Masoneilan SVI FF Instruction Manual
=
|
81
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Exiting Failsafe Using AMS
To exit Failsafe:
1. Inspect the (current) faults/status flags (Figure 40).
Figure 40 AMS Status/Faults
2. If there are:
No failsafe faults, the method
change app mode
works, but in most cases it is
unnecessary, and simply changing the Transducer block mode works fine.
Failsafe faults, they should be addressed (removed) first by:
a. Correcting the underlying cause.
b. Clearing the faults by:
i.) Scrolling down and pressing the button at the bottom of Figure 40.
ii.) Reviewing the screen for repeating faults.
iii.) Switch mode to Manual or Auto as required.
Failsafe faults are listed in Table on page 80.