GE GEH-6432 Скачать руководство пользователя страница 3

3. Depress  and  release  the  reset  button  to  insure

that the  Solid  State  Overload  Relay  is  reset.  In

this  condition,  there  should  be  continuity

between  the  terminals.

4. Slide  the  mechanical  trip  test  lever  from  right

to  left  to  trip  the  Solid  State  Overload  Relay.

There  should  be  no  continuity,  indicating  that

the contacts are  operating  normally. 

If 

continuity

is  indicated  with  the  relay  iripped, 

do  not 

use  ihe

relay.

5. If  the  contacts  work  properly,  reconnect  power

and  control  wiring  and  reset  the  Solid  State

Overload  Relay  for  normal  operation.

Additional  Features 

Reset Button 

Depress  the  reset  button fully  and  release  to reset  the 

Solid  State  Overload  Relay  after  a  trip.  For  motor 

protection purposes, the reset  occurs on the  upstroke of 

the reset button. It  is  also designed  so that even if  the 

reset  button is  continually  held  down,  the  Solid  State 

Overload  Relay  will  still  trip  normally. 

Remote 

Reset Pocket 

The  Remote  Reset  ( catalog  number  CR324XRRM)  i s  

an  optional,  field-installable  accessory.  When  the 

Solid  State  Overload  Relay  trips,  it  can  be  remotely 

reset by applying 120 Vac or  24 Vdc  across  the  Remote 

Reset  terminals. 

To install  the  Remote  Reset, remove  and  discard  the 

cover plate over the  Remote Reset pocket on  the  Solid 

State Overload  Relay.  The module  snaps  into  place i n

the slots provided. 

Trip Indicator and Manual  Trip  Test Lever 

When  the  trip  indicator  is  to  the  right,  indicated  by  I, 

the  Solid  State  Overload  Relay  contacts  are  in  the 

normal  position.  When  the  relay  is  tripped,  the 

indicator  moves  to  the  left,  indicated  by  0.  To 

manually  test  the  Relay,  move  the  indicator  manually 

to the left. 

Isolated Auxiliary Contacts 

The  Solid  State  Overload  Relay  provides  one  pair  of 

normally open  (NO)  and  one  pair  of  normally  dosed 

(NC)  isolated contacts to allow for diagnostic use  or  for 

alarm  signaling  when  the  Relay  trips.  The  terminals 

accept  AWG  #22-14,  60/75

° 

C  copper  wire  only. 

Tighten  the  terminal  screws  to  12  lb-in. 

Open  Collector 

With  this  feature  connected  as  illustrated  in  Figure  4, 

it  is  possible  to  differentiate  between  overload  and 

phase-unbalance  trips.  The  terminals  are  marked 

COM  for common and  O  for  output After  an  overload 

trip,  the  output appears  as  during  normal  operation. 

There  is  no  output  following  a  phase-unbalance  trip. 

Nominal  rating  is  +24 Vdc  at 25 mA 

NPN, 

suitable  to 

drive a PLC input.  The  terminals  accept AWG  #22-14, 

60/75

° 

C  copper  wire  only.  Tighten  the  terminal 

screws  to  12 lb-in. 

Customer-Supplied Limiting Resistor 

960 

at 24 Vdc, 480 

at 12 Vdc 

�--.o 

12-24 Vdc 

Su

j

ply 

Figure 4. Open collector wired for trip-type differentiation. 

Snap-In  Marking  Nameplate 

Write  on  the  nameplate  with  a  permanent  marker  or 

pen to identify starters  and  overloads. 

Wiring  Diagram 

Figure  5  is  a  typical  three-phase  wiring  diagram. 

95 

96 

0--N--O 

91fo:---l 

1--o 

198 

Overload Relay 

L1 

L2 

L3 

Disconnect Means 

Figure 5.  Typical three-phase wiring diagram. 

3

Содержание GEH-6432

Страница 1: ...ent Replacement NEMA Range Starter Mount Size amps CR324GXNS 5 32 68 CR324GXPS 5 65 135 CR324GXQS 5 130 270 CR324HXSS 6 130 270 CR324HXTS 6 260 540 Figure 1 Solid State Overload Relay external current transformers not shown 6 Check to see that the two wires from each current transformer have been reconnected to the top and bottom terminals on the same pole of the Solid State Overload Relay as on t...

Страница 2: ...t Replace the tamper resistant cover to provide addi tionai dust protection To protect against unauthorized persons tampering with the settings insert a wire lock through the locking tabs Phase Current Unbalance Sensitivity Adjustment The Solid State Overioad Relay contains a trip function activated by an unbalance among the phase currents The percent difference between the highest and lowest phas...

Страница 3: ...l Trip Test Lever When the trip indicator is to the right indicated by I the Solid State Overload Relay contacts are in the normal position When the relay is tripped the indicator moves to the left indicated by 0 To manually test the Relay move the indicator manually to the left Isolated Auxiliary Contacts The Solid State Overload Relay provides one pair of normally open NO and one pair of normall...

Страница 4: ...t without prior notice With regard to purchase orders the agreed particulars shall prevail ABB Inc does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction or utilization of its contents in whole or in parts is forbidden wi...

Отзывы: