Installation Instructions

CONNECTING DRYER USING 

3-WIRE CONNECTION

24” MODELS - CONNECTING AN ELECTRIC DRYER

3-wire Connection

NOT for use in Canada.
DO NOT use for Mobile Home Installations.
NOT for use on new construction.
NOT for use on recreational vehicles.
NOT for use in areas where local codes prohibit 
grounding through the neutral conduction.

CONNECTING DRYER USING 4-WIRE 

CONNECTION (MUST BE USED FOR 

MOBILE HOME INSTALLATION)

NOTE:

 Since January 1, 1996, the National Electrical 

Code requires that new constructions use a 4-wire 
connection to an electric dryer. A 4-wire cord must also 
be used where local codes do not permit grounding 
through the neutral.
3-wire connection is NOT for use on new construction.

1.

 Turn off the circuit breaker(s) (30 amp) or remove 

the dryer’s circuit fuse at the electrical box.

2.

 Be sure the dryer cord is unplugged from the wall 

receptacle.

3.

 Remove the power cord cover located at the lower 

back.

4.

 Remove and discard ground strap. Keep the green 

ground screw for Step 7.

5.

 Install 3/4 in. UL-recognized strain relief to power 

cord entry hole. Bring power cord through strain 
relief. 

6.

 Connect power cord as follows:

 

A.

  Connect the 2 hot lines to the outer screws of the 

terminal block (marked L1 and L2).

 

B.

  Connect the neutral (white) line to the center of 

the terminal block (marked N).

7.

 Attach ground wire of power cord with the green 

ground screw (hole above strain relief bracket). 
Tighten all terminal block screws (3) securely.

8.

 Properly secure power cord to strain relief.

9.

 Reinstall the cover.

NEVER LEAVE THE COVER OFF OF THE 

TERMINAL BLOCK.

NEVER LEAVE THE COVER OFF OF THE 

TERMINAL BLOCK.

L1

N

L2

RELOCATE GREEN
GROUND SCREW
HERE

STRAIN
RELIEF
BRACKET

GREEN OR
YELLOW WIRE

3/4", UL
RECOGNIZED
STRAIN RELIEF

HOT
WIRE

SCREWS
(3)

HOT WIRE

COVER 

NEUTRAL
(White)

REMOVE GROUND 
STRAP AND DISCARD.

 
KEEP GREEN
GROUND 
SCREW

4 #10 AWG MINIMUM COPPER
CONDUCTORS OR 120/240V 30A POWER
SUPPLY CORD KIT MARKED FOR USE
WITH DRYERS & PROVIDED WITH
CLOSED LOOP OR SPADE TERMINALS
WITH UPTURNED ENDS (NOT SUPPLIED).

L1

L2

STRAIN RELIEF
BRACKET

3/4", UL
RECOGNIZED
STRAIN RELIEF

HOT
WIRE

HOT
WIRE

GROUND
STRAP

GREEN
GROUND

SCREW

NEUTRAL
(White)

SCREWS
(3)

COVER

3 #10 AWG MINIMUM COPPER
CONDUCTORS OR 120/240V 30A POWER
SUPPLY CORD KIT MARKED FOR USE
WITH DRYERS & PROVIDED WITH
CLOSED LOOP OR SPADE TERMINALS
WITH UPTURNED ENDS (NOT SUPPLIED).

1.

 Turn off the circuit breaker(s) (30 amp) or remove 

the dryer’s circuit fuse at the electrical box.

2.

 Be sure the dryer cord is unplugged from the wall 

receptacle.

3.

 Remove the power cord cover located at the lower 

back.

4.

 Install 3/4-in. UL-recognized strain relief to power 

cord entry hole. Bring power cord through strain 
relief. 

5.

 Connect power cord as follows:

 

A.

  Connect the 2 hot lines to the outer screws of the 

terminal block (marked L1 and L2).

 

B.

  Connect the neutral (white) line to the center of 

the terminal block (marked N).

6.

 Be sure ground strap is connected to neutral 

(center) terminal of block and to green ground 
screw on cabinet rear. Tighten all terminal block 
screws (3) securely.

7.

 Properly secure power cord to strain relief.

8.

 Reinstall the cover.

