LP 3/5/6-11 installation drawing
Model
Heat
dissipation
Dimensions
Bottom
100% load
50% load
h
w
d
Weight
Air flow
100%
load
Amb.
temp.
Rel.
humidity
non-cond.
Altitude
(max 4000m)
Branch
protection
slow
Input/output
wiring
Minimum free space
required
front side rear
x y
LP
W
Btu/hr
W
Btu/hr
mm
mm
mm
kg
m3/hr
°C
%
m
A
mm2
AWG
mm
mm
mm
mm
mm
3-11
327
1116
211
720
537
313
590
85
330
-10-40
<95
16
4
12
100
50
200
184
448
5-11
545
1860
350
1195
537
313
590
110
330
-10-40
<95
25
6
10
100
50
200
184
448
6-11
655
2235
423
1445
537
313
590
115
330
-10-40
<95
<1000,
derating 12.5%
per 1000
25
6
10
100
50
200
184
448
5 - COMMON
9 - GENERAL ALARM
4 - NOT USED
8 - MAINS FAILURE
3 - SERIAL DATA IN / UPS SHUTDOWN
7 - PLUG&PLAY / RTS
2 - SERIAL DATA OUT
6 - BYPASS ACTIVE
1 - BATTERY LOW
INPUT
OUTPUT
EARTH CONNECTION
IS ESSENTIAL
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN
RPA CARD
PARALLEL OPERATION
SNMP CARD OR RELAY CARD
RS232 / CONTACT, SEE BELOW
OFF
ON
UPS
STATIC
BYPASS
MAINS
NOT ON LP 3-11
TOP
MANUAL BYPASS SWITCH
BATTERY PACK CONNECTOR
SWITCH / CIRCUIT BREAKERS
OPTION SLOTS
RS232 / CONTACT INTERFACE
SUB-D PINNING
I/O TERMINALS
SWIVELS
CASTORS
w
h
d
NORMAL: POSITION 1
(LOAD ON UPS)
SERVICE: POSITION 2
(LOAD ON BYPASS)