GE EPM6000 Скачать руководство пользователя страница 1

EPM 6000 Multi-function Power 

Metering System

Chapter 1: 

Digital Energy

Multilin

Instruction Manual

Software Revision: 1.17

Manual P/N: 1601-0215-A5

Manual Order Code: GEK-106558D

Copyright © 2010 GE Multilin

GE Multilin

215 Anderson Avenue, Markham, Ontario

Canada L6E 1B3

Tel: (905) 294-6222   Fax: (905) 201-2098

Internet: 

http://www.GEmultilin.com

*1601-0215-A5*

IISO9001:2000

G

E MULTILI

N

RE

GISTERED

GE Multilin's Quality 

Management System is 

registered to ISO9001:2000

QMI # 005094

LISTED

Содержание EPM6000

Страница 1: ... 0215 A5 Manual Order Code GEK 106558D Copyright 2010 GE Multilin GE Multilin 215 Anderson Avenue Markham Ontario Canada L6E 1B3 Tel 905 294 6222 Fax 905 201 2098 Internet http www GEmultilin com 1601 0215 A5 IISO9001 2000 G E M ULTILI N R E GISTERE D GE Multilin s Quality Management System is registered to ISO9001 2000 QMI 005094 LISTED ...

Страница 2: ......

Страница 3: ...2 3 MEASURED VALUES 2 3 UTILITY PEAK DEMAND 2 4 SPECIFICATIONS 2 5 3 MECHANICAL INSTALLATION INTRODUCTION 3 1 ANSI INSTALLATION STEPS 3 3 DIN INSTALLATION STEPS 3 4 EPM6000 TRANSDUCER INSTALLATION 3 5 4 ELECTRICAL INSTALLATION CONSIDERATIONS WHEN INSTALLING METERS 4 1 CT LEADS TERMINATED TO METER 4 2 CT LEADS PASS THROUGH NO METER TERMINATION 4 3 QUICK CONNECT CRIMP CT TERMINATIONS 4 3 VOLTAGE AND...

Страница 4: ... 6 5 INFRARED KYZ PULSE CONSTANTS FOR ACCURACY TESTING 6 6 UPGRADE THE METER USING V SWITCHESÂ 6 7 7 CONFIGURING THE METER USING THE FRONT PANEL OVERVIEW 7 1 START UP 7 3 CONFIGURATION 7 4 MAIN MENU 7 4 RESET MODE 7 4 CONFIGURATION MODE 7 6 CONFIGURING THE SCROLL FEATURE 7 7 PROGRAMMING THE CONFIGURATION MODE SCREENS 7 7 CONFIGURING THE CT SETTING 7 9 CONFIGURING THE PT SETTING 7 10 CONFIGURING TH...

Страница 5: ...RING SYSTEM USER GUIDE TOC 3 APPENDIX D DNP 3 0 PROTOCOL ASSIGNMENTS FOR EPM6000 DNP IMPLEMENTATION APPENDIX D 1 DATA LINK LAYER APPENDIX D 2 TRANSPORT LAYER APPENDIX D 3 APPLICATION LAYER APPENDIX D 4 OBJECT AND VARIATION APPENDIX D 5 ...

Страница 6: ...TOC 4 EPM 6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE ...

Страница 7: ...power a wye connection or a delta connection Each connection has several different manifestations in actual use When attempting to determine the type of connection in use it is a good practice to follow the circuit back to the transformer that is serving the circuit It is often not possible to conclusively determine the correct circuit connection simply by counting the wires in the service or chec...

Страница 8: ...currents to depart from the ideal 120o separation Three phase voltages and currents are usually represented with a phasor diagram A phasor diagram for the typical connected voltages and currents is shown below FIGURE 1 2 Three phase Voltage and Current Phasors for Wye Winding The phasor diagram shows the 120 angular separation between the phase voltages The phase to phase voltage in a balanced thr...

Страница 9: ...wye service it contains four wires if you trace the circuit back to its source usually a transformer In this type of connection the phase to ground voltage will be the phase to ground voltage indicated in the table above even though a neutral or ground wire is not physically present at the load The transformer is the best place to determine the circuit connection type because this is a location wh...

Страница 10: ...services one corner of the delta is grounded This means the phase to ground voltage will be zero for one phase and will be full phase to phase voltage for the other two phases This is done for protective purposes FIGURE 1 4 Three Phase Voltage and Current Phasors for Delta Winding Another common delta connection is the four wire grounded delta used for lighting loads In this connection the center ...

Страница 11: ...ductor in which there is no current coil Three phase power measurement is accomplished by measuring the three individual phases and adding them together to obtain the total three phase value In older analog meters this measurement was accomplished using up to three separate elements Each element combined the single phase voltage and current to produce a torque on the meter disk All three elements ...

Страница 12: ...f voltage and current simultaneously and calculate the individual phase and three phase power values The advantage of simultaneous sampling is the reduction of error introduced due to the difference in time when the samples were taken Blondell s Theorem is a derivation that results from Kirchhoff s Law Kirchhoff s Law states that the sum of the currents into a node is zero Another way of stating t...

Страница 13: ...000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 1 7 power flow in three wires This will require three voltage coils and three current coils a three element meter Similar figures and conclusions could be reached for other circuit configurations involving delta connected loads ...

Страница 14: ...c bills are based in part on the amount of energy used Typically electrical energy is measured in units of kilowatt hours kWh A kilowatt hour represents a constant load of one thousand watts one kilowatt for one hour Stated another way if the power delivered instantaneous watts is measured as 1 000 watts and the load was served for a one hour time interval then the load would have absorbed one kil...

Страница 15: ... it is necessary to accumulate the energy readings as illustrated in Figure 1 7 above and adjust the energy reading to an hourly value that constitutes the demand In the example the accumulated energy is 14 92 kWh But this measurement was made over a 15 minute interval To convert the reading to a demand value it must be normalized to a 60 minute interval If the pattern were repeated for an additio...

Страница 16: ...calculate demand it is necessary to accumulate the energy readings as illustrated in the Power Use Over Time figure above and adjust the energy reading to an hourly value that constitutes the demand In the example the accumulated energy is 14 92 kWh But this measurement was made over a 15 minute interval To convert the reading to a demand value it must be normalized to a 60 minute interval If the ...

Страница 17: ... SYSTEM USER GUIDE 1 11 FIGURE 1 8 Energy Use and Demand Intervals As seen in this example it is important to recognize the relationships between power energy and demand in order to effectively control loads or to correctly monitor use 0 20 40 60 80 100 1 2 3 4 5 6 7 8 Intervals 15 mins kilowatt hours ...

Страница 18: ...and the component that is at quadrature angularly rotated 90o or perpendicular to the voltage Figure 1 9 shows a single phase voltage and current and breaks the current into its in phase and quadrature components FIGURE 1 9 Voltage and Complex Current The voltage V and the total current I can be combined to calculate the apparent power or VA The voltage and the in phase current IR are combined to ...

Страница 19: ...tent If the voltage or current includes high levels of harmonic distortion the power values will be affected By calculating power factor from the power values the power factor will include the impact of harmonic distortion In many cases this is the preferred method of calculation because the entire impact of the actual voltage and current are included A second type of power factor is Displacement ...

Страница 20: ...sinusoidal current waveform This example has no distortion FIGURE 1 10 Non distorted current waveform Figure 1 11 shows a current waveform with a slight amount of harmonic distortion The waveform is still periodic and is fluctuating at the normal 60 Hz frequency However the waveform is not a smooth sinusoidal form as seen in Figure 1 10 FIGURE 1 11 Distorted current wave The distortion observed in...

Страница 21: ... We are accustomed to thinking about these impedances as they perform at 60 Hz However these impedances are subject to frequency variation EQ 1 3 At 60 Hz ω 377 but at 300 Hz 5th harmonic ω 1 885 As frequency changes impedance changes and system impedance characteristics that are normal at 60 Hz may behave entirely different in presence of higher order harmonic waveforms Traditionally the most com...

Страница 22: ...c distortion is not the same as not having harmonic distortion 1 4 3 Waveform Capture It is common in advanced meters to perform a function commonly referred to as waveform capture Waveform capture is the ability of a meter to capture a present picture of the voltage or current waveform for viewing and harmonic analysis Typically a waveform capture will be one or two cycles in duration and can be ...

Страница 23: ...ocation or they may be transported by the utility system to another adjacent customer Often equipment that is sensitive to power quality problems may in fact also be the cause of the problem If a power quality problem is suspected it is generally wise to consult a power quality professional for assistance in defining the cause and possible solutions to the problem Table 1 3 Typical Power Quality P...

Страница 24: ...1 18 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE POWER QUALITYCHAPTER 1 THREE PHASE POWER MEASUREMENT ...

Страница 25: ... an IrDA Port for remote interrogation EPM6000 meter features that are detailed in this manual are as follows 0 2 Class Revenue Certifiable Energy and Demand Metering Meets ANSI C12 20 0 2 and IEC 687 0 2 Classes Multifunction Measurement including Voltage Current Power Frequency Energy etc Power Quality Measurements THD and Alarm Limits V SwitchΤΜ Technology Field Upgrade without Removing Install...

Страница 26: ...hrough Bars that allow CT leads to be terminated on the meter This too eliminates any possible point of failure at the meter This is a preferred technique for insuring that relay class CT integrity is not compromised the CT will not open in a fault condition 2 1 2 Order Codes The order codes for the EPM6000 are indicated below For example to order an EPM6000 for 60 Hz system with a 1 A secondary C...

Страница 27: ...V Switch 3 V3 Volts Amps kW kVAR PF kVA Freq kWh kVAh kVARh DNP 3 0 V Switch 4 V4 Volts Amps kW kVAR PF kVA Freq kWh kVAh kVARh DNP 3 0 THD Monitoring and Limit Exceeded Alarms 2 1 4 Measured Values The following table lists the measured values available in real time average maximum and minimum Table 2 2 EPM6000 Measured Values Measured Values Real Time Average Maximum Minimum Voltage L N X X X Vo...

Страница 28: ...xed window demand that moves for a user specified subinterval period For example a 15 minute demand using 3 subintervals and providing a new demand reading every 5 minutes based on the last 15 minutes Utility demand features can be used to calculate kW kvar kVA and PF readings All other parameters offer maximum and minimum capability over the user selectable averaging period Voltage provides an in...

Страница 29: ...y PT ratio CURRENT INPUTS Class 10 5 A nominal 10 A maximum Class 2 1 A nominal 2 A maximum Burden 0 005 VA per phase maximum at 11 A Pickup current 0 1 of nominal Connections O or U lug Pass through wire 0 177 4 5 mm maximum diameter Quick connect 0 25 male tab Fault Withstand 100 A 10 seconds 300 A 3 seconds 500 A 1 second Reading Programmable full scale to any CT ratio MEASUREMENT METHODS Volta...

Страница 30: ...ncy 3Hz Contact type Solid State SPDT NO C NC Relay type Solid state Peak switching voltage DC 350V Meter Accuracy byMeasured Parameters Measured Parameters Display Range Accuracy of Reading Voltage L N 0 to 9999 V or kV Autoscale 0 1 Voltage L L 0 to 9999 V or kV Autoscale 0 1 Current Phase 0 to 9999 A or kA Autoscale 0 1 Current Neutral Calculated 0 to 9999 A or kA Autoscale 2 F S Watts 0 to 999...

Страница 31: ...YSTEM USER GUIDE 2 7 Continuous load current 120mA Peak load current 350mA for 10ms On resistance max 35Ω Leakage current 1μA 350V Isolation AC 3750V Reset State NC C Closed NO C Open Infrared LED Peak Spectral Wavelength 940nm Reset State Off FIGURE 2 1 Internal Schematic De energized State ...

Страница 32: ...ls Modbus RTU Modbus ASCII DNP 3 0 V3 and V4 Baud rate 9600 to 57600 bps Port address 001 to 247 Data format 8 bits no parity EPM6000 Transducer Default initial communication 9600 Baud MECHANICAL PARAMETERS Dimensions 4 25 4 82 4 85 L W H 105 4 mm 123 2 mm 123 2 mm L W H Mounting mounts in 92 mm square DIN or ANSI C39 1 4 inch round cut out Weight 2 pounds 0 907 kg ...

Страница 33: ... MechanicalInstallation 3 1 Introduction The EPM6000 meter can be installed using a standard ANSI C39 1 4 Round or an IEC 92mm DIN Square form In new installations simply use existing DIN or ANSI punches For existing panels pull out old analog meters and replace with the EPM6000 meter The various models use the same installation See Chapter 4 for wiring diagrams ...

Страница 34: ...r EPM6000 Meter Installation 2 Phillips screwdriver small wrench and wire cutters EPM6000 Transducer Installation requires no tools Mount the meter in a dry location free from dirt and corrosive substances The meter is designed to withstand harsh environmental conditions See Environmental Specifications in Chapter 2 DIN Mounting Brackets ANSI Mounting Rods screw in ...

Страница 35: ... Twist until secure 2 Slide ANSI 12 Mounting Gasket onto back of meter with rods in place 3 Slide meter with Mounting Gasket into panel 4 Secure from back of panel with lock washer and nut on each threaded rod Use a small wrench to tighten Do not overtighten The maximum installation torque is 0 4 Newton Meter FIGURE 3 2 ANSI Mounting Procedure NEMA12 mounting gasket threaded rods lock washer and n...

Страница 36: ...into grooves in top and bottom of meter housing Snap into place 3 Secure meter to panel with lock washer and a 8 screw through each of the 2 mounting brackets Tighten with a 2 Phillips screwdriver Do not overtighten The maximum installation torque is 0 4 Newton Meter FIGURE 3 3 DIN Mounting Procedure DIN mounting bracket top mounting bracket groove bottom mounting bracket groove 8 screw EPM 6000 m...

Страница 37: ...ing Specs for DIN Rail Mounting International Standards DIN 46277 3 DIN Rail Slotted Dimensions 0 297244 x 1 377953 x 3 inches 7 55mm x 35mm x 76 2mm millimeters DIN Rail Installation Steps 1 Slide top groove of meter onto the DIN Rail 2 Press gently until the meter clicks into place FIGURE 3 4 DIN Rail Mounting Procedure Note If mounting with the DIN Rail provided use the Black Rubber Stoppers al...

Страница 38: ...eter from DIN Rail Pull down on Release Clip to detach the unit from the DIN Rail Note DIN Rails are comonly used as a mounting channel for most terminal blocks control devices circuit protection devices and PLCs DIN Rails are made of cold rolled steel electrolitically plated and are also available in aluminum PVC stainless steel and copper Black Rubber Stoppers ...

Страница 39: ...ges and currents Avoid contact with any current carrying surfaces Do not use the meter or any I O Output Device for primary protection or in an energy limiting capacity The meter can only be used as secondary protection Do not use the meter for applications where failure of the meter may cause harm or death Do not use the meter for any application where there may be a risk of fire All meter termin...

Страница 40: ...e marked as the disconnecting device for the equipment 4 1 1 CT Leads Terminated to Meter The EPM6000 is designed to have Current Inputs wired in one of three ways Figure 4 1 below shows the most typical connection where CT Leads are terminated to the meter at the Current Gills This connection uses Nickel Plated Brass Studs Current Gills with screws at each end This connection allows the CT wires ...

Страница 41: ...without terminating at the meter In this case remove the current gills and place the CT wire directly through the CT opening The opening will accommodate up to 0 177 4 5 mm maximum diameter CT wire FIGURE 4 2 Pass Through Wire Electrical Connection 4 1 3 Quick Connect Crimp CT Terminations For quick termination or for portable applications a quick connect crimp CT connection can also be used Curre...

Страница 42: ...NG METERSCHAPTER 4 ELECTRICAL INSTALLATION FIGURE 4 3 Quick Connect Electrical Connection 4 1 4 Voltage and Power Supply Connections Voltage Inputs are connected to the back of the unit via a optional wire connectors The connectors accommodate up to AWG 12 2 5 mm wire Crimp CT terminations ...

Страница 43: ...irectly to the installation s protective earth ground Use 2 5 mm wire for this connection 4 1 6 Voltage Fuses GE Multilin recommends the use of fuses on each of the sense voltages and on the control power even though the wiring diagrams in this chapter do not show them Use a 0 1 Amp fuse on each voltage input Use a 3 0 Amp fuse on the Power Supply Power supply inputs Voltage inputs RS485 outputs d...

Страница 44: ...lement 2 Three phase four wire system Wye with no PTs direct voltage 3 CTs 2 5 element 3 Three phase four wire Wye with 3 PTs 3 CTs 3 element 4 Three phase four wire Wye with 2 PTs 3 CTs 2 5 element 5 Three phase three wire Delta with no PTs direct voltage 2 CTs 6 Three phase three wire Delta with 2 PTs 2 CTs 7 Three phase three wire Delta with 2 PTs 3 CTs 8 Current only measurement three phase 9 ...

Страница 45: ...GRAMS EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 4 7 4 2 2 1 Wye 4 Wire with no PTs and 3 CTs no PTs 3 Element For this wiring type select 3 EL WYE 3 element Wye in the meter programming setup FIGURE 4 5 4 Wire Wye with no PTs and 3 CTs 3 Element ...

Страница 46: ...E ELECTRICAL CONNECTION DIAGRAMSCHAPTER 4 ELECTRICAL INSTALLATION 4 2 3 2 Wye 4 Wire with no PTs and 3 CTs 2 5 Element For this wiring type select 2 5EL WYE 2 5 element Wye in the meter programming setup FIGURE 4 6 4 Wire Wye with no PTs and 3 CTs 2 5 Element ...

Страница 47: ...N DIAGRAMS EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 4 9 4 2 4 3 Wye 4 Wire with 3 PTs and 3 CTs 3 Element For this wiring type select 3 EL WYE 3 element Wye in the meter programming setup FIGURE 4 7 4 Wire Wye with 3 PTs and 3 CTs 3 Element ...

