This chapter describes the connector layout and cabling requirements on the RXi box IPC. Power
and communication connectors are described in this section.
All connectors are provided on the bottom panel of the IPC.
Summary of Cabled Ports
Port Name
Usage
Maximum Cable Length
Shielding
Required
24 VDC
Permanent
2
3 m (9.8 ft.)
No
Ethernet 1
Permanent
2
100 m (328 ft.)
Yes
1
Ethernet 2
Permanent
2
100 m (328 ft.)
Yes
1
RS-232 Serial
Permanent
2
10 m (32.8 ft.)
Yes
1
USB1
Maintenance
3
5 m (16.4 ft.)
Yes
1
USB2
Maintenance
3
5 m (16.4 ft.)
Yes
1
VGA Video
Permanent
2
7.6 m (25 ft.)
Yes
1
SD (Secure Digital) slot
Maintenance
3
NA
NA
Audio
Maintenance
3
2 m (6.5 ft.)
No
1
Shielding is required to be in compliance with the standards identified in Appendix A.
2
Can be permanently connected while the system is running.
3
Intended only for temporary connection.
Input Power
The IPC requires:
24VDC, 18–32V range, 48W power supply, Class 2 or LPS
The IPC is supplied with a Phoenix Contact part number
1827716 or 1851245 (spring loaded/quick release) power
terminal block for use with a power supply. The power
supply used must be a UL Listed (or equivalent) Limited
Power Source (LPS) or Class 2 power source.
FGND 0V +24V
Power cord
with 28 AWG –16 AWG wires
.
To connect the DC power supply, refer to “Initial Startup” in chapter 2.
Note:
There are no user-serviceable fuses in the IPC.