Specifications

Voltage

8.5  – 33 VDC, non polarity sensitive

Maximum ripple (pk to pk)

10% (V

p - p

)

Typical average standby current (24V)

731U, 741UT

100µA

711U, 711UT, 721UT

70µA

Typical alarm current (24V) -2 Wire

up to 60 mA (max), if not limited by control panel

Typical alarm current (24V) -4 Wire

up to 50mA (max) but 15mA (min)

Relay  contacts

2 A @ 30 VDC, 1 A @ 120 VAC

Sensitivity

2.85%, + 0.37, – 0.75%

Operating temperature

32°F to 120°F (0° to 49°C)

Operating humidity range

0 to 95% Non-condensing

RFI Immunity

20 V/m minimum; 0-1000 MHz

Color

White head and base

Field wiring size

12-24 AWG

Heat detector specifications

Fixed temperature - 135°F ± 3°F (57°C ± 1.7°C)

(for 711UT, 721UT,  and 741UT)

Rate of rise - 15°F/min and > 105°F (8.3°C/min and > 40.6°C), 50 ft. spacing for 711UT/721UT/741UT

UL two-wire compatibility identifier

S10A for all models except 731U/731L, S11A for 731U/731L, S00 for all bases

Remote LED output current

5 mA min, 8.5 mA max

Drift compensation adjustment

1.0%/ft. max for photoelectric models

0.5%/ft. max for ionization models

Detector head dimensions

4" (10 cm) diameter; 1.75" (4.44 cm) height

Base dimensions

702E

4"  (10 cm) diameter; 0.05" (1.27 cm) height

701U, 702U

6" (15.2 cm) diameter, 0.6" (1.3 cm) height

Total height, head and base together

1.98" (5 cm) height

Remote test input

100 ohm max

Reset voltage

2.5V max

Reset time

1 second minimum

Listings

UL 268, FM, MEA, CSFM

Product Ordering

Detectors

Description

   711U

2-wire photoelectric type smoke detector

   711UT

2-wire photoelectric type smoke detector with rate-of-rise heat detector and fast response algorithms

   721UT

2-wire photoelectric type, with rate-of-rise heat detector with fast response algorithms, remote test, alarm/trouble LED output

   731U

2-wire photoelectric type smoke detector, with auxiliary relay (N.C./N.O.) outputs, UL Listed for releasing service

  741UT

4-wire photoelectric type smoke detector, alarm relay (N.O.) output and remote alarm/trouble LED output with rate-of-rise heat

detector with fast response algorithms

    731L

(OEM only, not for resale) See 731U description

B a s e s

   701U

Base, for 711U heads; 6" (15 cm) base, 3 terminal connectors

   702E

Base, for all heads; 4" (10 cm) base, 6 terminal connectors

   702U

Base, for all heads; 6" (15 cm) base, 6 terminal connectors

   702RE

Base, for 731U relay type smoke detector heads; 4" (10 cm) base, 6 terminal connectors

   702RU

Base, for 731U relay type smoke detector heads; 6" (15 cm) base, 6 terminal connectors

Accessories

   204-12/24V

End-of-line, power supervision relay for 4-wire applications

   SM-200

Smoke! in a can

®

 (canned smoke) for functional testing of smoke detectors

   211

Replacement optical block cover for all models (set of 10)

   706U1A

Remote Indicator with red alarm LED, for use with 731U and 741UT

   706U2A

Remote Indicator with red alarm LED and keyed remote test, for use with 731U and 741UT

   706U3A

Remote Indicator with red alarm LED, keyed remote test and reset, for use with 731U and 741UT

13083 Rev H     06/04

Tech Support
800-648-7424

www.GESecurity.com

GE Security
12345 SW Leveton Drive
Tualatin, OR 97062
503-692-4052
USA & Canada: 800-547-2556

GE Security 

g

firealarmresources.com

Содержание ESL 700 Series

Страница 1: ...ery 9 seconds during normal condition Blinks once every second during trouble condition Latches on in alarm No indication during loss of power Normally Open Common Normally Closed End of Line Device 1 3 2 6 4 5 1 3 2 6 4 5 NOTE Alarm contacts shown in non alarm mode 700 Series 4 Wire Wiring Diagram 741UT Head Figure 1 Wiring diagrams RemoteLED Blinks every 9 seconds during normal condition Blinks ...

Страница 2: ...orized removal of the detector head is not a concern the head can be removed by simply turning counterclockwise However when the head must lock to the base break away the locking tab slot with a pair of pliers Then to remove the detector head insert a small screwdriver into the slot on the side of the base and press in while simultaneously turning the detector head counterclockwise see Figure 7 In...

Страница 3: ...tivity test If the error persists replace unit 2 3 Indication Unit is becoming insensitive Action Clean and reset the unit Rerun sensitivity test If the error persists replace the unit 4 7 Indication Unit is within normal sensitivity range Action N A 8 9 Indication Unit is becoming too sensitive Action Verify the optical chamber is snapped down securely Clean the unit and replace the optical chamb...

Страница 4: ...ctor 711UT 2 wire photoelectric type smoke detector with rate of rise heat detector and fast response algorithms 721UT 2 wire photoelectric type with rate of rise heat detector with fast response algorithms remote test alarm trouble LED output 731U 2 wire photoelectric type smoke detector with auxiliary relay N C N O outputs UL Listed for releasing service 741UT 4 wire photoelectric type smoke det...

Отзывы: