r w lf J I 0 w I r T I M E U N I T 4 I I 1 I I 1 0 Zl 5I 71 1111 M U LT I P L ES OF P I C K U P SETTI N G I I f 1 1 1 11 I 1 1 1 1 1 11 I 1 Ito 1 Ill 01 to 70 so 30 1 1 I I u 1 07 oo 04 11 I I I Ul F I G 6 01 0888969 1 6 0 HERTZ TIME CURRENT CHARACTER I STICS FOR R ELAY TYPE IFC66 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c ...

Страница 46: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 47: ...6 t 5 4 z 3 t 1 f 2 l I J If _J r T I M E U N I T I 4 5 I J I I ID I 0 l U I 1 2 ll 41 Sl II 70 liN 1 U LTI PLES O F P I C K U P S E TT I N G I i l FIG 7 01 0888970 1 50 HERTZ T IME CURRENT CHARACTERI STICS FOR RELAY TYPE TFC66 24 I 000 100 100 700 100 00 200 Iao 10 70 10 so o 20 I I I I 7 I J I I l 01 z 01 07 1 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a ...

Страница 48: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 49: ... O W E R C I R C U I T B R E A K E R l J O C T R I P 8 U S a 5 2 T C 5 0 1 5 1 2 5 1 3 5 0 2 s o S A l E A S P H A S E I F I G 8 0269A301 4 0 TYP ICAL EXTERNAL CONNECT IONS FOR RELAY TYPES I FC66A AND I FC668 25 _ ___ _ __ _ _ _ w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 50: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 51: ...R O P O U T w 0 lL i N ST U N I T G a a 50 0 0 8 _J u t 0 0 0 5 t 0 C U R R E N T N O R M A L D R O P O U T J NST U N I T 5 0 A F I G 9 0269A305 5 0 MOTOR PROTECTION CHARACTER I ST I C CURVE 26 i T__ _ __ _ w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 52: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 53: ... I L I A RY R E L A Y N O R M A L D R O P O U T I N S TA N TA N E O U S OV E R C U R R E N T U N I T l P O W E R C I RC U I T B R E A K E R H iGH D R O P O U T I N S TA N TA N E O U S O V E RC U R R E N T U N I T AUXI L I A RY CO N TAC T CLOSED W H E N C I R CU I T B R E A KE R I S C _O S E D T R I P C O I L F I G 1 0 0269A301 3 l TYP I CAL EXTERNAL CONNECTIONS FOR RELAY TYPE I F 66K 27 w w w E l ...

Страница 54: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 55: ... O 2 i v I I I l I I v i v I I v l I I _i 1 l I T 0 4 1 I I I I I i I I I ___ i 1 I V i I I v J I t i T D 3 T O 5 1 0 I 4 6 8 1 0 1 2 1 4 1 6 1 8 20 M U LT I P L E S O F P I C K U P F I G 1 1 0269A 1 869 0 OVERTRAV EL CURVES FOR RELAY TYPE I FC66 28 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 56: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 57: ...J J 8 CL CL II J t i fj ffi c UJ Q Q ij 1 0 a ffi t Q Q a II It CL CD t _ r _ 0 0 lN3J 3d N l HOV3 3AO F IG 1 2 0208A8694 l TRANS I ENT OV ERREACH C HARACTER IST ICS OF THE H I SE I SMIC INSTANTANEOUS UNIT 29 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 58: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 59: ...0 10 y I I I I v v 1 u 0 tn 0 0 8 SON003S N l 3 11 d l d FIG 1 3 0208A8695 0 TH E CURR ENT CHARACTER I ST I CS O F THE H I S E I SMIC I NSTANTANEOUS UN l 1 30 a u a u 0 w J a 1 J l t ll w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 60: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 61: ...O R 1 2 X C A I I A 2 R E L A Y C C I L N O T I N C I R C U I T 0 0 R E L A Y S I D E C A S E S I D E 1 2 X C A I I A I 5 6 F I G 1 4 0269A 1 787 0 TEST CONNECTIONS FOR TEST I NG CT SECONDARY USED WITH THE I FC RELAY 31 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 62: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 63: ...N G _ L I G H T W H E N C H EC K I N G P I C K U P R E L AY I 2 T E R M I N A L S t t 1 2 XCA I I A I REL AY SIDE i C A SE S IDE 0 0 5 5 C T J U M P E R F I G 1 5 0269Al 789 0 TEST CONNECT IONS FOR TESTING P I C KUP AND OPERAT I NG T IMES OF THE IFC RELAY T IME OVERCURRENT UNIT 32 f w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 64: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 65: ...K U P RELAY 2 3 4 T E R M I N A LS 0 R ELAY R ELAY S I DE S I D E CAS E C ASE S I D E S IDE 1 2 X C A I I A I 0 0 0 0 5 0 R E L AY S I D E C AS E S I D E I 5 C T J U M P E R F I G 1 6 0269Al 788 l TEST CONNECTI ONS FOR TESTING P I C KUP AND OPERAT ING T IMES OF THE I FC R ELAY H I SE I SM IC INSTANTANEOUS UNIT 33 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r...

Страница 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 67: ... E S I S T O R 8 O r TO S T O P T I M E R 9 10 R E LA Y i R E L A Y S I D E S I D E C A SE S I D E 0 o l C A SE S I D E 0 TO I N D I C A T I N G L I G H T W H E N C H E C K I N G P I C K U P F I G 1 7 0269Al 865 0 TEST CONNECT IONS P IC KUP AND DROPOUT OF THE HIGH DROPOUT I NSTANTANEOUS UNIT 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c ...

Страница 68: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 69: ...N ALS REL A Y S I D E C A SE S IDE 1 2 X C A I IA I 0 2 0 F I G 1 8 0269Al 790 0 TEST CONNECTIONS FOR TEST I NG THE HI SEISMIC TARGET AND SEAL IN UNIT USED WITH THE I FC RELAY 35 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 70: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 71: ... L EM E N T S U PP O R T STR U C T U R E CAS E C O N N E C T I O N B L O C K F I G 1 9 804271 5 CROSS SECT ION OF I FC DRAWOUT CASE SHOWING SHORTING BAR 36 __ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ ___ _ _ _ _ _ _ _ t w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 72: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 73: ...L C O N N EC T I O NS 1 0 32 SC R EW S I G L _ I _2 844_ i 73MM I L 5 6 88 1 4 6 _ M I r 3 94 79t 1M I T I E Sl 0_ _ _y L EW S E I F LU S H MOU N T I NG P A N E L DB L l JJ lli 1 F tJ L l L_ OI _ I fTI NG PA N E l ___ __ ___ WA 3H E R LOC KWA S H E R 8 32 SC F EW 5U P P O RT O R T I E A N C H O R M AX 1 2 5 TH K 3HH F NU T V l E W A I O X I 2 TY P E B T T H E A D CU T T I N G C A B L ES If I I HD ...

Страница 74: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 75: ...M O U N T I NG H AX l88 P A N E L 5 N H 1 5 3 44 668 I 212 H N 94MNf S E E VIEW C I E X T E R NAL C O N N E C n ONS 10 32 SC R EWS MOU N TI NG S U R FACE S I C E I E W REC SL RFA C E M T G F O R h THK PAN E L S A N D AEO V E PAN EL D R I L LI NG E N L A R G E D V I E w e H 0 W 0 2 57A8 5 4 9 G 2 T r 7 4 E 9 2 3 7 1 2M H 6 1 MH It_ 750 j _ ___ ___ __L9NtD _ 4 7so 0 0 0 qoo T 12 0 0 5_ E 2 5 1 6 M M...

Страница 76: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: