5.2 PRODUCT SETUP
5 SETTINGS
5
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
NETWORK 1(3)
These messages appear with the Ethernet card present.
The
PRT1 (2, 3) GOOSE ENABLED
setting provides the ability to disable/enable GOOSE transmission from the port.
PRT2 REDUNDANCY
determines if ports 2 and 3 operate in redundant or independent mode. In non-redundant mode, port 2
and 3 operate independently with their own MAC and IP address. In redundant mode, port 2 and 3 use the port 2 MAC and
IP address, port 3 is in standby mode and monitors its link to the Multilink switch, and when port 2 detects a problem with
the link then communication switches to port 3 until the link returns.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
behind a router). By setting a different
TCP/UDP PORT NUMBER
for a given protocol on each UR-series relay, the router can
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
NETWORK PORT 1
PRT1 IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT1 SUBNET IP MASK:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT1 GWY IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT1 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NETWORK PORT 2
PRT2 IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 SUBNET IP MASK:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 GWY IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 REDUNDANCY:
No
Range: No, Yes
MESSAGE
PRT2 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NETWORK PORT 3
PRT3 IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 SUBNET IP MASK:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 GWY IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...