TECHNICAL CHARACTERISTICS
GEK-105597C
DBT Digital Trip Coil Supervision Relay
11
5. TECHNICAL CHARACTERISTICS
5.1 TECHNICAL CHARACTERISTICS
•
AUXILIARY SUPPLY
A ripple factor is allowed provided that the instantaneous voltage does not exceed the indicated upper and lower
limits. For example, on the 110-125 V model the voltage at any given time should never drop below 88 V nor go
above 150 V.
•
110-125 V DC
±
20%
•
220-250 V DC
±
20%
•
TEMPERATURE RANGES
Operational range:
-25ºC to + 55ºC
Storage range:
-40ºC to + 70ºC
Complies with IEC 255-6 and ANSI C37.90 Standards.
•
HUMIDITY
Up to 95% without condensation.
•
OUTPUT CONTACTS
Breaking
capacity:
4000
VA
Maximum DC voltage: 300 V DC
Maximum AC voltage: 440 V AC
Continuously:
16
A
Making
capacity: 30
A
•
ACCURACY
Voltage:
±
5%
Resistance:
±
10%
Time:
20
ms
•
VOLTAGE CIRCUIT BURDEN
110-125 V DC model: 48 k
Ω
220-250 V DC model: 96 k
Ω
DIGITAL INPUT BURDEN
110-125 V DC model: 66 k
Ω
220-250 V DC model: 132 k
Ω
•
AUXILIARY POWER CONSUMPTION
Standby:
3 W (only NC alarm relay activated)
Operated:
7.5 W (all relays activated)
Содержание DBT
Страница 5: ...DESCRIPTION 4 DBT Digital Trip Coil Supervision Relay GEK 105597C ...
Страница 9: ...MODEL LIST 8 DBT Digital Trip Coil Supervision Relay GEK 105597C ...
Страница 15: ...TECHNICAL CHARACTERISTICS 14 DBT Digital Trip Coil Supervision Relay GEK 105597C ...
Страница 24: ...FIGURES GEK 105597C DBT Digital Trip Coil Supervision Relay 23 FIGURE 1 NAMEPLATE 226B1298H3 ...
Страница 29: ...FIGURES 28 DBT Digital Trip Coil Supervision Relay GEK 105597C FIGURE 6 REAR TERMINAL PLATE 226B6292H1 ...
Страница 30: ...FIGURES GEK 105597C DBT Digital Trip Coil Supervision Relay 29 FIGURE 7 BLOCK DIAGRAM ...