The ins tantane ous unit burdens a re lis ted in Ta bl e X.
TABLE X
RANGE
BURDENS AT MIN.
BURDENS IN
60 HZ
tCON-
MIN.
PICKUP
OHMS
(Z)
V.A. AT 5 AMPS
RELAYS
NEC-
TAP
TIMES PICKUP
CALCULATED FROM
ONLY
TIONS
AMPS
R
Jx
l
3
10
20
IMPEDANCE AT MIN.
(AMPS)
OHMS OHMS
OHMS
PICKUP (I2Z
)
0.5-4.0
LOW
0.5
12.7 11.5
17.1
9.6
8.7
8.2
427.5
HIGH
1.0
3.18 2.86
4.28
2.40 2.18 2.04
107.0
2.0-16.0
LOW
2.0
0.76 0.72
1.05
0.59 0.53 0.50
26.25
HIGH
4.0
0.189 0.180 0.261 0.147 0.133 0.125
6.63
10.0-80.0 LOW
10.0
0.042 0.029 0.051 0.029 0.026 0.024
1.28
HIGH
20.0
0.010 0.007 0.013 0.007 0.007 0.006
0.33
20.0-160.0 LOW
20.0
0.015 0.008 0.017 0.010 0.009 0.008
0.43
HIGH
40.0
0.004 0.002 0.004 0.002 0.002 0.002
0.10
RANGE
BURDENS AT MIN.
BURDENS IN
50 HZ
tCON-
MIN.
PICKUP
OHMS
(Z)
V.A. AT 5 AMPS
RELAYS
NEC-
TAP
TIMES PICKUP
CALCULATED FROM
ONLY
TIONS AMPS
R
Jx
z
3
10
20
IMPEDANCE AT MIN.
(AMPS)
OHMS OHMS
OHMS
PICKUP {I2Z
}
0.5-4.0
LOW
0.5
10.6
9.35 14.30
8.03
7.27
6.86
357.5
HIGH
1.0
2.65
2.38 3.57
2.00
1.81
1.70
89.25
2.0-16.0
LOW
2.0
0.64
0.59 0.875
0.49
0.441 0.417
21.875
HIGH
4.0
0.157 0.15 0.22
0.145 0.112 0.105
5.50
10.0-80.0 LOW
10.0
0.035 0.024 0.042
0.024 0.021 0.0197
1.05
HIGH 20.0
0.008 0.006 0.101
0.0054 0.0054 0.046
0.25
20.0-160.0 LOW
20.0
0.0125 0.007 0.014
0.008 0.0074 0.0065
0.35
HIGH 40.0
0.0027 0.0013
0.003 0.0015 0.0015
0.0015
t
LOW
=
t wo w�nd1n gs c onnected 1n
ser1es.
HIGH
=
t wo windings c onne c te d in pa rallel.
See in t e rnal-connect ions diagram for a dd itional informa t i on
CHARACTERISTICS
Pickup of these relays is defined as the c urre n t required to
close the con t a cts from the
0.5
time-dial positi on .
The pickup va�ue
of t he
IAC53
relays is wit hin
3%
of the t a p value .
The setting of the t ime d ia l determines the length of time the
unit require s to c los e its contac t s when t he c ur rent reaches the
pred e t e rmined va lue.
The con t acts a re jus t c losed when the d ia l is
s e t a t ze r o.
When the dia l is s e t at 10 , the d is k mus t t ra ve l t h e
ma xi mum distance to c l ose the conta c t s ; this gives the maximum t ime
s e tt ing.
The unit res e t s a t
80%
of the minimum c l os in g va l ue of
c urre n t .
9