5.1.27 B-## Braking Functions
Par. No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
B-0#
B-00
DC Hold Current
50 %
All set-ups
TRUE
0
Uint8
B-01
DC Brake Current
50 %
All set-ups
TRUE
0
Uint16
B-02
DC Braking Time
10 s
All set-ups
TRUE
-1
Uint16
B-03
DC Brake Cut In Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
B-04
DC Brake Cut In Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
B-06
Parking Current
50 %
All set-ups
TRUE
0
Uint16
B-07
Parking Time
3 s
All set-ups
TRUE
-1
Uint16
B-1#
B-10
Brake Function
ExpressionLimit
All set-ups
TRUE
-
Uint8
B-11
Brake Resistor (ohm)
ExpressionLimit
All set-ups
TRUE
-2
Uint32
B-12
Brake Power Limit (kW)
ExpressionLimit
All set-ups
TRUE
0
Uint32
B-13
Braking Thermal Overload
[0] Off
All set-ups
TRUE
-
Uint8
B-15
Brake Check
[0] Off
All set-ups
TRUE
-
Uint8
B-16
AC brake Max. Current
ExpressionLimit
All set-ups
TRUE
-1
Uint32
B-17
Over-voltage Control
[2] Enabled
All set-ups
TRUE
-
Uint8