![background image](http://html.mh-extra.com/html/ge/d20-me/d20-me_quick-start-manual_123211005.webp)
D20 ME
Quick Start Guide
GE Power Systems
D20 ME Jumper Options,
Continued
Table: VME
Jumper
Options
The following tables summarize the jumper settings for each board function
and position that is installed in a CCU for D20 or D200:
Single Node
For D20 or D200:
Board Function
JP1
Master /
Slave
JP2
VME Address Bits
4 3 2 1
JP3-1
RTC -
SERCLOCK
JP3-2
RTC -
BRTC
Single
Node
OUT IN IN IN IN
OUT
IN
Multi-Node
For D20 or D200:
Board Function
JP1
Master /
Slave
JP2
VME Address Bits
4 3 2 1
JP3-1
RTC -
SERCLOCK
JP3-2
RTC -
BRTC
Node
#1
OUT IN IN IN
OUT
IN
IN
Node
#2
IN
IN IN OUT IN
IN
OUT
Node #3
IN
IN
IN
OUT
OUT
IN
OUT
Node
#4
IN
IN OUT IN IN
IN
OUT
Node
#5
IN
IN OUT IN OUT
IN
OUT
Node
#6
IN
IN OUT
OUT IN
IN
OUT
Node
#7
IN
IN OUT OUT OUT
IN
OUT
Node
#8
IN OUT
IN IN IN
IN
OUT
Notes:
•
Single Node is the factory default configuration
•
If you have a single-node implementation with Ethernet or Memory expansion or
both, configure jumpers as Single Node
994-0025-1.00-8
General
5
Full
Release