4. To guarantee the enough space for heat dissipation and facilitate the installation and removal, 
the spacing around the inverter should meet the requirements as demonstrated in the following 
illustration.

4.2.2 Mounting procedure

1. Use the wall-mount bracket as a template and drill holes with 10mm in diameter and 80 mm in 

depth on the wall.

2. Fix the wall-mount bracket on the wall with the expansion bolts in the accessories bag.
3. Hold the inverter by the side groove.
4. Mount the inverter onto the wall-mount bracket.

200mm

200mm

300mm

500mm

300mm

Upward
Downward
Front
Both sides

-------------300mm

---------500mm

----------------300mm

----------200mm

120mm

329mm

A  lock  could  be  used  for  anti-theft  if  it  is 
necessary for individual requirement.

Step 1: 

Put AC cable through terminal cover follow the sequence.

Step 2: 

Press the 3 connectors on cable conductor core tightly.

Grade

A
B
C
D

Description

Outside diameter
Separated wire length
Conductor wire length
Conductor core section

Value

13~18mm
20~25mm
7~9mm
2.5~10mm

2

D

A

B

Annealed copper wire

C

Cables

Screw cap

AC sheet cover

Single hole

seal ring

The insulator

Inverter

GEP4.6-1C-10/GEP5.0-1C-10
GEP7.0-1-10
GEP8.5-1-10/GEP9.0-1-10/GEP10-1-10

Conductor core section

2.5mm

2

4mm

2

10mm

2

4.3 Electrical Connection

4.3.1 AC Side Connection

1. When connecting the inverter, please make sure to adjust the voltage and the frequency in 

compliance with grid regulations and the specifications of the inverter installed. 

2. Add a breaker or fuse to the AC side. Please note that the specification should be more than 1.25 

times the rated AC output current.

3. The PE wire of the inverter should be connected to earth. Make sure the impedance of neutral 

wire and earth wire is less than 10Ω.

4. Disconnect the breaker or fuse between the inverter and the utility.
5. When laying the AC Wire make sure that the protective earthing conductor is not strained.

07

08

Содержание GEP5.0C

Страница 1: ...3 support au gesolarinverter com sales au gesolarinverter com Global Sales Service Network GEP 4 6 10KW SINGLE PHASE USER MANUAL GE is a registered trademark of General Electric Company and is used un...

Страница 2: ...l Connection 08 4 4 Communication Connection 12 5 System Operation 16 5 1 LCD Panel 16 5 2 User Interface and System Configuration 17 5 3 Wi Fi LAN Reset Wi Fi LAN Reload 22 5 4 Precaution for Initial...

Страница 3: ...d to prevent such damage otherwise the warranty may be null and void Ensure the output voltage of the proposed PV array is lower than the maximum rated input voltage of the inverter otherwise the inve...

Страница 4: ...y extension solution for our customer For further details please visit www gesolarinverter com Item 1 2 3 4 5 6 7 8 9 Name DC Switch PV Input Terminal Wi Fi LAN Module Optional DRED Function Optional...

Страница 5: ...be installed near flammable and explosive items Strong electro magnetic charges should be kept away from installation site 4 Product label and warning symbols should be located and placed in a manner...

Страница 6: ...Grade A B C D Description Outside diameter Separated wire length Conductor wire length Conductor core section Value 13 18mm 20 25mm 7 9mm 2 5 10mm2 D A B Annealed copper wire C Cables Screw cap AC sh...

Страница 7: ...PE wire ground wire Not following this instruction may cause damage to the inverter 5 Red wire represents positive black wire represents negative 6 For the GE series the minimum insulation resistance...

Страница 8: ...d metal parts of the equipment and other enclosures in the PV power system must be grounded Please follow the steps below to connect PE cable to ground L1 L2 L1 1 2mm Step 1 Strip the wire insulation...

Страница 9: ...installations in compliance with Australian and New Zealand safety requirements and DRED is not provided by the manufacturer DRED should be connected to the COM port with 6 Pin as illustrated below P...

Страница 10: ...ion of commu nication connection you can access portal gesolarinverter com or download the Power Sight App by scanning the QR code to monitor your PV plant and device Please contact after sales for fu...

Страница 11: ...6000W Or Or Power Limit ON Pac 6000W Power Limit OFF Pac 6000W Set Power Limit XXX Set Power Limit XXX Set Modbus Addr Pac 6000W Short Press Long Press Short press short press to select Leading or Lag...

Страница 12: ...E Today menu which displays the total power generation for today Short press the button to enter the E Total menu which displays the total power generation up to today Short press the button to enter...

Страница 13: ...et Power Limit XXX Long press 2S 6 Operation of display under grid connected mode When the input voltage reaches the inverter s start up voltage the LCD starts to work the yellow light will be turned...

Страница 14: ...ecifically according to the inverter Modbus address and Modbus register value according to the set range to set the corresponding value PF Power Curve Mode Function PF curve mode enable or disable B P...

Страница 15: ...e refer to the following instructions before contacting your local service If any problems arise the red FAULT LED indicator on the front panel will light up and the LCD screen will display relevant i...

Страница 16: ...s possible that there are special characters not supported by the module in the hotspot password Please modify the password so that it consists of only Arabic numerals or uppercase lowercase letters...

Страница 17: ...20 360 80 600 0 13 13 13 16 3 16 3 16 3 3 1 1 1 4600 4600 230V 50 20 3 150 120 80 97 7 97 3 GEP7 0S 13500 600 80 550 80 120 360 80 600 0 13 13 13 16 3 16 3 16 3 3 1 1 1 7000 7000 230V 3 50 1 35 1 Adju...

Страница 18: ...es Moisture Location Category Definition Environment Category Definition Outdoor the ambient air temperature is 20 50 Relative humidity range is from 4 to 100 applied to PD3 Indoor unconditioned the a...

Отзывы: