GE HumiTrac XR Series Скачать руководство пользователя страница 1

GE

HumiTrac™ XR Transmitter Series

Sensing & Inspection Technologies

Installation Guide

A40254250

,Rev. A (August 2009)

Page 1 of 2     

Warranty

GE Sensing & Inspection Technologies warrants equipment 
of its manufacture to the original buyer against defective 
materials or workmanship, for a period of one year for the 
sensor tip and two years for the rest of the product, from the 
date of shipment. The sensor element and calibration are not 
covered by this warranty.

Calibration

All GE Sensing & Inspection Technologies RH/Dewpoint 
and Temperature Products are fully tested and calibrated in 
accordance with the National Institute of Standards and 
Technology (NIST) prior to shipment. This is the highest 
quality calibration standard available.

Power Requirements

12–30 VDC power supply (furnished by the customer).

Specifications

Contact Information

To contact the factory, use the following information:

GE Sensing & Inspection Technologies
1100 Technology Park Drive
Billerica, MA 01821-4111
Web: www.gesensing.com
Telephone: +1 814-834-9140 or 800-321-4878

HumiTrac Information

For information specific to the 

HumiTrac

, see the website 

www.humitrac.com

.

Installation

For your convenience, the transmitters can be mounted
using the base as a mounting template (see Figure 1 or 2).

Wall Mount

Locate the transmitter where it will be exposed to an
unrestricted air circulation that is representative of the
average humidity and/or temperature of the controlled
space. Avoid locations where excessive moisture, corrosive
fumes, vibration, or high ambient temperatures are present.

The wall mount transmitter is designed to install onto a
standard electric switch box

Mount the transmitter on an

indoor wall approximately 4 to 6 feet above the floor. The
base assembly should be positioned with the letters 

FR/ABS

located on the left side.

Figure 1: Wall Mount - Mounting Dimensions

Duct Mount

The transmitter should be mounted away from fans, corners, 
heating and cooling coils, and other equipment that will 
affect the measurement of relative humidity. It should be 
mounted in a location that receives adequate air flow for 
proper operation.

The duct mount transmitter should be mounted so that the 
sensor probe is in the center of the duct. 

Outside Air Mount

The transmitter should be mounted in a sheltered area that is 
protected from rain. Ideally, the transmitter should be located 
on the north side of the building (under an eave) to prevent 
sun-heated air from rising up the building's wall and 
affecting the relative humidity of the sensor.

The outside air mount transmitter should be mounted with 
the sensor pointing down to prevent water collection in the 
sensor cavity.

Figure 2: Duct / Outside Air - Mounting Dimensions

 Environmental Conditions

Operating Range:

–40°F to 140°F (–40°C to 60°C)
0-99% RH non-condensing.

Storage Temperature:

–67°F to +185°F (–55°C to +85°C)

Sensing Element:

Capacitive Sensor

Long Term Stability:

Less than 1% drift per year, typical.

Temperature Effect:**

Delta %RH = 
       (0.0014 x %RH + 0.1325) x T°C –
            (0.0317 x %RH + 3.0876)

**Not needed for Signal-Conditioned Temperature units.

Signal Outputs:

4-20 mA, 0-5V or 0-10V (user selectable)

Space (Wall Mount) Range

Dew Point

40° to 90°F (4.4 to 32.2°C)

Enthalpy

0-50 BTU/lb (0-116.3 kJ/kg)

Wet Bulb

40° to 90°F (4.4 to 32.2°C)

Dry Bulb

40° to 90°F (4.4 to 32.2°C)

Duct/Outside Air Mount Range

Dew Point

-20° to 120°F (-28.8° to 49°C)

Enthalpy

0-50 BTU/lb (0-116.3 kJ/kg)

Wet Bulb

0° to 100°F (-17.8° to 37.8°C)

Dry Bulb

-20° to 120°F (-28.8° to 49°C)

Accuracy

Dew Point

±1.8°F (±1°C)

Enthalpy

±2 BTU/lb (±4.7 kJ/kg)

Wet Bulb

±3°F (±1.7°C)

Dry Bulb

±0.5°C (±0.9°F)

Certification

CE Marked
Complies with EMC Directive 89/336/EEC and LVD 73/23/EEC.
IP 42 rating for Duct Mount and Outside Air Transmitters.

FR

ABS

2.37 (60.3)

2.37

(60.3)

3.30

(83.8)

3.79 (96.2)

4.69

(119.1)

*

*

Notes:
1. Dimensions are in inches (millimeters).

2. 

*

To open the enclosure, squeeze the base

       where indicated, and remove the cover.

1.50 (38.1)

1.75

(44.5)

3.79 (96.2)

4.69

(119.1)

*

Ø.188 (4.76)

mounting hole, 4 pl.

Ø.50

(12.7)

Notes:
1. Dimensions are in inches (millimeters).
2. Ensure the Duct Probe doesn't make any

    contact with the metal housing.

3. 

*

To open the enclosure, squeeze the base

     where indicated, and remove the cover.