D60 Line Distance Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
Figure 5–161: OPEN POLE DETECTOR LOGIC (Sheet 2 of 2)
g) BROKEN CONDUCTOR DETECTION
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BROKEN CONDUCTOR 1(2)
Two broken conductor detection elements are provided.
The broken conductor function will detect a transmission line broken conductor condition or a single-pole breaker malfunc-
tion condition through checking the phase current input signals and the I_2 / I_1 ratio. The intention of this function is to
detect a single-phase broken conductor only. As such two-phase or three-phase broken conductors cannot be detected.
BROKEN CONDUCTOR 1
BROKEN CONDUCTOR 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BROKEN CONDUCTOR 1
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
BROKEN CONDUCTOR 1
I2/I1 RATIO:
20%
Range: 20.0% to 100.0% in steps of 0.1%
MESSAGE
BROKEN CONDUCTOR 1
I1 MIN: 0.10 pu
Range: 0.05 to 1.00 pu in steps of 0.01
MESSAGE
BROKEN CONDUCTOR 1
I1 MAX: 1.50 pu
Range: 0.05 to 5.00 pu in steps of 0.01
MESSAGE
BROKEN CONDUCTOR 1
PKP DELAY: 20.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BROKEN CONDCT 1 BLK:
Off
Range: FlexLogic operand
MESSAGE
BROKEN CONDUCT 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BROKEN CONDUCT 1
EVENTS: Disabled
Range: Disabled, Enabled
OR
837038A2.CDR
OR
OR
OR
OR
XOR
FLEXLOGIC OPERAND
TRIP PHASE A
PHASE A
TIMER
0.5 cycles
0
ENABLED
from the trip output element
OR
FLEXLOGIC OPERAND
TRIP PHASE B
PHASE B
TIMER
0.5 cycles
0
from the trip output element
OR
FLEXLOGIC OPERAND
TRIP PHASE C
PHASE C
TIMER
0.5 cycles
0
from the trip output element
AND
AND
AND
TIMER
0
20 ms
TIMER
0
20 ms
TIMER
0
20 ms
FLEXLOGIC OPERAND
OPEN POLE BLK N
FLEXLOGIC OPERAND
OPEN POLE OP A
Φ
FLEXLOGIC OPERAND
OPEN POLE BLK AB
FLEXLOGIC OPERAND
OPEN POLE OP B
Φ
FLEXLOGIC OPERAND
OPEN POLE BLK BC
FLEXLOGIC OPERAND
OPEN POLE OP C
Φ
FLEXLOGIC OPERAND
OPEN POLE BLK CA
FLEXLOGIC OPERAND
OPEN POLE OP
AND
AND
AND
from open pole logic sheet 1
from open pole logic sheet 1
from open pole logic sheet 1
from open pole logic sheet 1
SETTING
= Accelerated
= Traditional
Open Pole Mode
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...