Содержание GUD27GSSM2WW

Страница 1: ...gas connector when used must not exceed 4 feet FOR GAS DRYERS ONLY 2 Strainer Screens Rubber Washers 2 Washer Hoses 1 Cable Tie 234D2665P001 31 16781 3 08 18 GEA Unitized Washer Dryer 01 Installation...

Страница 2: ...door closed including handle and knobs FOR GAS DRYERS ONLY Gas Inlet Rear View of Appliance 2 24 NOMINAL PRODUCT DIMENSIONS 24 5 8 43 33 7 8 27 3 8 32 3 4 51 18 Water Inlets rear Drain outlet rear Ve...

Страница 3: ...of 72 square inches of open area for 24 width models 120 square inches of open area for 27 width models NOTE WHEN THE EXHAUST DUCT IS LOCATED AT THE REAR OF THE DRYER THE CONFIGURATION OF THE DUCTING...

Страница 4: ...d old flexible gas connector and ducting material Shut off Valve MATERIALS YOU WILL NEED 4 dia metal elbow Pipe compound or PTFE tape Flexible gas line connector Duct clamps 2 or Spring clamps 2 Safet...

Страница 5: ...ted connector ANSI Z21 24 CSA 6 10 The length of the connect shall not exceed 4 ft Use a new CSA International approved flexible gas supply line Never reuse old flexible connectors Install an individu...

Страница 6: ...tor 27 ONLY New metal flexible gas line connector Adaptor 1 8 NPT pipe plug for checking gas inlet pressure 6KXW 2 YDOYH Pipe size at least 1 2 Floor 24 27 Tighten the flexible gas line to the adaptor...

Страница 7: ...ed 3 prong grounding type receptacle GROUNDING INSTRUCTIONS This appliance must be grounded In the event of a malfunction or breakdown grounding will reduce the risk of electric shock by providing a p...

Страница 8: ...pliers Flat blade screwdriver 1 4 Nutdriver Level 4 dia UL listed flexible metal duct if needed Appliance power cord kit not provided with appliance UL rated 120 240V 30A with 3 or 4 prongs Identify...

Страница 9: ...unded cord connected dryer This appliance must be grounded In the event of a malfunction or breakdown grounding will reduce the risk of electric shock by providing a path of least resistance for elect...

Страница 10: ...securely 8 Properly secure power cord to strain relief 9 Reinstall the cover NEVER LEAVE THE COVER OFF OF THE TERMINAL BLOCK NEVER LEAVE THE COVER OFF OF THE TERMINAL BLOCK L1 N L2 RELOCATE GREEN GROU...

Страница 11: ...cord to strain relief 9 Reinstall the cover NEVER LEAVE THE COVER OFF OF THE TERMINAL BLOCK NEVER LEAVE THE COVER OFF OF THE TERMINAL BLOCK 1 Turn off the circuit breaker s 30 amp or remove the dryer...

Страница 12: ...uct In Canada and the United States only transition ducts that comply with UL 2158A STANDARD FOR CLOTHES DRYER TRANSITION DUCT shall be used Avoid resting the duct on sharp objects For best drying per...

Страница 13: ...of the system including the transition duct EXHAUST LENGTH DO NOT bend or collapse ducting Use elbows if turns are necessary DO NOT use excessive exhaust length Cut duct as short as possible DO NOT cr...

Страница 14: ...uld require little or no maintenance to prevent clogging Wall caps must be installed at least 12 above ground level or any other obstruction with the opening pointed down SEPARATION OF TURNS For best...

Страница 15: ...esired Rotate elbow sections so that the opening points to the side to which you want to vent Preassemble 4 elbow with 4 duct Use only 4 UL approved rigid metal for ducting inside the dryer Insert duc...

Страница 16: ...CETS Must be within 42 of the appliance water inlet hose connections The faucets must be 3 4 garden hose type so inlet hoses can be connected WATER PRESSURE Must be between 20 and 120 pounds per squar...

Страница 17: ...appliance in its final position place a level on top of back part of the washer lid and check it side to side then check front to back Screw the front leveling legs up or down to ensure the appliance...

Страница 18: ...18 Notes...

Страница 19: ...19 Notes...

Страница 20: ...20 Printed in Mexico...

Страница 21: ...AS A GAS NICAMENTE Instrucciones de Instalaci n Secadora Unificada a Lavadora 01 PIEZAS PROVISTAS 2 Pantallas de Filtro Arandelas de Caucho 2 Mangueras de desag e para lavadora 1 Enlace de cables NOTA...

Страница 22: ...to 2 27 DIMS NOMINALES DEL PRODUCTO 3 SECADORAS A GAS NICAMENTE Entrada para el gas Vista trasera del aparato 3 NOTA Con las patas en la posici n intermedia stas se pueden ajustar en 3 8 Mangueras y p...

Страница 23: ...s de 24 de ancho 120 pulgadas cuadradas de espacio abierto para los modelos de 27 de ancho NOTA CUANDO EL CONDUCTO DE SALIDA EST UBICADO EN LA PARTE TRASERA DE LA SECADORA LA CONFIGURACI N DEL DUCTO P...

Страница 24: ...erial del conducto V lvula de cierre MATERIALES NECESARIOS Codo de metal de 4 di metro Compuesto o PTFE cinta para tuber as Conector de tuber a de gas flexible Abrazaderas de tuber a 2 o abrazaderas d...

Страница 25: ...r la muerte una explosi n o incendio La instalaci n deber ser conforme con los c digos locales o en ausencia de los c digos locales con el C digo Nacional de Gas Combustible National Fuel Gas Code ANS...

Страница 26: ...lvula de cierre Tama o de la tuber a de por lo menos Piso 24 27 Ajuste la l nea de gas flexible al adaptador usando 2 llaves de ajuste 27 Aplique compuesto para tuber a al adaptador y a la entrada de...

Страница 27: ...orriente de salida Recept culo de 3 clavijas debidamente conectado a tierra deber n colocarse de modo que el cable de alimentaci n est accesible cuando la secadora est instalada en su posici n final S...

Страница 28: ...ados planos Llave para turcas de 1 4 Nivel Conducto de metal flexible de 4 de di metro si fuese necesario Kit de cable de energ a de el electrodom stico no incluido con el electrodom stico Clasificado...

Страница 29: ...e electrodom stico deber estar conectado a tierra En caso de mal funcionamiento o aver a la conexi n a tierra reducir el riesgo de descargas el ctricas al brindar un camino con una resistencia menor p...

Страница 30: ...alivio de tensi n de 3 4 pulgadas reconocido por UL en el orificio de entrada del cable de energ a Pase el cable de energ a a trav s del alivio de tensi n 5 Conecte el cable de energ a de la siguiente...

Страница 31: ...livio de tensi n de 3 4 pulgadas reconocido por UL en el orificio de entrada del cable de energ a Pase el cable de energ a a trav s del alivio de tensi n 5 Conecte el cable de energ a de la siguiente...

Страница 32: ...ar o doblar CONDUCTO DE TRANSICI N DE METAL FLEXIBLE SECADORA DE ROPA DE LA LISTA DE UL Si un conducto de metal r gido no puede ser utilizado entonces un conducto de metal flexible aprobado por UL pue...

Страница 33: ...de transici n LONGITUD DE SALIDA NO doble o pliegue los conductos Utilice codos si algunos codos resultan necesarios NO utilice una longitud de salida excesiva Corte los conductos con la longitud m s...

Страница 34: ...hacia abajo SEPARACI N DE CURVAS Para un mejor desempe o separe todas las curvas con 4 pies de conducto recto como m nimo incluyendo la distancia entre la ltima curva y la cubierta de pared con regul...

Страница 35: ...interno de la secadora Aseg rese de no tirar o da ar los cables el ctricos ubicados dentro de la secadora cuando introduzca el conducto Aplique cinta aislante como puede verse en la junta entre el co...

Страница 36: ...STRO DE AGUA GRIFOS DE AGUA CALIENTE Y DE AGUA FR A Deben estar dentro de las 42 de las conexiones de la manguera de entrada de agua del electrodom stico Los grifos deben ser del tipo para manguera de...

Страница 37: ...n el electrodom stico en su ubicaci n final coloque un nivel sobre la parte trasera de la tapa de la lavadora y controle la misma de un costado a otro y luego de adelante hacia atr s Atornille las pat...

Страница 38: ...Notas 18...

Страница 39: ...19 Notas...

Страница 40: ...20...

Отзывы: