![background image](http://html.mh-extra.com/html/ge/entelliguard-akr-30-800/entelliguard-akr-30-800_installation-manual_122812058.webp)
57
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH41549 R05
AKD-8—Neutral Disconnect Assembly, Bus Compartment
The AKD-8 EntelliGuard R Circuit Breaker uses an air-core Rogowski Current sensor to measure current level.
Legacy AK and AKR breakers used iron core CTs. For the Retrofill breaker to calculate the current levels on a
4-wire circuit, the Neutral Iron Core CT in the cable compartment needs to be replaced with a Rogowski style
CT.
The Rogowski CT comes mounted on copper bars matching the same hole-pattern as the existing neutral
bar. Neutral CT wires from the Rogowski coil to the AKD-8 gray terminal blocks must be run as a “twisted
pair”.
Table 8
shows the Rogowski assembly part numbers for AKD-8 Switchgear.
AKD-8—Rogowski Assembly Part Numbers
Table 8. AKD-8—Rogowski Assemblies (Neutral Bus Part Numbers)
Breaker/Switchgear
Rogowski Assembly or
Neutral Bus Bar
Part Number
Figure References for Assembly Drawings
AKD8 400A
10108266G1
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD8 600A
10108266G2
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD8 800A
10108266G3
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD8 1000A
10108266G4
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD8 1200A
10108266G5
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD8 1600A
10108266G6
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD8 2000A
10108266G7
Figure 40.
Neutral Bus Rogowski ASM 10108266
AKD-8-Neutral CT Adapter 400A-5000A
This is a miniature Rogowski coil. It mounts between the incoming Neutral disconnect and the breaker trip
unit. It converts the signal from an iron Core Neutral sensor to a Rogowski voltage output which is wired to
the Breaker's Trip Unit Neutral input connections.
The Neutral CT Adapter supports iron core Neutral sensors compatible with MicroVersa Trip, MVT RMS-9,
MVT Plus & PM, Power Plus, Pro Trip and EntelliGuard TU rated from 150 to 5000 Amps as used in GE
switchboards and switchgear from 1979-2015. It is available in five variations (shown in Table below).
Catalog Number
Supported Neutral CT ratings (A)
RNCTA1200 (R)
600, 1200
RNCTA2000 (R)
150, 200, 400, 800, 1000, 1600, 2000
RNCTA3000 (R)
3000
RNCTA4000 (R)
2500, 3200, 4000
RNCTA5000 (R)
5000