5-16
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
Ö
SERIAL PORTS
It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that is
connected to these ports.
The RS485 ports may be connected to a computer running EnerVista UR Setup. This software can download and upload
setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained
and connected to a DCS, PLC or PC using the RS485 ports.
The baud rate for standard RS485 communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, or 115200 bps.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
each transmission.
If the
RS485 COM2 USAGE
setting is “RRTD”, then the COM2 port is used to monitor the RTDs on a remote RTD unit. The
remote RTD unit uses the Modbus RTU protocol over RS485. The RRTD device must have a unique address from 1 to
254. The baud rate for RRTD communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, or 19200 bps.
If the RS485 COM2 port is used for an RRTD, then there must not be any other devices connected in the daisy-chain for
any other purpose. The port is strictly dedicated to RRTD usage when
RS485 COM2 USAGE
is selected as “RRTD”.
Power must be cycled to the G60 for changes to the
RS485 COM2 USAGE
setting to take effect.
SERIAL PORTS
RS485 COM1 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
MESSAGE
RS485 COM1 PARITY:
None
Range: None, Odd, Even
Only active if CPU Type E is ordered
MESSAGE
RS485 COM1 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type E is ordered
MESSAGE
COM2 USAGE:
RS485
Range: RS485, RRTD
MESSAGE
RRTD SLAVE ADDRESS:
254
Range: 1 to 254 in steps of 1. Shown only if the COM2
USAGE setting is “RRTD”.
MESSAGE
RS485 COM2 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Shown
only if the COM2 USAGE is setting is “RS485”.
MESSAGE
RRTD BAUD RATE:
19200
Range: 1200, 2400, 4800, 9600, 19200. Shown only if
the COM2 USAGE is setting is “RRTD”.
MESSAGE
RS485 COM2 PARITY:
None
Range: None, Odd, Even.
MESSAGE
RS485 COM2 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10.
NOTE
NOTE
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...