background image


 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

Ref.No 

 

Description 

Catalog 

Number 

Quantity 

Required 









10 
11 

Coil retainer assembly 
Overload relay (3-heater, non-compensated form, 1 NC contact) 
Overload relay (3-heater, non-compensated, 1 NO-1 NC contacts) 
Set of stationary and movable contacts with springs and screws for 3 poles           
Molded cover for stationary and movable contacts 
Return spring for movable contact support 
Molded movable contact support for 2, 3 poles 
Armature and frame (magnet) with retainer 
Operating coil for 2-and 3-pole forms 
Spring retainer for armature 
Cross electrical interlock 

 546A780G052 

CR324D310F 
CR324D360F 

546A780G051 
546A780G054 
547A524G001 
188D700P001 
546A780G053 

15D22G*** 

546A627P001 

CR305X200C 











CHECK FOR WELDED CONTACTS IN 
OVERLOAD RELAY

  

This feature permits the maintenance 
man to check for welded relay contacts 
by simply depressing the white operator 
located at the top of the overload relay 
contact housing. When the relay is in the 
reset condition, an audible “click” will be 
heard when the operator is depressed, 
indicating that the contacts are 
operating normally. A continuity check 
can also be made by disconnecting the 
control wiring from the terminals of the 
relay and placing a bell set or a 
resistance measuring instrument in the 
circuit. Connecting either of these across 
the relay terminals will indicate the relay 
contact is closed until the contact-check 
operator is depressed, opening the 
circuit.  
The exclusive manual contact operation 
check gives positive assurance that 
contacts have not welded due to short 
circuits in the control wiring. 

SIMPLE MAINTENANCE

  

300/400-Line starters and contactors require 
virtually no corrective maintenance. Preventive 
maintenance will assure many years of 
dependable on-line service.  

1.

 Always remove power from device before 

performing any maintenance.  

2.

 Keep magnet mating surfaces free of 

accumulated dirt or dust.  

3.

 DO NOT OIL OR GREASE the magnet mating 

surfaces.  

4.

 Contacts are carefully designed for 

maximum life. They need only be replaced 
when nearly all the silver tip is gone and the 
contact tip support is ex posed. DO NOT FILE 
the contacts. Filing or otherwise dressing the 
contacts only results in lost tip material and 
reduces contactor or starter life.  

5.

 The ultimate tripping current of the installed 

relay heater can be adjusted ±10% by using 
adjustment dial.

 

Accessory Kits 

1 st NO aux. cont. (rt.side mtg)………………..CR3O5X200A  
1 st NC aux. cont. (rt.side mtg)…………………CR3O5X200B  
1 st NO-NC aux. cont.for (rt.side mtg)……CR3O5X200C  
Additional NO aux. cont. for all forms……CR3O5X100D  
Additional NC aux. cont. for all forms ….CR3O5X100E  
Pushbutton………………………………………………….. CR305X220N  
Selector switch, H—O—A. …………………………CR305X230N  
Selector switch, OFF—ON. ……………………… CR305X230D 
Indicating light. …………………………………………  CR305X250N  
Fifth pole.(for adding to  
4-pole form only)………………………………………. CR3O5X211B  
Control circuit fuse……………………………………. CR305X241A, B, C, D

  

 
*** 

Coil Data

 

 

For three-pole device, order Catalog Number 
15D22G plus number in table below.

 

Frequency 

115V 

200/ 

208V 

230V 

460V 

575V 

600V 

60Hz 

002 

023 

003 

004 

005 

006 

 

Frequency 

110V 

220V 

380V 

440V 

550V 

600V 

50Hz 

007 

008 

064 

009 

010 

011 

 

*** Add suffix numbers for particular coil rating required. See COIL TABLE above

 

General Electric Company  
41 Woodford Avenue, Plainville, CT 06062 
GEH-4776B 08/10, 10-2049 © 2010 General Electric 
Visit us on the web at www.Geindustrial.com                                  

1.

 Perform steps 1 through 5 

under “Coil Removal”.  

2.

 Remove magnet from 

molded cover and movable 
arm.  

3.

 Remove return spring from 

center of movable arm.  

4.

 Remove molded cover from 

movable arm.  

5.

 Depress and slide movable 

contact, spring, and spring 
seat from movable arm.  

6.

 Remove screws holding 

stationary contacts in place 
and remove stationary 
contacts 
 

PRINCIPAL RENEWAL PARTS  

Use 022 for 120V, 60 Hertz/110V, 50Hertz coil. 

7.

 Reassemble device by reversing 

procedure.  

NOTE:

 Do not attempt to remove or replace 

arc traps in arc chute cover.  
         When reassembling, note that the arc 
chute cover will only fit one way and is 
marked “TOP” in upper right hand corner. 
Magnet and movable arm will fit either way 
but will be quieter if reassembled the same 
way they were taken apart.  
 