INSTRUCTIONS
CAUTION: Before Installing in a nuclear applica
tion, determine that the product Is intended for
such use.
� DANGER
HAZARD OF ELECTRICAL
SHOCK OR BURN.
COVER
SCREWS
JUMPER WlRE "A"
DISCONNECT ALL POWER
BEFORE SERVICING
READ INSTRUCTIONS
FOR THIS EQUIPMENT
LOW VOLTAGE
PROTECTION
(LVP)UNIT
/
Figure 1. CR1062RL manual motor starter with low voltage protection
GENERAL
The CA1062AL
&
SL manual motor starters are designed to
meet motor starter applications where low voltage protection Is
required. Low voltage protection (LVP) on the CR1062RL
&
SL is
provided by a solenoid assembly which de-energizes and turns off
the starter when a loss of power occurs. The motor cannot be
restarted until power is restored and the motor starter is turned to
the on position. Terminals are provided for the installation of a
remote stop contact. The CA1062AL
&
SL starters are also provid-
ed with thermal overload relays for motor overcurrent protection.
INSTALLATION AND WIRING
1. Be sure line power Is off before wiring.
2. Be sure that the low voltage protection solenoid coil is the
correct voltage. The coil voltage ls shown on the label attach
ed to t,he LVP unit.
3. Connect line and I08.d wires. To Install a remote stop, see
instructions below.
4. Select Jhe
_
proper_ ov8'rload heaters ·from the heater table
provided with the starter and install where shown in Figure 1.
5. Check the low voltage protection unit by"attemptlng to turn
on the.starter with the line power off. The starter should im
mediately turn off when the toggle or start button is released.
The starter should remain on when the line power is on, if not,
recheck coil voltage.
INSTALLATION OF A REMOTE STOP
1. Disconnect all power to the starter.
2. Locate: the top clamp type terminals on the LVP unit.
(Figure 1.)
3. Loosen the terminals and remove the jumper wire'' A".
(Figure 1.)
4. Wire the remote stop pilot device between the terminals.
CONNECTION DIAGRAM
�
r,1
ra1
�
:
e
7R:MOVE JUMP� "A"TO CONNECT
REMOTE STOP OPERATOR. WIRE
MOTOR
TO VACATED TERMINALS,
CONNECTIONS FOR 3 POLE SWITCH
USED IN 3 PHASE, 3 WIRE CIRCUIT
Figure 2. Typical connection diagram forCR1062RL and SL manual starters
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with
installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufflclently for the
Purchaser's purposes, the matter should be referfed to the nearest ABB Sales Office.
1
GEH
-
4737
Installation Instructions
CR1062RL and SL
manual motor starters
WITH LOW VOLTAGE PROTECTION (LVP)