background image

GEK-34055 

The  one  second  thermal  ratings  are  listed  in  Table  IV. 

TABLE  IV 

TIME  OVE RCURRENT  UNIT 

1-SEC.  RATING 

(AMPS) 

(AMPS) 

0.5  - 4. 0 

125. 0 

15.625 

1.5 - 12. 0  

260:0 

15.0 

260.0 

67,600 

For  ratings  of  less  than  one  second,  the  rating  may  be  calculated  according  to  the  formula 

where  T  is  the  time  in  seconds  that  the  current  flows. 

The  continuous  ratings  of  the  time  overcurrent  units  are  shown  in  Table  V. 

TABLE  V 

0. 5  - 4. 0  AW  RANGE 

TAP 

0. 5 

0. 6 

0. 7 

0.8 

1. 0 

1.2 

1.5 

2.0 

2.5 

3. 0 

4. 0 

RATING  3.5 

3.7 

4. 0 

4.5 

5.0 

5. 5 

6.0 

7.0 

8. 0 

9.0  10. 0 

1. 5 - 12. 0 

Af1> 

RANGE 

TAP  1.5 

2.0 

2.5 

3.0 

4.0 

7.0 

8. 0  10.0 

12.0 

RATING  9.5  10. 5  1L5  125"  1 4.0 

1

8.

0  19.0 

20.0 

20.0 

2. 0  - 15.0 

AMP 

RANGE 

TAP 

2. 0 

2.5 

3.0 

4.0 

5.0 

6.0 

7.0 

8. 0 

10. 0 

12. 0  

15. 0 

RATING  10. 0  1 1. 0   12. 0  13.0  15. 0  17.0  18.0  19. 0  20.0 

20.0 

20. 0 

INSTANTANEOUS  UNIT 

The  instantaneous  unit  has  a  double  wound  coil  for  operation  on  either  one  of  two  ranges.  Any  setting 

obtained  in  the  lower  range  (series  connected)  is  doubled,  .within  ±3�when  the  unit  is  connected  for  high 

range  operation  (parallel  connected). 

The  instantaneous  unit  has  a  continuous  rating  of  1.5  times  minimum  setting  or  25  amperes  whichever 

is  smaller.  Example:  The  2. 0-16. 0  ampere  instantaneous  unit  when  set  on  the  low  range  (2.0-8. 0  amperes) 

has  a  continuous  rating  of  3. 0  amperes,  and  when  connected  for  high  range  operation  (4.0-16. 0  amperes) 

has  a  continuous  rating  of  6.0  amperes.  The  continuous  and  one  second  ratings  for  the  instantaneous  unit 

are  shown  in Table  VI. 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание IAC77B

Страница 1: ...C77B FORM 800 AND UP IAC78A FORM 800 AND UP IAC78B FORM 800 AND UP TIME OVERCURRENT RELAYS GEK 34055C Supersedes GEK 340558 GENERAL ELECTRIC w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 3: ...TANEOUS UNIT 9 SETTING THE INSTANTANEOUS UNIT 9 PICK UP TESTS 10 TARGET AND SEAL IN UNIT 10 PICK UP AND DROPOUT TEST 10 INSTALLATION TESTS 10 TIME OVERCURRENT UNIT 10 TARGET AND SEAL IN UNIT 10 INSTANTANEOUS UNIT 11 PERIODIC CHECKS AND ROUTINE MAINTENANCE 11 TIME OVERCURRENT UNIT 11 INSTANTANEOUS UNIT 11 TARGET AND SEAL IN UNIT 11 CONTACT CLEANING 11 SYSTEM TEST 11 SERVICING 11 TIME OVERCURRENT UN...

Страница 4: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 5: ...elays for interphase faults residually connected can be utilized for single phase to ground faults Use of a is advantageous because it can be adjusted to provide more sensitive protection on connections for applying these relays are shown in Figures 14 and 15 A separate relay separate ground relay ground faults Typical In the application of IAC77 and 78 relays with automatic reclosing devices the ...

Страница 6: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 7: ...s up it raises a target into view which latches up and remains exposed until released by pressing a button beneath the lower left corner of the cover The instantaneous unit is a small hinge type unit which may be mounted on the front to the right of the shaft of the time overcurrent unit Its contacts are normally connected in parallel with the contacts of the time overcurrent unit and its coil is ...

Страница 8: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 9: ... 0 4 0 5 0 6 0 7 0 8 0 10 0 12 0 15 0 RATING 10 0 1 1 0 12 0 13 0 15 0 17 0 18 0 19 0 20 0 20 0 20 0 INSTANTANEOUS UNIT The instantaneous unit has a double wound coil for operation on either one of two ranges Any setting obtained in the lower range series connected is doubled within 3 when the unit is connected for high range operation parallel connected The instantaneous unit has a continuous rat...

Страница 10: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 11: ...TABLE VII TAP 0 2 2 0 D C RESISTANCE 10 OHMS 7 0 13 MIN OPERATING AMPERES 0 25 0 2 2 0 CARRY CONT AMPERES 0 3 3 0 CARRY 30 AMPS FOR SEC 0 03 4 0 CARRY 10 AMPS FOR lSEC l 0 25 30 0 60 HZ IMPEDANCE OHMS 52 0 0 53 If the tripping current exceeds 30 amperes an auxiliary relay should be used the connections being such that the tripping current does not pass through the contacts or the target and seal i...

Страница 12: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 13: ... 0 007 0 006 0 33 20 0 160 0 LOW 20 0 0 015 0 008 0 017 0 010 0 009 0 008 0 43 HIGH 40 0 0 004 0 002 0 004 0 002 0 002 0 002 0 10 Low means two windings connected in series High means two windings connected in parallel See Internal Connections diagram for additional information CHARACTER STICS Pick up of these relays is defined as the current required to close the contacts from the 0 5 time dial p...

Страница 14: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 15: ...d be at least 1 32 wipe on the seal in contacts 4 The targets in the seal in unit and in the instantaneous unit must come into view and latch when the armatures are operated by hand and should unlatch when the target release lever is operated 5 Make sure that the fingers and shorting bars agree with the internal connections diagram CAUTION EVERY CIRCUIT IN THE DRAWOUT CASE HAS AN AUXILIARY BRUSH I...

Страница 16: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 17: ...ctory to close its contacts from any time dial position at a minimum current within five per cent of the tap setting The unit resets at 85 percent of the minimum closing value PICKUP TEST Set the relay at the 0 5 time dial position and 2 0 amp tap Using the test connections of Figure 13 the main unit should close its contacts within 2 of tap value current l 96 2 04 amp TIME TEST Set the relay at t...

Страница 18: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...he time dial to the ZERO TIME DIAL POSITION 1 Increase the current slowly until the seal in unit picks up See Table XI Move the time dial away from the ZERO TIME DIAL position the seal in unit should remain in the picked t up position Decrease the current slowly until the seal in unit drops out See Table XI TABLE XI TAP PICK UP DROPOUT CURRENT CURRENT 0 2 0 15 0 195 05 OR MORE 2 0 1 50 1 95 55 OR ...

Страница 20: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 21: ...he Installation Section INSTANTANEOUS UNIT Check that the Instantaneous Unit picks up at the desired current level as outlined in the Acceptance Test Section TARGET AND SEAL IN UNIT 1 Check that the unit picks up at the values shown in Table XI 2 Check that the units drops out at 30 or more of tap value CONTACT CLEAN lNG For cleaning relay contacts a flexible burnishing tool should be used This co...

Страница 22: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 23: ... setting is within the limits shown above Then set at 1 2 T D S and restore pick up by adjusting the resistor Compensation should be rechecked after the resistor adjustment With the contacts just open check the current required to just close the contacts on each of the other taps This current should be within 3 of tap value With the time dial at No 10 time setting and the tap plug in the 2 amp tap...

Страница 24: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 25: ...should close with feeler gage in place TARGET AND SEAL IN UNIT Check steps 1 and 2 as described under Instantaneous Unit To check the wipe of the seal in unit insert a 0 012 inch feeler gage between the plastic residual of the armature and the pole piece with the armature held closed Contacts should close with the feeler gage in place RENEWAL PARTS It is recommended that sufficient quantities of r...

Страница 26: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 27: ...GAG ING AUXILIARY BRUSH CONNECTING PLUG TRAVELS Y4 INCH BEFORE ENGAGING THE MAIN BRUSH ON THE TERMINAL BLOCK FIG 1 8025039 CROSS SECTION OF DRAWOUT CASE SHOWING POSITION OF AUXILIARY BRUSH 14 P ___ __ ____ ___ w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 28: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 29: ..._ j JRUCTIONS TIME AMPERES INSTANTA1 1EOUS UNIT ADJUSTABL CORE TIME DIAL i ll DISK AND SHAFT INSTANTANEOUS TYPE I CYCLES UNIT MA IN STATIONARY BRUSH AND CONTACT ASSEMBLY MAGNET FIG 2 8041298 TYPE IAC77 800 SERIES RELAY REMOVED FROM CASE FRONT VIEW 15 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 30: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 31: ... UNIT RANGE SELECTOR LEADS GEK 34055 e FIG 3 8041297 TYPE IAC77 800 SERIES RELAY REMOVED FROM CASE REAR VIEH 16 0 CRADLE CAPACITOR w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 32: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 33: ... SI T SI r 5 2 6 SHORT FI NGERS FIG 4 01 65A7758 0 TYPE IAC77A 800 SERIES RELAY INTERNAL CONNECTIONS FRONT VIEW 17 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 34: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 35: ...S UNIT B t V 7 NOTE INST UNIT CONNS lSHOWN ARE FOR LOW RANGE OPERATIO FOR HIGH RA NGE OPERATION CONNECT B 0 TO TERMI NAL 5 4 C 6 TO TERMINAL 7 FIG 5 0246A2200 l TYPE IAC77B 800 SERIES RELAY INTERNAL CONNECTIONS FRONT VIEW 18 l f w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 36: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 37: ...NIT T SI Sl 1 5 2 6 SHORT Fl NGER FIG 6 0165A7781 0 TYPE IAC7RA 800 SERIES RELAY INTERNAL CONNECTIONS FRONT VIEW 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 38: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 39: ...Sl TARGET SEAL IN NOTE INSTANTANEOUS UNIT CONNECTIONS SHOWN ARE FOR LOW RANGE OPERATION FOR HIGH RANGE OPERATION CONNECT 8 0 TO TERMINAL 5 A 1C TO TERMINAL 7 FIG 7 0246A2286 l TYPE IAC78B 800 SERIES RELAY INTERNAL CONNECTIONS FRONT VIEW 20 1 i j t w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 40: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 41: ...2 4 GEK 34055 OPERATING TIME RANGE FOR ANY PICKUP SETTING 6 MULTIPLES OF PICK UP FIG 8 K 6306872 5 TIME CURRENT CURVE OF THE INSTANTANEOUS UNIT 21 10 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 42: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 43: ... F REL Y TAP SETTING FIG 9 010888940 2 TIME ClJRRENT CHARACTERISTICS OF 50 H TYPES IAC77 AND IAC78 800 SERIES RELAYS 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 44: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 45: ...o 5 o 6 o 7 o s o 10 12 2 012 51 3 0 4 0_ 5 0_ fi O 7 0 8 0_ 10 0 12 15 _ l 1 t 10 1 t r t I b 5 4 __ I 3 i C 2 Ci 0 I I E 2 1 I 4 1 1 71111 II so 10 J I I I I Ill MULTIPLES OF RELAY TAP SETTING I I I I IIIII AOJ U5TMEHTS IHST UNIT COHTl NUOUSL Y AOJU STABLE 1 1 1 l 21 1 l I I z 0 2 1 Ill Ol a II I I I I IIIII FIG 10 088880274 5 TIME CURRENT CHARACTERISTICS OF 60 H TYPES IAC77 AND IAC78 800 SERIES...

Страница 46: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 47: ...ILL 10 HOLES 19MM ISMM DRILL 2 HOLES CUTOUT MAY REPLACE DRILLED HOLES OPTIONAL 29 MM 1 1 6 PANEL ORILLlNG FOR 9JRFAC OUNTING TFRONT VIEW Fig 1 1 K 6209271 5 Outline and Panel Drilling for the IAC78B 800 Series Relay 24 t w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 48: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 49: ...INE u VIEW SH NtiNG A5SEMB Y OF HAROWAFiE FOR SURfACE WTG ON STEEL PANELS L DRILLING FOR SURFAC LNTING FRONT lEVi FIG 12 K 6209270 2 OUTLINE AND PANEL DRILLING FOR TYPES IAC77A IAC778 AND IAC78A 800 SERIES RELAYS 25 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 50: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 51: ...XLA13 TEST PLUG VARIABLE RESISTOR TO TIMER START TO ACCURATELY REPRODUCE RELAY CHARACTERISTICS ALL TESTS SHOULD BE MADE WITH RELAY IN CASE MIN RECOMMENDED VOLTS 120 AT RATED FREQUENCY FIG 13 K 6154399 7 TEST CONNECTIONS FOR TESTING PICK UP AND TIME CURVE OF IAC RELAYS 26 _ w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 52: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 53: ...1 1 5tH 1 1 l FIG 14 0246A6966 0 EXTERNAL CONNECTIONS OF FOUR IAC77A RELAYS USED FOR MULTI PHASE AND P ASE TO TO GROIJND FAULT PROTECTION OF A 3 PHASE CIRCUIT 27 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 54: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 55: ... 5 1 1 51H FIG 15 0246A6967 0 EXTERNAL CONNECTIONS OF FOUR IAC78A RELAYS PROTECTING A 3 PHASE CIRCUIT AGAINST MULTI PHASE AND PHASE TO GROUND FAULTS GENERAL ELECTRIC CO POWER SYSTEMS MANAGEMENT BUSINESS DEPT MALVERN PA 19355 c w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 56: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: