B-46
B30 Bus Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
9993
Teleprotection Local Relay ID
0 to 255
---
1
F001
0
9994
Teleprotection Terminal 1 ID
0 to 255
---
1
F001
0
9995
Teleprotection Terminal 2 ID
0 to 255
---
1
F001
0
9996
Reserved (10 items)
0 to 1
---
1
F001
0
9A00
Teleprotection Input 1-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9A10
Teleprotection Input 2-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9A20
Teleprotection Output 1-n Operand (16 items)
0 to 4294967295
---
1
F300
0
9A40
Teleprotection Output 2-n Operand (16 items)
0 to 4294967295
---
1
F300
0
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
0 to 2
---
1
F134
1 (OK)
9AA1
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA2
Teleprotection Channel 2 Status
0 to 2
---
1
F134
2 (n/a)
9AA3
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA4
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9AAF
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9AB0
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9AC0
Teleprotection Input 1 States, 1 per register (16
items)
0 to 1
---
1
F108
0 (Off)
9AD0
Teleprotection Input 2 States, 1 per register (16
items)
0 to 1
---
1
F108
0 (Off)
Selector Switch Actual Values (Read Only)
A210
Selector Switch 1 Position
1 to 7
---
1
F001
0
A211
Selector Switch 2 Position
1 to 7
---
1
F001
1
Selector Switch Settings (Read/Write) (2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 4294967295
---
1
F300
0
A285
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A286
Selector 1 Acknowledge
0 to 4294967295
---
1
F300
0
A288
Selector 1 Bit0
0 to 4294967295
---
1
F300
0
A28A
Selector 1 Bit1
0 to 4294967295
---
1
F300
0
A28C
Selector 1 Bit2
0 to 4294967295
---
1
F300
0
A28E
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28F
Selector 1 Bit Acknowledge
0 to 4294967295
---
1
F300
0
A291
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A292
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A293
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A294
Reserved (10 items)
---
---
1
F001
0
A29E
...Repeated for Selector 2
Digital Counter (Read/Write Setting) (8 modules)
A300
Digital Counter 1 Function
0 to 1
---
1
F102
0 (Disabled)
A301
Digital Counter 1 Name
---
---
---
F205
“Counter 1"
A307
Digital Counter 1 Units
---
---
---
F206
(none)
A30A
Digital Counter 1 Block
0 to 4294967295
---
1
F300
0
A30C
Digital Counter 1 Up
0 to 4294967295
---
1
F300
0
A30E
Digital Counter 1 Down
0 to 4294967295
---
1
F300
0
A311
Digital Counter 1 Preset
–2147483647 to
2147483647
---
1
F004
0
A313
Digital Counter 1 Compare
–2147483647 to
2147483647
---
1
F004
0
Table B–10: MODBUS MEMORY MAP (Sheet 38 of 60)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...