Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E
RSTi-EP User Manual
184
Overview of the Editable Parameter EP-5112
Channel
Description
Options (
†
)
Default
Diagnostic alarm
disabled (0) / enabled (1)
disabled
0 ... 1
Filter time signal A
0,01 ms [100 kHz] (0) / 0,017 ms [50 kHz] (1) / 0,033 ms [30 kHz] (2)
/ 0,1 ms [10 kHz] (3) / 0,2 ms [5 kHz] (4) / 0,5 ms [2 kHz] (5) / 1 ms
[1 kHz] (6)
0,01 ms
0 ... 1
Filter time signal B
0,01 ms [100 kHz] (0) / 0,017 ms [50 kHz] (1) / 0,033 ms [30 kHz] (2)
/ 0,1 ms [10 kHz] (3) / 0,2 ms [5 kHz] (4) / 0,5 ms [2 kHz] (5) / 1 ms
[1 kHz] (6)
0,01 ms
0 ... 1
Process alarm
overflow
disabled (0) / enabled (1)
disabled
0 ... 1
Process alarm
underflow
disabled (0) / enabled (1)
disabled
0 ... 1
Process alarm comp.
value
disabled (0) / enabled (1)
disabled
0 ... 1
Process alarm end
value
disabled (0) / enabled (1)
disabled
0 ... 1
Counting mode
count endless (0) / once - forward (1) / once - backwards (2) /
once - no main direction (3) / periodic - forward (4) / periodic -
backwards (5) / periodic - no main direction (6)
count
endless
0 ... 1
Comparison function
disabled (0) / higher equal comparison value (1) / lower equal
comparison value (2)/ equal comparison value (3)
disabled
0 ... 1
Counter dir. signal B
inv.
disabled (0) / enabled (1)
disabled
0 ... 1
Signal mode
Rotary transducer - single (0) / Rotary transducer - double (1) /
Rotary transducer - quadruple (2) / Pulse and Direction (3) /
disabled (4)
disabled
0 ... 1
Counter behavior
internal gate
Interrupt counting (0) / Cancel counting (1)
interrupt
counting
0 ... 1
Setting value
-2147483648 to 2147483647
0
0 ... 1
End value
-2147483648 to 2147483647
2147483647
0 ... 1
Load value
-2147483648 to 2147483647
0
0 ... 1
Hysteresis
0 to 255
0
Note:
The parameter setting in the network adapter for the Behaviour of outputs on fieldbus error
affects the control word and thus the behavior of the EP-5112:
•
The Hold last value setting - The counter continues to count during the error. Once
normal operating conditions have been restored, the counter continues to count starting
at the previous value.
•
The Enable substitute value setting - The counter value is frozen. Once normal operating
conditions have been restored, the counter value is reset to the parameterised load
value.
•
All outputs off setting - The counter behaves in the same way as for Hold last value.
Содержание GFK-2958E
Страница 1: ...RSTi EP User Manual GFK 2958E November 2017 ...
Страница 23: ...Chapter 1 Introduction GFK 2958E RSTi EP User Manual 19 Notes ...
Страница 56: ...Chapter 3 Configuration GFK 2958E RSTi EP User Manual 52 Notes ...
Страница 166: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 162 EP 5111 Block Diagram EP 5111 ...
Страница 183: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 179 EP 5111 ...
Страница 184: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 180 EP 5111 ...
Страница 211: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 207 Frequency Counter EP 5212 ...
Страница 316: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 312 Notes ...
Страница 330: ...Chapter 6 Installation GFK 2958E RSTi EP User Manual 326 Notes ...
Страница 344: ...Chapter 7 Earthing and Shielding GFK 2958E RSTi EP User Manual 340 ...
Страница 345: ...Chapter 7 Earthing and Shielding GFK 2958E RSTi EP User Manual 341 Notes ...
Страница 385: ...Chapter 8 Web Server GFK 2958E RSTi EP User Manual 381 Notes ...
Страница 401: ...Chapter 11 Disassembly and Disposal GFK 2958E RSTi EP User Manual 397 Notes ...
Страница 413: ...Chapter 12 LED Indicators and Troubleshooting GFK 2958E RSTi EP User Manual 409 Notes ...
Страница 416: ...Chapter 14Accessories and Replacement Parts GFK 2958E RSTi EP User Manual 412 Notes ...