Wiring

Match your transmitter with the corresponding diagrams 
(Figure 4 through Figure 9), set the switches and wire 
accordingly. (See Figure 3 below for switch and terminal 
block locations.) Ensure that all the installation and wiring is 
in compliance with all national and local codes.

Note:

All Voltage Outputs are measured with respect to the 
POWER SUPPLY / CONTROLLER GROUND.

Wiring for the transmitter should be a shielded, twisted pair, 
16-22 AWG. Use only copper conductors. Do not run 
transmitter wires and AC power wires together in the same 
conduit or wire bundle.

Caution!

Running transmitter wires and AC power wires, 

including earth ground, in the same conduit or 

wire bundle may cause malfunction due to 

electrical noise.

Figure 3: Connector/Switch Locations - Inside Cover

Figure 4: Switch Positions for Voltage Mode

Figure 5: DP/EN/WB and Temp. (Direct Connection) - 

Voltage

Figure 6: DP/EN/WB and Temp. (Signal Condition) - 

Voltage

Figure 7: Switch Positions for Current Mode

Figure 8: DP/EN/WB and Temp. (Direct Connection) - 

Current

Figure 9: DP/EN/WB and Temp. (Signal Condition) - 

Current

Wiring (cont.)

Figure 10: Remove/Install the Sensor Tip

J7

10V

SW2

5V

J8

Voltage

Current

SW3

SW1

V

I

V

I

JPR1

3K

10K

SW3

SW1

V

I

V

I

XR 0-5/0-10Vout

Switch Selectable 0-5 Volt or 0-10 Volt Output

I1XR/P+

I2XR/P–

V-XR

GND

V-TMP

J7

10V

SW

2

5V

–GND, 0-5/0-10Vout

+V

J8

TH

TH

I2-TMP

I2XR/P–

I1XR/P+

Thermistor Output*

Voltage

*To provide a connector for Thermistor

Output, divide the 5-pin terminal block into

a 3-pin and a 2-pin terminal block as shown.

XR REPRESENTS

Dew Point - DP

Enthalpy - EN

Wet Bulb - WB

Switch Selectable 0-5 Volt or 0-10 Volt Output

I1XR/P+

I2XR/P–

V-XR

GND

V-TMP

J7

10V

SW

2

5V

+V

Voltage

–V

XR

GND

Temp

XR REPRESENTS

Dew Point - DP
Enthalpy - EN

Wet Bulb - WB

SW3

SW1

V

I

V

I

J8

TH

TH

I2-TMP

I2XR/P–

I1XR/P+

Current*

V in

XR (4-20mA) out

Thermistor Output

*Shipped in 4-20mA output.

XR REPRESENTS

Dew Point - DP

Enthalpy - EN

Wet Bulb - WB

J8

TH

TH

I2-TMP

I2XR/P–

I1XR/P+

Current*

V in

XR RTN

Temp RTN

*Shipped in 4-20mA output.

XR REPRESENTS

Dew Point - DP

Enthalpy - EN

Wet Bulb - WB

CE COMPLIANCE

1.

Ensure that the probe earth ground wire (for Duct and 

Outside Air units only), the shield wire and the PCB earth 

ground wire are connected to the mounting screw or the 

NEAREST (<1.5m) earth ground.

2.

The other end of the shield wire MUST be connected to 

the power supply /controller earth ground ONLY.

Table 1:  HumiTrac XR Ordering Information

Model

Product Information

Space 

(Wall) 

Mount

HUMI-DP-XR-S

DEW POINT TRANSMITTER-SPACE MOUNT

HUMI-EN-XR-S

ENTHALPY TRANSMITTER-SPACE MOUNT

HUMI-WB-XR-S

WET BULB TRANSMITTER-SPACE MOUNT

Duct Mount

HUMI-DP-XR-D

DEW POINT TRANSMITTER-DUCT MOUNT

HUMI-EN-XR-D

ENTHALPY TRANSMITTER-DUCT MOUNT

HUMI-WB-XR-D

WET BULB TRANSMITTER-DUCT MOUNT

Air Mount

HUMI-DP-XR-O

DEW POINT TRANSMITTER-OPEN AIR

HUMI-EN-XR-O

ENTHALPY TRANSMITTER-OPEN AIR

HUMI-WB-XR-O

WET BULB TRANSMITTER-OPEN AIR

Hold the sides of 

the sensor tip

the sintered filter.

near the base of

Caution:  Remove power before replacing the sensor.

Отзывы: