GE Multilin
D60 Line Distance Protection System
5-153
5 SETTINGS
5.5 FLEXLOGIC
5
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
(will not appear unless ordered)
(will not appear unless ordered)
Cont Op 1 VOff
Cont Op 2 VOff
(will not appear unless ordered)
(will not appear unless ordered)
INPUTS/OUTPUTS
Direct inputs
DIRECT INPUT 1 On
DIRECT INPUT 32 On
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Remote double-
point status inputs
RemDPS Ip 1 BAD
RemDPS Ip 1 INTERM
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
Asserted while the remote double-point status input is in the bad state.
Asserted while the remote double-point status input is in the intermediate
state.
Asserted while the remote double-point status input is off.
Asserted while the remote double-point status input is on.
REMDPS Ip 2...
Same set of operands as per REMDPS 1 above
INPUTS/OUTPUTS:
Remote inputs
REMOTE INPUT 1 On
REMOTE INPUT 2 On
REMOTE INPUT 3 On
REMOTE INPUT 32 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual inputs
Virt Ip 1
On
Virt Ip 2
On
Virt Ip 3
On
Virt Ip 64
On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual outputs
Virt Op 1 On
Virt Op 2 On
Virt Op 3 On
Virt Op 96 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
LED INDICATORS:
Fixed front panel
LEDs
LED IN SERVICE
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
Asserted when the front panel IN SERVICE LED is on.
Asserted when the front panel TROUBLE LED is on.
Asserted when the front panel TEST MODE LED is on.
Asserted when the front panel TRIP LED is on.
Asserted when the front panel ALARM LED is on.
Asserted when the front panel PICKUP LED is on.
Asserted when the front panel VOLTAGE LED is on.
Asserted when the front panel CURRENT LED is on.
Asserted when the front panel FREQUENCY LED is on.
Asserted when the front panel OTHER LED is on.
Asserted when the front panel PHASE A LED is on.
Asserted when the front panel PHASE B LED is on.
Asserted when the front panel PHASE C LED is on.
Asserted when the front panel NEUTRAL/GROUND LED is on.
LED INDICATORS:
LED test
LED TEST IN PROGRESS
An LED test has been initiated and has not finished.
LED INDICATORS:
User-programmable
LEDs
LED USER 1
Asserted when user-programmable LED 1 is on.
LED USER 2 to 48
The operand above is available for user-programmable LEDs 2 through 48.
PASSWORD
SECURITY
ACCESS LOC SETG OFF
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
Asserted when local setting access is disabled.
Asserted when local setting access is enabled.
Asserted when local command access is disabled.
Asserted when local command access is enabled.
Asserted when remote setting access is disabled.
Asserted when remote setting access is enabled.
Asserted when remote command access is disabled.
Asserted when remote command access is enabled.
Asserted when a password entry fails while accessing a password protected
level of the D60.
Table 5–17: D60 FLEXLOGIC OPERANDS (Sheet 10 of 11)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...