9 APPLICATION OF SETTINGS 9.1APPLICATION GUIDELINES
9.1.1 INTRODUCTION
This chapter provides general application guidelines for stepped distance, overcurrent and pilot protection. Where relevant,
design details and performance characteristics of the D60 are given to facilitate the process of setting the relay for a given
application.
9.1.2 IMPACT OF MEMORY POLARIZATION
As explained, the D60 uses a memorized positive sequence voltage as a polarizing signal in order to achieve dependable
operation for forward faults and secure non-operation for reverse faults.
The dynamic shift of the characteristic ensures improved directionality, but it also means that if a backup function is
required for a reverse fault on the bus, then it is appropriate to reverse Zone 4 so that a time delayed backup function may
be obtained. As mentioned earlier, it may be beneficial to also avoid extremely large reach settings by setting a remote
backup so that it is reverse looking. This strategy can be beneficial if the reduced reach enhances the discrimination
between the load and fault conditions.
9.1.3 HIGH-SET OVERCURRENT ELEMENTS
Especially at low SIR values, fast fault clearance times may be seen as extremely important, both from system stability, and
from equipment damage viewpoints. The high-set overcurrent element, when set appropriately, can be extremely useful in
achieving these goals. It helps the setting calculations if the system impedances are reasonably well known.
The overcurrent pick up should be set to the greater of the following values:
1.
The maximum infeed seen by the relay, for a close in reverse fault.
2.
The maximum fault level seen by the relay for a fault at 100% of the protected line.
The maximum error of the phase overcurrent elements is below 2%. A safety factor of 1.25 should be used to account for
relay errors and system impedance uncertainty.
If CT saturation is an issue such as close to a generation where long lasting dc components are likely to saturate the CTs, it
should be noted that the instantaneous overcurrent elements require 1.33 cycle of data to operate for a multiple of pickup of
1.01. For higher multiples of pickup, the relation between the multiple of pickup and the amount of data required for opera-
tion before complete CT saturation is approximately linear. For example, for a multiple of pickup of 4, approximately 1.33 /
4 = 0.332 of power cycle is required by the phase instantaneous overcurrent element to operate. The above information
should not be confused with the operating time, which includes some inherent delays such as a trip rated output contact.
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...