Appendix N. Changing Out of LO Mode
LO (local override) indicates that someone is working on the device from the local display.
Sometimes users forget to switch back the TB to Normal mode and the following results occur:
ALL commands are ignored from the Fieldbus:
The only command accepted is Set to Normal.
To resolve this problem, you need to have the positioner so that the LCD displays
Normal
so the
TB is out of
LO
mode. There are several different methods available to move the positioner out of
LO. All of these separate methods work:
Local Display
This procedure assumes that you are starting with a display displaying LO mode.
Press
+
until
Normal
appears (usually
Normal
), then click
*
.
You can verify that the action is complete by observing that the LCD automatically cycles
through the pressures and setpoints.
DTM
DD
DCS
Handheld
Asset Manager
Take care at all times that the positioner is not in or left in LO mode
inadvertently, as control commands from other sources can be
ignored!
Switching the display to Normal mode allows the positioner to
follow the Setpoint from the TB, which may move the valve.
WARNING
WARNING
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......