![GE CTF878 Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/ge/ctf878/ctf878_user-and-service-manual_128351047.webp)
Troubleshooting
4-3
February 2009
Displaying Diagnostic
Parameters
As part of its measurement menu, the CTF878 offers a list of
diagnostic parameters to aid in troubleshooting in the event of
flowcell, transducer, or electrical problems. You can select any
diagnostic parameter for display as a measurement (see
Displaying
and Configuring Data,
Chapter 2 of the
Programming Manual
or
Chapter 4 of the
Startup Guide
). Table 4-2 below shows all the
available diagnostic parameters and ranges.
Table 4-2: Diagnostic Parameters
Diagnostic
Parameter
Displays
Good
Bad
Carrier
Amplitude
Up
The peak voltage amplitude (millivolts) of the
upstream channel received signal before
demodulation.
75–1100mV
< 75mV or
> 1100mV
Carrier
Amplitude
Dn
The peak voltage amplitude (millivolts) of the
downstream channel received signal before
demodulation.
75–1100mV
< 75mV or
> 1100mV
Carrier Gain
Up
The gain of the variable stage of the upstream
channel received signal.
–6 to +31dB
---
Carrier Gain
Dn
The gain of the variable stage of the
downstream channel received signal.
–6 to +31dB
---
I Amplitude
Up
The RMS voltage amplitude (millivolts) of the
upstream channel demodulated signal I*.
295–1180mV
< 295mV or
> 1180mV
I Amplitude
Dn
The RMS voltage amplitude (millivolts) of the
downstream channel demodulated signal I*.
295–1180mV
< 295mV or
> 1180mV
Q Amplitude
Up
The RMS voltage amplitude (millivolts) of the
upstream channel demodulated signal Q*.
295–1180mV
< 295mV or
> 1180mV
Q Amplitude
Dn
The RMS voltage amplitude (millivolts) of the
downstream channel demodulated signal Q*.
295–1180mV
< 295mV or
> 1180mV
Modulation
Gain Up
The gain of the variable stage of the upstream
channel demodulated signals I and Q*.
–16 to +31dB
---
Modulation
Gain Dn
The gain of the variable stage of downstream
channel demodulated signals I and Q*.
–16 to +31dB
---
Tau
The time it takes for fluids to move from the
upstream channel to the downstream channel.
N/A
N/A
Correlation
SNR
The Correlation Signal–to–Noise Ratio.
> 10
< 10
* Signals I and Q are those modulated carrier waves which have been converted (demodulated)
into a current equivalent to the original signal.
Содержание CTF878
Страница 1: ...GE Sensing Model CTF878 Clamp On Tag Flowmeter User s Service Manual ...
Страница 2: ...GE Sensing Model CTF878 Clamp On Tag Flowmeter User s Service Manual 910 254SA4 February 2009 ...
Страница 6: ...Chapter 1 ...
Страница 18: ...Chapter 2 ...
Страница 30: ...Chapter 3 ...
Страница 43: ...Chapter 4 ...
Страница 51: ...Chapter 5 ...
Страница 63: ...Appendix A ...
Страница 64: ...Service Record Introduction A 1 Data Entry A 1 ...
Страница 66: ...February 2009 A 2 Service Record Table A 1 Service Record Continued Date Description of Service Performed By ...