5-148
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
A description of the operation of the breaker control and status monitoring features from the front panel is provided in
chapter 4.
There are two breaker control elements for each CT/VT module installed. The following settings are available for each
breaker control element.
BREAKER 1 FUNCTION
— This setting enables and disables the operation of the breaker 1 control feature.
BREAKER1 PUSH BUTTON CONTROL
— Set to “Enable” to allow front panel pushbutton open/close control operations.
BREAKER1 TAGGING
— Set to "Enable" to allow the graphical front panel to tag breaker 1. When tagged, the following
operations are disabled: pushbutton open/close, IEC 61850 open/close, and close command initiated by
BREAKER 1 CLOSE
setting. The trip command issued by the Trip Out element or
BREAKER 1 OPEN
setting is not affected.
BREAKER1 SUBSTITUTN
— Set to "Enable" to allow the graphical front panel to substitute breaker 1 status. When substituted,
breaker 1 control open/close status is forced to the substituted value.
BREAKER1 BYPASS
— Set to "Enable" to allow the graphical front panel to bypass breaker 1 interlocking. When asserted,
BREAKER 1 BLK OPEN
and
BREAKER 1 BLK CLOSE
settings are bypassed.
BREAKER1 AR BLOCK
—Set to "Enable" to generate an operand to block the Autoreclose element.
The Autoreclose element is not automatically inhibited by
BLOCK AR
from the front panel. If the autoreclose scheme needs
to be inhibited, set setting
AR BLOCK
in the corresponding autoreclose element with the
BREAKER 1 BLK RCLS
operand.
BREAKER 1 NAME
— Assign a user-defined name (up to six characters) to the breaker. This name is used in flash messages
related to breaker 1.
BREAKER 1 MODE
— Selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-Pole” mode where all
breaker poles are operated either independently or simultaneously.
BREAKER 1 OPEN
— Selects an operand that when activated, and unless blocked, initiates the Breaker 1 open and individual
phase trip commands.
BREAKER 1 BLK OPEN
— Selects an operand that prevents initiation of Breaker 1 open and individual phase trip commands.
This setting can be used for blocking circuit breaker tripping for instance when breaker monitoring detects conditions such
as low SF
6
gas density during which breaker opening can cause damage.
BREAKER 1 CLOSE
— Selects an operand that when activated, and unless blocked, initiates the Breaker 1 close commands.
BREAKER 1 BLK CLOSE
— Selects an operand that prevents initiation of Breaker 1 close commands. This setting can be used
for blocking circuit breaker closing, for instance to prevent closing into a closed ground switch.
BREAKER1
Φ
A/3P CLSD
— Selects an operand, usually a contact input connected to a breaker auxiliary position tracking
mechanism. This input is for a normally-open 52/a status input that creates a logic 1 when the breaker is closed. If the
BREAKER 1 MODE
setting is selected as "3-Pole," this setting selects a single 52/a input as the operand used to track the
breaker open or closed position. If the mode is selected as "1-Pole," the input mentioned is used to track phase A and the
BREAKER 1
Φ
B
and
BREAKER 1
Φ
C
settings select operands to track phases B and C, respectively.
BREAKER1
Φ
A/3P OPND
— Selects an operand, usually a contact input, that is for a normally-closed 52/b status input that
creates a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted 52/a status
signal or the inverted
BREAKER 1 CLOSED
status signal can be used.
BREAKER 1
Φ
B CLOSED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER 1
Φ
B OPENED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER 1
Φ
C CLOSED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1
Φ
C OPENED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER 1 TOPERATE
— This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS
FlexLogic operand is asserted for alarm or blocking purposes.
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...