Страница 48: ...IDE ELECTRICAL CONNECTION DIAGRAMSCHAPTER 4 ELECTRICAL INSTALLATION 4 2 5 4 Wye 4 Wire with 2 PTs and 3 CTs 2 5 Element For this wiring type select 2 5EL WYE 2 5 element Wye in the meter programming setup FIGURE 4 8 4 Wire Wye with 2 PTs and 3 CTs 2 5 Element ...

Страница 49: ... CONNECTION DIAGRAMS EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 4 11 4 2 6 5 Delta 3 Wire with no PTs 2 CTs For this wiring type select 2 Ct dEL 2 CT Delta in the meter programming setup FIGURE 4 9 3 Wire Delta with no PTs and 2 CTs ...

Страница 50: ...SYSTEM USER GUIDE ELECTRICAL CONNECTION DIAGRAMSCHAPTER 4 ELECTRICAL INSTALLATION 4 2 7 6 Delta 3 Wire with 2 PTs 2 CTs For this wiring type select 2 Ct dEL 2 CT Delta in the meter programming setup FIGURE 4 10 3 Wire Delta with 2 PTs and 2 CTs ...

Страница 51: ... CONNECTION DIAGRAMS EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 4 13 4 2 8 7 Delta 3 Wire with 2 PTs 3 CTs For this wiring type select 2 Ct dEL 2 CT Delta in the meter programming setup FIGURE 4 11 3 Wire Delta with 2 PTs and 3 CTs ...

Страница 52: ...ree Phase For this wiring type select 3 EL WYE 3 Element Wye in the meter programming setup FIGURE 4 12 Current Only Measurement Three Phase Note Even if the meter is used only for current measurement the unit requires a AN volts reference Please ensure that the voltage input is attached to the meter AC control power can be used to provide the reference signal ...

Страница 53: ...ual Phase For this wiring type select 3 EL WYE 3 Element Wye in the meter programming setup FIGURE 4 13 Current Only Measurement Dual Phase Note Even if the meter is used only for current measurement the unit requires a AN volts reference Please ensure that the voltage input is attached to the meter AC control power can be used to provide the reference signal ...

Страница 54: ...ngle Phase For this wiring type select 3 EL WYE 3 Element Wye in the meter programming setup FIGURE 4 14 Current Only Measurement Single Phase Note Even if the meter is used only for current measurement the unit requires a AN volts reference Please ensure that the voltage input is attached to the meter AC control power can be used to provide the reference signal ...

Страница 55: ...aking Modbus ASCII Modbus RTU and DNP 3 0 V3 and V4 protocols 5 1 1 IrDA Port COM 1 The EPM6000 meter s Com 1 IrDA Port is on the face of the meter The IrDA Port allows the unit to be set up and programmed using a PDA or remote laptop without the need for a communication cable Just point at the meter with an IrDA equipped PC or PDA and configure it Communicator EXT COPILOT is a Windows CE software...

Страница 56: ...m 1 IrDA Port are as follows Address 1 Baud Rate 57 6k Protocol Modbus ASCII Additional settings are configured using Communicator EXT software 5 1 2 RS 485 KYZ Output COM 2 485P Option The 485P Option provides a combination RS 485 and a KYZ Pulse Output for pulsing energy values The RS 485 KYZ Combo is located on the terminal section of the meter See section 6 3 1 for Pulse Constants ...

Страница 57: ...85 allows you to connect one or multiple EPM6000 meters to a PC or other device at either a local or remote site All RS485 connections are viable for up to 4000 feet 1219 20 meters FIGURE 5 3 EPM6000 Connected to PC via RS485 As shown in Figure 5 3 to connect a EPM6000 to a PC you need to use an RS485 to RS232 converter Figure 5 4 below shows the detail of a 2 wire RS485 connection ...

Страница 58: ...ld be connected at any one point on an RS485 network whether the connections are for devices converters or terminal strips Include all segments when calculating the total cable length of a network If you are not using an RS485 repeater the maximum length for cable connecting all devices is 4000 feet 1219 20 meters Connect shield to RS485 Master and individual devices as shown in Figure 5 6 You may...

Страница 59: ...CHAPTER 5 COMMUNICATION INSTALLATIONEPM6000 COMMUNICATION EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 5 5 FIGURE 5 5 RS485 Daisy Chain Connection FIGURE 5 6 Incorrect T and Star Topologies ...

Страница 60: ... can connect to the EPM6000 using the Factory Initial Default Settings This feature is useful in debugging or in any situtation where you do not know the meter s programmed settings and want to find them When the EPM6000 is powered up you have up to 5 seconds to poll the Name Register as shown in the example below How to Connect You will be connected to the meter with the Factory Initial Default S...

Страница 61: ...creen Note If you do not connect with the Factory Initial Default Settings within 5 seconds after powering on the meter the Device Profile reverts to the programmed Device Profile In that case disconnect and reconnect power before clicking the Connect button The Device Status screen appears confirming a connection FIGURE 5 9 Device Status screen Click OK The main screen of Communicator EXT softwar...

Страница 62: ... AND PROGRAMMING OVERVIEWCHAPTER 5 COMMUNICATION INSTALLATION 4 Click the Profile button on the left of the toolbar A set of EPM6000 Profile Programming Screens appears 5 Click the Communication tab The Communication Settings appear Use pull down menus to change settings if desired ...

Страница 63: ... DNP Baud Rate 9600 to 57600 Response Delay 0 750 msec 6 When changes are complete click the Update button to send a new profile to the meter 7 Click Cancel to Exit the Profile or 8 Click other tabs to update other aspects of the Profile see section 5 2 2 below 5 2 2 EPM6000 Profile Settings SCALING CT PT Ratios and System Wiring CT Numerator Primary CT Denominator Secondary CT Multiplier CT Fulls...

