background image

INSTRUCTIONS 

GEH-29068 

Supersedes  GfH-29NA 

and GfH-2903A 

DISTRIBUTION  SURGE  ARRESTERS 

CAUTION:  THE 

EQUIPMENT 

COVERED 

BY 

THESE  INSTRUCTIONS  SHOULD  BE  INSTALLED 
AND  SERVICED  ONLY  BY  COMPETENT  PER­
SONNEL  FAMILIAR  WITH  GOOD  SAFETY  PRAC­
TICES. 

THIS  INSTRUCTION  IS  WRITTEN  FOR 

SUCH  PERSONNEL  AND  IS  NOT  INTENDED  AS  A 
SUBSTITUTE  FOR  ADEQUATE  TRAINING  AND 
EXPERIENCE  IN  SAFE  PROCEDURES  FOR  THIS 

TYPE  OF  EQUIPMENT. 

GENERAL 

The  nameplate  rating  should be checked to ascer­

tain  that  the  maximum  circuit  line-to-ground  volt­
age  under  any  condition  of  operation,  including fault 
conditions,  will  not  exceed  the  voltage  rating  of  the 
arrester. 

Application  of  higher-than-rated  power 

voltages  may  result  in  the  failure  of  the  arrester. 

EffiCient  operation  of  the  lightning  arrester  re­

quires  a  permanent  low-resistance  ground 

The 

best  protection is obtained by connecting the arrester 
directly  across  the  line  and  ground  terminals  of the 
apparatus  being  protected,  using  a  common  ground 
connection  for  both  apparatus  and  arrester. 

If 

this 

is  not  physically  possible,  the  arrester  should be so 
connected  that  its  grounding  resistance  does not ex­

ceed  five  ohms. 

INSTALLATION 

CAUTION: 

CARE  SHOULD 

B

TAKEN 

IN 

HANDLING 

ARRESTERS  TO  AVOID 

BRE

A

K

AGE

The  arrester  preferably  should  be  mounted  ver­

tically  and  installed  as  close  as  possible  to  the  ap­

paratus  being  protected.  Line  and  ground  connec­
tions  should  be  short  and  direct.  Line  and  ground 
terminal  nuts  or  bolts  should  be  tightened  firmly on 

their  respective  leads,  but  with  no  more  than 

15 

lb-ft  torque. 

The  arrester  should  be  clamped  securely  in  its 

hanger  and  in  a  location  where  it  will  not  be  sub­
jected  to  sustained  vibration. 

Fig. 

1. 

Distribution  arrester  with  disconnector. 

Fig. 

2. 

Distribution  arrester,  externally  gapped. 

Arresters  may  also  be  mounted  horizontally. 

However,  a  slight  inclination  with  the  line  end  ele­
vated  may  be  desirable. 

NOTE:  Precautions  to  be  taken  in  instal­
ling  direct-connected  arresters  are  shown 
in  Fig. 

3. 

These  instructions  do  not  purport  to  cover  all  details  or  variations  in  equipment  nor  to  provide  for  every  possible  contingency  to 

be met 

in  connection  with 

installation,  operation  or  maintenance.  Should  further  information 

be 

desired  or  should  particular  problems  arise  which  are  not  covered  sufficiently  far 

the 

purchaser's  purposes,  the  matter  should 

be 

referred  to  the  General  Electric  Company. 

www 

. ElectricalPartManuals 

. com 

Отзывы: