GE Multilin
G30 Generator Protection System
5-185
5 SETTINGS
5.6 GROUPED ELEMENTS
5
•
NEG SEQ DIR OC1 FWD PICKUP:
This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a
positive-sequence restraint
technique.
•
NEG SEQ DIR OC1 REV LIMIT ANGLE:
This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
•
NEG SEQ DIR OC1 REV PICKUP:
This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a
positive-sequence restraint
technique.
Figure 5–73: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC
827091A7.CDR
AND
AND
AND
AND
AND
OR
OR
NOTE:
V_2 is negative-sequence voltage
I_2 is negative-sequence current
I_0 is zero-sequence current
AND
SETTING
Off = 0
Block
SETTING
= Neg Sequence
= Zero Sequence
Type
SETTINGS
Forward Pickup
RUN
( |3I_0| – × |I_1| ) Pickup
K
≥
Positive-Sequence Restraint
TIMER
1.25 cycles
1.5 cycles
FLEXLOGIC OPERAND
NEG SEQ DIR OC1 FWD
SETTING
Enabled = 1
Function
ACTUAL VALUES
V_2
I_2
I_0
RUN
( |I_2| – × |I_1| ) Pickup
K
≥
Voltage Polarization
SETTINGS
Forward ECA
RUN
Forward Limit Angle
Reverse Limit Angle
Offset
Forward
Reverse
SETTINGS
Reverse Pickup
RUN
( |I_2| – × |I_1| ) Pickup
K
≥
Pos Seq Restraint
RUN
( |3I_0| – × |I_1| ) Pickup
K
≥
AND
AND
AND
FLEXLOGIC OPERAND
NEG SEQ DIR OC1 REV
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...