Time  Overcurrent  Relays  Type  lAC 

GEH-1753 

INSTANTANEOUS  UNIT 

INTRODUCTION 

The  instantaneous  unit  is  a  small  instantaneous 

hinge-type  unit  which  may  be  mounted  on  the  right 
front  side  of  the  induction  unit  (See  Fig. 

7). 

Its 

contacts  are  normally  connected  in  parallel  with 

the  contacts  of  the  main  unit.  Its  coil  is  connected 

in 

series  with  the  operating  coil  of  the  main  unit. 

When  the current reaches a predetermined value, 

the  instantaneous  unit  operates,  closing  the  contact 
rircuit  and  raising  its  target  into  view.  The  target 
latches  in  the  exposed  position  until  released  by 
pressing  the  button  beneath  the  lower  left-hand 
corner  of  the  relay  cover. 

APPLICATION 

The  instantaneous  unit  is  used  on  certain  lAC 

relay  models  to  provide  instantaneous  tripping  for 
current  exceeding  a  predetermined  value. 

OPERATING  CHARACTERISTICS 

The  instantaneous  element  operates  over  a 

to 

range  and  has  its  calibration  stamped  on  a  scale 

OP[IIATING 
COIL 

TAAGe:T 

CONTACTS 
MOVING 

CONTACT 

ASSEMBLY 

Fig.  7.  (8006998) 

Type  lAC  Relay  with  an 

Instantaneous  Unit. 

mounted  beside  the  adjustable  pole  piece. 

Time­

current  characteristics  are  shown  in  Fig. 

10. 

RATINGS 

The  instantaneous  unit  is  designed  to  use  either 

of  two  coils  having  pickup  ranges  of 

10 

to 

40, 

and 

20 

to 

80 

amperes  respectively.  The current-closing 

rating  of  the  contacts  is 

30 

amperes  for  voltages 

not  exceeding 

250 

volts. 

BURDENS 

Burden  data  on  the  instantaneous  unit  coils  are 

given  in  the  following  table: 

Coil 

Freq.  Amp. 

Volt 

Imp. 

Amp 

Ohms 

10-40 

60 

0.83 

0.033 

50 

0.80 

0.032 

25 

0.65 

0.027 

20-80 

60 

0.21 

0.008 

50 

0.20 

0.008 

25 

0.15 

0.007 

Fig.  8.  (8007060) 

Type  IAC  Relay  with  an 

A-C  Tripping  Unit. 

PF 

0.95 

0.95 

0.98 
0.95 

0.95 

0.98 

www 

. ElectricalPartManuals 

. com 

Содержание IAC60A

Страница 1: ...INSTRUCTIONS TIME GEI 19957G Supersedes GEI 19957F Insert Booklet GEH 1753 OVERCURRENT RELAYS Types IAC60A IAC60J IAC60B IAC61A GENERAL fjELECTRIC w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 2: ...DIRECTION OF TORQUE TrllW I r nli rrTtnwo iz l K 6154168 5 Typical External Connections For Three T e IAC60A Relays Used In Conjunction With One TYPe CAP15A And Two Type HGA Relays For Direc tional O...

Страница 3: ...1 r l t rr1 1r1 110 INSTUTANEOUS l Hli TS K 6400341 5 Internal Connections For Tyre IAC60J Relay Front View Ttme OvercurrentRelays Type lAC GEI 19957 1 PUND SHADING 1 COILS SEAL IN I UN I T I I N N D...

Страница 4: ...1 125 OR STUD r 504MM 19 B75 _ _ i 18 3 slg s 4 SURFACE MTG Y OUTLINE lo 32 X MT 5t 4M 144MM SCREWS 6 z1s 1s s7 t 19 MI 7 781 L CUT I 9SMM 5 502 L 1 I DRILc OUT b l I I 252MM 9 937 504 19 8 p CASE MM...

