5-222
F60 Feeder Protection System
GE Multilin
5.8 TRANSDUCER INPUTS/OUTPUTS
5 SETTINGS
5
5.8.3 DCMA OUTPUTS
PATH: SETTINGS
ÖØ
TRANSDUCER I/O
ÖØ
DCMA OUTPUTS
Ö
DCMA OUTPUT H1(W8)
Table 5–25: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
RESISTANCE (IN OHMS)
°C
°F
100 W PT
(DIN 43760)
120 W NI
100 W NI
10 W CU
–50
–58
80.31
86.17
71.81
7.10
–40
–40
84.27
92.76
77.30
7.49
–30
–22
88.22
99.41
82.84
7.88
–20
–4
92.16
106.15
88.45
8.26
–10
14
96.09
113.00
94.17
8.65
0
32
100.00
120.00
100.00
9.04
10
50
103.90
127.17
105.97
9.42
20
68
107.79
134.52
112.10
9.81
30
86
111.67
142.06
118.38
10.19
40
104
115.54
149.79
124.82
10.58
50
122
119.39
157.74
131.45
10.97
60
140
123.24
165.90
138.25
11.35
70
158
127.07
174.25
145.20
11.74
80
176
130.89
182.84
152.37
12.12
90
194
134.70
191.64
159.70
12.51
100
212
138.50
200.64
167.20
12.90
110
230
142.29
209.85
174.87
13.28
120
248
146.06
219.29
182.75
13.67
130
266
149.82
228.96
190.80
14.06
140
284
153.58
238.85
199.04
14.44
150
302
157.32
248.95
207.45
14.83
160
320
161.04
259.30
216.08
15.22
170
338
164.76
269.91
224.92
15.61
180
356
168.47
280.77
233.97
16.00
190
374
172.46
291.96
243.30
16.39
200
392
175.84
303.46
252.88
16.78
210
410
179.51
315.31
262.76
17.17
220
428
183.17
327.54
272.94
17.56
230
446
186.82
340.14
283.45
17.95
240
464
190.45
353.14
294.28
18.34
250
482
194.08
366.53
305.44
18.73
DCMA OUTPUT H1
DCMA OUTPUT H1
SOURCE: Off
Range: Off, any analog actual value parameter
MESSAGE
DCMA OUTPUT H1
RANGE: –1 to 1 mA
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
MESSAGE
DCMA OUTPUT H1
MIN VAL: 0.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
DCMA OUTPUT H1
MAX VAL: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...