GFK-2571A
Chapter 1 Introduction
1-3
1
PROFINET Controller Specifications
PROFINET Support
PROFINET Version 2.2 General Class A IO-Controller
CPU Compatibility
Requires CPU315 or CPU320, with firmware version 7.0 or higher.
Power Requirements
3.3V: 0.5 A with no SFP devices installed
1.2 A maximum (2 SFP devices installed, 0.35 A per SFP device)
5V: 1.5 A maximum
Operating Temperature Range
0 to 60°C maximum surrounding air temperature without a fan.
A lower maximum temperature may be required depending on PNC
location and SFP population.
Refer to ―Maximum Surrounding Air
Temperature Derating
‖ on page 1-4.
Number of Port Connectors
Two RJ-45 and Two SFP Cages
(SFP devices not included, available separately.)
Micro USB Connector
One, for communication with a computer using Command Line Interface.
LAN
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
Maximum I/O Memory
128 Kbytes of combined input/output memory per PROFINET Controller
CPU Status Bits
32
PROFINET IO-Device Data
Update Rates on the
PROFINET Network
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms
and 512ms
Number of IP addresses
One
Number of MAC Addresses
Five. One per external port and one internal.
System Maximum Limits
PROFINET Controllers per RX3i
CPU
4. Must be located in main rack. Cannot be located in a remote node.
IO-Devices per IO-Controller
64 per PROFINET Controller at maximum update interval. For limits at
shorter update intervals, refer to
―PNC Loading Limits‖ in chapter 3.
IO-Devices per Network
128 per network, spread across up to 8 IO-Controllers
IO-Devices per RX3i CPU
128 per RX3i CPU, spread across up to 4 PROFINET Controllers
IO-Controllers per network
8
Number of PROFINET Slots per
device
256
Number of PROFINET Subslots
per slot
256
Number of PROFINET
Submodules per RX3i CPU
2048
Programmer Limits
Number of IO-Controllers
128 (32 RX3i CPU targets × 4 IO-Controllers per RX3i CPU)
Number of IO-Devices
2048 (128 per network × 16 PROFINET networks)
Total number of devices
2176 (does not include backplanes, power supplies, or I/O modules)
Hot-swappable
Yes
For product standards, general operating specifications, and installation requirements, refer to the
PACSystems RX3i
System Manual
, GFK-2314.