Страница 5: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 6: ...GENERAL ELECTRIC COMPANY POWER SYSTEMS MANAGEMENT BUSINESS DEPT PHILADELPHIA PA 19142 GENERAL ELECTRIC 3 80 2 65 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 7: ...INSTRUCTIONS TIME OVERCURRENT RELAYS TYPES IAC51A IAC52A IAC51B IAC52B IAC51R GENERAL fjELECTRIC GEH 1753J w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 8: ...AL IN UNIT STATIONARY CONTACT LEFT SEAL IN UNIT STATIONARY CONTACT RIGHT SEAL IN MOVING CONTACT ASSEMBL t DISK AND SHAFT l__ A 6006996 Front VieW l OWER JEWEL SCREW DRAG IE MAGNET B 8006997 Rear Vie l...

Страница 9: ...ive the proper contact closing current and its motion is retarded by a permanent magnet acting on the disk to give the correct time delay There is a seal in unit mounted on the front to the left of th...

Страница 10: ..._ r I t t r r r k l _ t r _ r r r I _ r I 4 I I l I I 10 r r 20 1 10 r r 1 9 1 t 1 8 1 r lg tJt I c I 4 r t r 3 G f r r 2 r c r 0 t I r G E t r 1 30 40 50 80 70 80 110 MULTlPLES OF RELAY TAP SETTING...

Страница 11: ...Iv II v I v 0 Time Overcurrent Relays Type IAC GEH 1753 BURDENS Burdens for the standard coils are given in the following table These are calculated burdens at five amperes based on burden of minimum...

Страница 12: ...l TRJPP t ACTOR i f q T ll l 1 t Fig 5 K6375668 l External Connections of Three Type IAC51A Relays used in Conjunction with Tripping Reactors for Protection of aTThree Phase Circuit 6 A C BUS ill z 3...

Страница 13: ...ng a predetermined value OPERATING CHARACTERISTICS The instantaneous element operates over a 4 to 1 range and has its calibration stamped on a scale OP IIATING COIL 11 1 1 TAAGe T STATIONARY CONTACTS...

Страница 14: ...ormer Normally most of the flux generated by the main REA coil passes through the upper limb of the magnetic structure and holds the armature firmly against this limb When the contacts of the inductio...

Страница 15: ...ed as a part of a control panel will be shipped in cartons designed to yrotect them against damage Immediately upon receipt of the relay an examination should be made for any damage sustained during s...

Страница 16: ...A C RIP UNIT INSTANT uu Fig 13 K 6209294 3 Internal Connections for the Type IAC51R Relay Front View SEAL IN UNIT Sl INDUCTION 2 INDUCTION UNIT 6 SHORT FINGER Fig 14 K 6209662 5 Internal Connections f...

Страница 17: ...the various relay types are shown in Fig 11 to 17 inclusive Typical wiring diagrams are given in Fig 4 to 6 inclusive One of the mounting studs or screws should be permanently grounded by a conductor...

Страница 18: ...The primary adjustment for the time of opera tion of the unit is made by means of the time dial However further adjustment is obtained by moving the permanent magnet along its supporting shelf moving...

Страница 19: ...edge of the stationary contact sup porting post 2 ARMATURE ADJUSTMENT Loosen the two screws which hold the armature assembly bracket to the bottom of the frame Slide the bracket in or out whichever i...

Страница 20: ...ctory PERIODIC TESTING An operation test and inspection of the relay at least once every six months are recommended Test connections are shown in Fig 18 RENEWAL PARTS It is recommended that sufficient...

Страница 21: ...UIIBER INC FRONT VIEW FIG 6 I i l 3 5 7 9 100000 _00000 2 6 B 10 PANEL Rl Lll NG SENI Fl SH MTG FIG A 8 SURFACE WTG VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE WTG ON STEEl PANELS DR Ill 2 HOLES DRI...

Страница 22: ...GE Power Management 215 Anderson Avenue Markham Ontario Canada L6E 183 Tel 905 294 6222 Fax 905 201 2098 www ge com indsys pm w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: