g
GT Model
1000R UL
1500R UL
2200R UL
3000R UL
Capacity
1kVA/800W
1.5kVA/1200W
2.kKVA/1600W
3kVA/2400W
Rated Voltage
100V, 110V, 120V
Voltage Range
80V~138V (full load); 65V~80V (70% load)
Frequency
50Hz / 60Hz (± 4.8 Hz)
Input
Power Factor
≥
0.97
Voltage
100V, 110V, 120V
Frequency 50Hz
/
60Hz
Voltage Regulation
± 2%
Frequency Accuracy
± 0.05 Hz
Wave Form
pure sine wave
Transient Response
± 8% (10%~90% linear load)
THD (linear load)
≤
3%
≤
3%
≤
3%
≤
4%
THD (computer load)
≤
6%
Overload Capacity
105%~125% for 3mins; 125%~150% for 30secs; >150% for 1sec
Crest Factor
3:1
Output
Efficiency (AC-AC)
≥
87%
Outlet
Receptacle NEMA
TYPE
Battery Voltage
36V
48V
48V
72V
Battery Type (Lead
acid)
12V/7Ah 12V/9Ah
Back-up Time
(Typical)
5mins
Battery
Recharge Time
4~6 hours after complete discharge to recover 90%
Transfer
Time
Transfer Time
zero
LED Status
On-line / Bypass / On-battery / Overload / Battery Low / Fault
Battery Replace / Battery Level / Load Level
LED
Alarm buzzer
DB9 RS232/dry
contact
Interface
SNMP Slot
internal
Noise (At 1 Meter)
40dB(A)
45dB(A)
45dB(A)
47dB(A)
Operating
Temperature
0~40°C (32~104°F)
Environ-
ment
Humidity 0%~90%
(non-condensing)
Safety UL/cUL
EMC
FCC Class A (1.5, 2.2, 3kVA) /B (1kVA)
CISPR PUB 22 Class B; TUV/EMC; CE (1, 1.5kVA)
CISPR PUB 22 Class A (2.2, 3kVA)
Safety
Approval
Lightning IEEE
62.41
Category
A
Battery Start
yes
Extended Battery
Bank
yes (optional for longer runtime)
Others
Long Time Model
yes (optional)
Dimensions
(W
×
D
×
H)
440x434x88 mm
17.3x17.1x3.4 inch
440x526x88 mm
17.3x20.7x3.4 inch
440x503x132 mm
17.3x19.8x5.2 inch
Appearance
Weight
17kg
37.4 lbs
19kg
41.8 lbs
24kg
52.9 lbs
33 kg
72.7 lbs
All specifications are subject to change without prior notice.