Страница 64: ...play a 14 40kV Example CT Settings 200 5 Amps Set the Ct n value for 200 Ct Multiplier value for 1 800 5 Amps Set the Ct n value for 800 Ct Multiplier value for 1 2 000 5 Amps Set the Ct n value for 2000 Ct Multiplier value for 1 10 000 5 Amps Set the Ct n value for 1000 Ct Multiplier value for 10 Example PT Settings 277 277 Volts Pt n value is 277 Pt d value is 277 Pt Multiplier is 1 14 400 120 V...

Страница 65: ...D DISPLAY POWER AND ENERGY FORMAT Power Scale Energy Digits Energy Decimal Places Energy Scale Example Based on Selections Power Direction View as Load Demand Averaging Averaging Method Block or Rolling Interval Minutes Sub Interval Auto Scroll Click to Activate Display Configuration Click Values to be displayed Note You MUST have at lease ONE selected ...

Страница 66: ...rect values are entered on this screen the following message appears Current CT PT and Energy Settings will cause invalid energy accumulator values Change the inputted settings until the message disappears SETTINGS Password Meter is shipped with Password Disabled and there is NO DEFAULT PASSWORD Enable Password for Reset Enable Password for Configuration Change Password Change VSwitch Call GE Mult...

Страница 67: ...on High Set Point of Full Scale Example 100 of 120VFS 120V 90 of 120V FS 108V Return Hysteresis Point to go back in Limit Example High Set Point 110 Out of Limit at 132V Return Hysteresis 105 Stay Out until 126V Low Set Point of Full Scale Return Hysteresis Point to go back in Limit Settings appear in the Table at the bottom of the screen Note If Return Hysteresis is High Set Point the Limit is Di...

Страница 68: ...NG OVERVIEWCHAPTER 5 COMMUNICATION INSTALLATION Note If the Update fails the software asks if you want to try again to Update Click Cancel to Exit the Profile Use Communicator EXT to communicate with the device and perform required tasks Refer to the Communicator EXT User s Manual for more details ...

Страница 69: ... with the network administrator before performing these steps because some of the functions may be restricted to Administrator privileges The Host PC could have multiple Ethernet Adapters Network Cards installed Identify and configure the one that will be used for accessing the EPM6000 meter The PC s Ethernet Adapter must be set up for point to point communication when configuring the EPM6000 mete...

Страница 70: ...E CONFIGURING THE ETHERNET CONNECTION E OPTION CHAPTER 5 COMMUNICATION INSTALLATION 2 Right click on the Local Area Network Connection you will use to connect to the EPM6000 meter and select Properties from the drop down menu You will see the window shown below ...

Страница 71: ...ING SYSTEM USER GUIDE 5 17 3 Select Internet Protocol TCP IP and click the Properties button You will see the window shown below 4 Click the Use the Following IP Address radio button and enter these parameters IP Address 10 0 0 2 Subnet Mask 255 255 255 0 5 Click the OK button You have completed the setup procedure ...

Страница 72: ...ort used for setting up the meter This eliminates the possibility of several people trying to configure the Ethernet interface simultaneously It is possible to reset the Ethernet card to its default values See the procedure on page 5 16 5 17 5 3 2 1 Configuring the EPM6000 Meter s Ethernet Connection using Windows XP on the Host Computer Establish a Telnet connection on port 9999 Follow these step...

Страница 73: ...ing the current setting Serial Number 5415404 MAC Address 00 20 4A 3C 2C Software Version V01 2 000719 Press Enter to go into Setup Mode Microsoft Windows XP Version 5 1 2600 C Copyright 1985 2001 Microsoft Corp C Documents and Settings Administrator telnet 10 0 0 1 9999 1 Network IP Settings IP Address 10 0 0 1 Default Gateway Not Set Netmask 255 255 255 0 2 Serial Mode Settings Protocol Modbus R...

Страница 74: ...ded After finishing your modifications make sure to press the S key on the keyboard This will save the new values and perform a Reset in the Ethernet card CAUTION DO NOT PRESS D as it will overwrite any changes and save the default values Note If the IP Address of the Ethernet card is lost you can restore the factory default settings by pressing the Reset button on the card Follow the procedure in...

Страница 75: ...THERNET CONNECTION E OPTION EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE 5 21 Using an implement such as a ballpoint pen tip press and hold the Reset button for 30 seconds The E card will be reset to the default settings shown in Section 5 3 2 ...

Страница 76: ...5 22 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE CONFIGURING THE ETHERNET CONNECTION E OPTION CHAPTER 5 COMMUNICATION INSTALLATION ...

Страница 77: ...ly by using the Elements and the Buttons on the meter face This chapter will review Front Panel Navigation Complete Navigation Maps can be found in Appendix A of this manual FIGURE 6 1 Faceplate of EPM6000 Meter with Elements 6 1 1 Meter Face Elements Reading Type Indicator Indicates Type of Reading IrDA Communication Port Com 1 Port for Wireless Communication Parameter designator Watt hour pulse ...

Страница 78: ... perform the following functions View Meter Information Enter Display Modes Configure Parameters Password Protected Perform Resets Perform LED Checks Change Settings View Parameter Values Scroll Parameter Values View Limit States Enter Button Press and release to enter one of four Display Modes Operating Mode Default Reset Mode ENTER once then Down Settings Mode ENTER twice then Down Configuration...

Страница 79: ...ode menus Use Buttons in Modes of Operation Operating Mode default View Parameter Values Reset Mode Reset Stored Max and Min Values Settings Mode View Meter Setting Parameters and Change Scroll Setting Configuration Mode Change Meter Configuration Can be Password Protected Note The above is a brief overview of the use of the Buttons For Programming refer to Chapter 7 For complete Navigation Maps r...

Страница 80: ...6000 unit s display provides a graphic representation of Amps The segments light according to the load in the Load Segment Table below When the Load is over 120 of Full Load all segments flash On 1 5 secs and Off 0 5 secs Table 6 1 Load Segments Segments Load Full Load None No Load 1 1 1 2 15 1 3 30 1 4 45 1 5 60 1 6 72 1 7 84 1 8 96 1 9 108 1 10 120 All Blink 120 ...

Страница 81: ... providers use field test standards to ensure that the unit s energy measurements are correct Since the EPM6000 is a traceable revenue meter it contains a utility grade test pulse that can be used to gate an accuracy standard This is an essential feature required of all billing grade meters FIGURE 6 3 Watt hour Test Pulse Refer to the figure below for an example of how this test works Refer to Tab...

Страница 82: ...TER 6 3 1 Infrared KYZ Pulse Constants for Accuracy Testing Note Minimum pulse width is 40 ms Refer to section 2 2 for Wh Pulse specifications Table 6 2 Infrared KYZ Pulse Constants for Accuracy Testing Voltage Level Class 10 Models Class 2 Models Below 150 V 0 2505759630 0 0501151926 Above 150 V 1 0023038521 0 2004607704 ...

Страница 83: ...R PF kVA Freq kWh kVAh kVARh DNP 3 0 V Switch 4 V4 Volts Amps kW kVAR PF kVA Freq kWh kVAh kVARh DNP 3 0 THD Monitoring and Limit Exceeded Alarms To change the V Switch follow these simple steps 1 Install Communicator EXT 3 0 in your computer 2 Set up EPM6000 to communicate with your computer see Chapter 5 power up your meter 3 Log on to Communication EXT 3 0 software 4 Click on the Profile icon A...

Страница 84: ...6 8 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE UPGRADE THE METER USING V SWITCHESÂCHAPTER 6 USING THE METER ...

Страница 85: ...eFrontPanel 7 1 Overview The EPM6000 front panel can be used to configure the meter The EPM6000 has three MODES Operating Mode Default Reset Mode Configuration Mode The MENU ENTER DOWN and RIGHT buttons navigate through the MODES and navigate through all the SCREENS in each mode FIGURE 7 1 EPM6000 Label Reading Type Indicator IrDA Comm Port of Load Bar Scale Selector Watt Hour Test Pulse Parameter...

Страница 86: ...FIGURING THE METER USING THE FRONT PANEL In this chapter a typical set up will be demonstrated Other settings are possible The complete Navigation Map for the Display Modes is in Appendix A of this manual The meter can also be configured with software see Communicator EXT 3 0 Manual ...

Страница 87: ...r Error Screen if an error exists EPM6000 will then automatically Auto Scroll the Parameter Designators on the right side of the front panel Values are displayed for each parameter The KILO or MEGA LED lights showing the scale for the Wh VARh and VAh readings An example of a Wh reading is shown here An example of a Wh reading is shown below FIGURE 7 2 Typical Wh Reading The EPM6000 will continue t...

Страница 88: ... blinking in the A Screen If you push DOWN again the MENUscrolls back to Reset Mode rSt If you push ENTER from the Main Menu the meter enters the Mode that is in the A Screen and is blinking See Appendix A for Navigation Map FIGURE 7 3 Main Menu Screens 7 3 2 Reset Mode If you push ENTER from the Main Menu the meter enters the Mode that is in the A Screen and is blinking Reset Mode is the first mo...

Страница 89: ...reen and 4 dashes in the B Screen The LEFT digit is flashing Use the DOWN button to scroll from 0 to 9 for the flashing digit When the correct number appears for that digit use the RIGHT button to move to the next digit Example On the Password screens below On the left screen four dashes appear and the left digit is flashing On the right screen 2 digits have been entered and the third digit is fla...

Страница 90: ...ppears and the screen returns to Reset ALL YES 7 3 3 Configuration Mode The following procedure describes how to navigate the configuration mode menu 1 Press the MENU Button from any of the auto scrolling readings 2 Press DOWN to display the Configuration Mode CFG string in the A screen 3 Press ENTER to scroll through the configuration parameters starting at the SCrL Ct Pt screen ...

Страница 91: ...wn below FIGURE 7 4 Scroll Mode Configuration When in scroll mode the unit scrolls each parameter for 7 seconds on and 1 second off The meter can be configured through software to only display selected screens In this case it will only scroll the selected displays 3 Push ENTER to select YES or no The screen scrolls to the CT parameters 7 3 5 Programming the Configuration Mode Screens Use the follo...

Страница 92: ...st digit of the B screen will also flash 4 Use the DOWN button to change the first digit 5 Use the RIGHT button to select and change the successive digits 6 When the new value is entered push ENTER twice This will display the Stor ALL no screen 7 Use the RIGHT button to scroll to change the value from no to YES 8 When the Stor ALL YES message is displayed press ENTER to change the setting The Stor...

Страница 93: ...rameters Press ENTER when Ct is the active parameter i e it is in the A screen and flashing This will display the and the Ct n CT numerator screen 2 Press ENTER again to change to display the Ct d CT denominator screen The Ct d value is preset to a 1 or 5 A at the factory and cannot be changed 3 Press ENTER again to select the to Ct S CT scaling value The Ct S value can be 1 10 or 100 Refer to Pro...

Страница 94: ...ENTER to scroll through the other CFG parameters Pressing DOWN or RIGHT displays the password screen see Reset Mode above for details 5 Press MENU to return to the main configuration menu Note Ct n and Ct S are dictated by Primary Voltage Ct d is secondary Voltage 7 3 7 Configuring the PT Setting Use the following procedure to program the PT setting 1 Push the DOWN Button to scroll through the con...

Страница 95: ...g 1 Push the DOWN Button to scroll through the Configuration Mode parameters Scroll CT PT Connection Cnct and Port The active parameter is in the A screen and is flashing 2 Press ENTER when Cnct is the active parameter i e it is in the A screen and flashing This will display the Cnct Connection screen To change this setting use the RIGHT button to scroll through the three settings Select the setti...

Страница 96: ...l through the configuration mode parameters 2 Press ENTER when POrt is the active parameter i e it is in the A screen and flashing as shown below The following parameters can be configured through the POrt menu The meter Address Adr a 3 digit number The Baud Rate bAUd Select from 9600 19 2 38 4 and 57 6 for 9600 19200 38400 and 57600 kbps respectively The Communications Protocol Prot Select rtU fo...

Страница 97: ...ove for details on changing values The next POrt screen is the baud rate bAUd The current baud rate is displayed on the B screen Refer to Programming the Configuration Mode Screens above for details on changing values The possible baud rate screens are shown below The final POrt screen is the Communications Protocol Prot The current protocol is displayed on the B screen Address 005 ...

Страница 98: ... operating mode The active parameter has the indicator light next to it on the right face of the meter Push the RIGHT button to view additional displays for that parameter A table of the possible displays in the operating mode is below Refer to Appendix A for a detailed navigation map of the operating mode Note Readings or groups of readings are skipped if not applicable to the meter type or hooku...

Страница 99: ...tionMaps Appendix A 1 Introduction The EPM6000 meter can be configured and a variety of functions performed using the BUTTONS on the meter face An Overview of the Elements and Buttons on the meter face can be found in Chapter 6 An Overview of Programming using the BUTTONS can be found in Chapter 7 The meter can also be programmed using software see Communicator EXT 3 0 Manual ...

Страница 100: ...ext page They show in detail how to move from one screen to another and from one Display Mode to another using the buttons on the face of the meter All Display Modes will automatically return to Operating Mode after 10 minutes with no user activity Appendix A 2 1 EPM6000 Navigation Map Titles Main Menu Screens Sheet 1 Operating Mode Screens Sheet 2 Reset Mode Screens Sheet 3 Configuration Mode Scr...

Страница 101: ...APPENDIX A EPM6000 NAVIGATION MAPS NAVIGATION MAPS SHEETS 1 TO 4 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE A 3 ...

Страница 102: ...A 4 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE NAVIGATION MAPS SHEETS 1 TO 4 APPENDIX A EPM6000 NAVIGATION MAPS ...

Страница 103: ...APPENDIX A EPM6000 NAVIGATION MAPS NAVIGATION MAPS SHEETS 1 TO 4 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE A 5 ...

Страница 104: ...A 6 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE NAVIGATION MAPS SHEETS 1 TO 4 APPENDIX A EPM6000 NAVIGATION MAPS ...

Страница 105: ...troduction The Modbus Map for the EPM6000 Meter gives details and information about the possible readings of the meter and about the programming of the meter The EPM6000 can be programmed using the buttons on the face plate of the meter Chapter 7 The meter can also be programmed using software For a Programming Overview see section 5 2 of this manual For further details see the Communicator EXT 3 ...

Страница 106: ...tion Registers 1000 5003 details the Meter s Readings including Primary Readings Energy Block Demand Block Maximum and Minimum Blocks THD Block Phase Angle Block and Status Block Operating Mode readings are described in Section 7 3 4 Commands Section Registers 20000 26011 details the Meter s Resets Block Programming Block Other Commands Block and Encryption Block Programmable Settings Section Regi...

Страница 107: ...hout any termination charcters Example EPM6000 would be 4 registers containing 0x5378 0x6172 0x6B31 0x3030 SINT16 UINT16 16 bit signed unsigned integer SINT32 UINT32 32 bit signed unsigned integer spanning 2 registers The lower addressed register is the high order half FLOAT 32 bit IEEE floating point number spanning 2 registers The lower addressed register is the high order half i e contains the ...

Страница 108: ...so the Exponent value is 10 The Mantissa is 11000010001110110111001 binary With the implied leading 1 the Mantissa is 1 C23B72 hex The Floating Point Representation is therefore 1 75871956 x 210 Decimal equivalent 1800 929 Note Exponent the whole number before the decimal point Mantissa the positive fraction after the decimal point Register 0 1 Byte 0 1 0 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 ...

Страница 109: ...nly 0383 0384 900 901 Watts 3 Ph total FLOAT 9999 M to 9999 M watts 2 0385 0386 902 903 VARs 3 Ph total FLOAT 9999 M to 9999 M VARs 2 0387 0388 904 905 VAs 3 Ph total FLOAT 9999 M to 9999 M VAs 2 Block Size 6 Primary Readings Block 60 cycles IEEE Floating Point read only 03E7 03E8 1000 1001 Volts A N FLOAT 0 to 9999 M volts 2 03E9 03EA 1002 1003 Volts B N FLOAT 0 to 9999 M volts 2 03EB 03EC 1004 1...

Страница 110: ... FLOAT 0 to 9999 M amps 2 07D3 07D4 2004 2005 Amps C Average FLOAT 0 to 9999 M amps 2 07D5 07D6 2006 2007 Positive Watts 3 Ph Average FLOAT 9999 M to 9999 M watts 2 07D7 07D8 2008 2009 Positive VARs 3 Ph Average FLOAT 9999 M to 9999 M VARs 2 07D9 07DA 2010 2011 Negative Watts 3 Ph Average FLOAT 9999 M to 9999 M watts 2 07DB 07DC 2012 2013 Negative VARs 3 Ph Average FLOAT 9999 M to 9999 M VARs 2 07...

Страница 111: ... 0 to 9999 M amps 2 0C2B 0C2C 3116 3117 Amps C Maximum Avg Demand FLOAT 0 to 9999 M amps 2 0C2D 0C2E 3118 3119 Positive Watts 3 Ph Maximum Avg Demand FLOAT 0 to 9999 M watts 2 0C2F 0C30 3120 3121 Positive VARs 3 Ph Maximum Avg Demand FLOAT 0 to 9999 M VARs 2 0C31 0C32 3122 3123 Negative Watts 3 Ph Maximum Avg Demand FLOAT 0 to 9999 M watts 2 0C33 0C34 3124 3125 Negative VARs 3 Ph Maximum Avg Deman...

Страница 112: ... 0FC4 4030 4037 Phase C Current same as Phase A Current 0th to 7th harmonic magnitudes 8 0FC5 0FC8 4038 4041 Phase C Voltage same as Phase A Voltage 0th to 3rd harmonic magnitudes 4 Block Size 42 Phase Angle Block14 read only 1003 1003 4100 4100 Phase A Current SINT16 1800 to 1800 0 1 degree 1 1004 1004 4101 4101 Phase B Current SINT16 1800 to 1800 0 1 degree 1 1005 1005 4102 4102 Phase C Current ...

Страница 113: ...5000 Force Meter Restart UINT16 password5 causes a watchdog reset always reads 0 1 Block Size 1 Encryption Block read write 658F 659A 26000 26011 Perform a Secure Operation UINT16 encrypted command to read password or change meter type 12 Block Size 12 Programmable Settings Section See note 15 Basic Setups Block write only in PS update mode 752F 752F 30000 30000 CT multiplier denominator UINT16 bi...

Страница 114: ... bargraph UINT16 0 to 9999 none If non zero and user settings bit g is set this value replaces CT numerator in the full scale current calculation 1 7540 7547 30017 30024 Meter Designation ASCII 16 char none 8 7548 7548 30025 30025 COM1 setup UINT16 bit mapped dddd 0100110 dddd reply delay 50 msec ppp protocol 1 Modbus RTU 2 Modbus ASCII 3 DNP bbb baud rate 1 9600 2 19200 4 38400 6 57600 1 7549 754...

Страница 115: ...C4A 9C4A 40011 40011 Power Factor 3 Ph total UINT16 1047 to 3047 none 1047 1 2047 0 3047 1 pf register 2047 1000 1 9C4B 9C4B 40012 40012 Frequency UINT16 0 to 2730 Hz 0 45 or less 2047 60 2730 65ormore freq 45 register 4095 30 1 9C4C 9C4C 40013 40013 Volts A B UINT16 2047 to 4095 volts 2047 0 4095 300 1 9C4D 9C4D 40014 40014 Volts B C UINT16 2047 to 4095 volts volts 300 register 2047 2047 1 9C4E 9...

Страница 116: ...matically terminates via reset 9 Reset commands make no sense if the meter state is LIMP An illegal function exception will be returned 10 Energy registers should be reset after a format change 11 Entities to be monitored against limits are identified by Modbus address Entities occupying multiple Modbus registers such as floating point values are identified by the lower register address If any of ...

Страница 117: ...ue then the meter will stay in LIMP mode Please read the comments section or the range for each register in programmable settings section for acceptable 16 If V Switch is 1 or 2 and protocol ppp is set to 3 DNP then meter will use the MODBUS RTU protocol as DNP is supported by V Switch 3 or above Table Appendix B 1 Modbus Register Map Sheet 9 of 9 Hex Decimal Description1 Format Range6 Units or Re...

Страница 118: ...B 14 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE MODBUS REGISTER MAP APPENDIX B MODBUS MAPPING FOR EPM6000 ...

Страница 119: ...1 EPM6000 Multi function Power Metering System Appendix C DNP Mapping for EPM6000 Digital Energy Multilin DNPMappingforEPM6000 Appendix C 1 Introduction The DNP Map for the EPM6000 Meter shows the client server relationship in the EPM6000 s use of DNP Protocol ...

Страница 120: ...UINT32 0 to 99999999 multiplier 10 n d where n and d are derived from the energy format n 0 3 or 6 per energy format scale and d number of decimal places W hr example 20 1 4 W hours Negative UINT32 0 to 99999999 W hr energy format 7 2K and W hours counter 1234567 20 2 4 VAR hours Positive UINT32 0 to 99999999 VAR hr n 3 K scale d 2 2 digits after decimal point multiplier 10 3 2 101 10 so energy is...

Страница 121: ...Angle Phase A Current SINT16 1800 to 1800 0 1 degree 30 21 5 Angle Phase B Current SINT16 1800 to 1800 0 1 degree 30 22 5 Angle Phase C Current SINT16 1800 to 1800 0 1 degree 30 23 5 Angle Volts A B SINT16 1800 to 1800 0 1 degree 30 24 5 Angle Volts B C SINT16 1800 to 1800 0 1 degree 30 25 5 Angle Volts C A SINT16 1800 to 1800 0 1 degree 30 26 5 CT numerator SINT16 1 to 9999 N A none CT ratio 30 2...

Страница 122: ...C 4 EPM6000 MULTI FUNCTION POWER METERING SYSTEM USER GUIDE DNP MAPPING DNP 1 TO DNP 2 APPENDIX C DNP MAPPING FOR EPM6000 ...

Страница 123: ...n on the back face of the meter RS 485 RS 485 provides multi drop network communication capabilities Multiple meters may be placed on the same bus allowing for a Master device to communicate with any of the other devices Appropriate network configuration and termination should be evaluated for each installation to insure optimal performance Communication Parameters EPM6000 meters communicate in DN...

Страница 124: ... is necessary after a meter has been restarted either by applying power to the meter or reprogramming the meter The meter must receive a RESET command before confirmed communication may take place Unconfirmed communication is always possible and does not require a RESET User Data Function 3 After receiving a request for USER DATA the meter will generate a Data Link CONFIRMATION signaling the recep...

Страница 125: ...ER GUIDE D 3 Appendix D 3 Transport Layer The Transport Layer as implemented on EPM6000 meters is subject to the following considerations Transport Header Multiple frame messages are not allowed for EPM6000 meters Each Transport Header should indicate it is both the first frame FIR 1 as well as the final frame FIN 1 ...

Страница 126: ...unction 1 Objects supporting the READ function are Binary Outputs Object 10 Counters Object 20 Analog Inputs Object 30 Class Object 60 These Objects may be read either by requesting a specific Variation available as listed in this document or by requesting Variation 0 READ request for Variation 0 of an Object will be fulfilled with the Variation listed in this document Write Function 2 Objects sup...

Страница 127: ...ccumulate power generated or consumed over time as Hour Readings which measure positive VA Hours and positive and negative W Hours and VAR Hours These readings may be reset usinga Control Relay Output Block object Obj 12 This Binary Output Status point reports whether the Energy Readings are in the process of being reset or if they are accumulating Normally readings are being accumulated and the s...

Страница 128: ...cumulate power generated or consumed over time as Hour Readings which measure positive VA Hours and positive and negative W Hours and VAR Hours These readings may be reset using Point 0 Use of the DIRECT OPERATE Function 5 function will operate only with the settings of Pulsed ON Code 1 of Control Code Field once Count 0x01 for ON 1 millisecond and OFF 0 milliseconds ...

Отзывы: