5.7 CONTROL ELEMENTS
5 SETTINGS
5
•
BRK 1 FLSHOVR SPV A
to
BRK 1 FLSHOVR SPV C
: These settings specify FlexLogic operands (per breaker pole)
that supervise the operation of the element per phase. Supervision can be provided by operation of other protection
elements, breaker failure, and close and trip commands. A six-cycle time delay applies after the selected FlexLogic
operand resets.
•
BRK FLSHOVR PKP DELAY
: This setting specifies the time delay to operate after a pickup condition is detected.
Figure 5–76: BREAKER FLASHOVER SCHEME LOGIC
c) CT TROUBLE ZONE
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
CT TROUBLE ZONE 1(2)
This element uses the differential current calculated in accordance with the bus configuration programmed under Bus Zone
1. Operation of this element is therefore completely dependent on the dynamic bus replica, which must be defined first. The
bus differential zones are defined using the path
SETTINGS
SYSTEM SETUP
BUS
. The CT Trouble element 1 detects
CT problems in any of the circuits actually connected to the differential zone defined as Bus Zone 1.
The
CT TROUBLE ZONE 1 PICKUP
setting specifies the differential current level that defines an abnormal bus state. If the dif-
ferential current in a given phase remains above this level for the time interval defined by the
CT TROUBLE ZONE 1 DELAY
setting, CT Trouble is declared for the given phase by setting the appropriate FlexLogic output operand.
CT TROUBLE ZONE 1
CT TROUBLE ZONE 1
FUNCTION: Disabled
Range: Disabled, Enabled, Alarm
MESSAGE
CT TROUBLE ZONE 1
PICKUP: 0.100 pu
Range: 0.020 to 2.000 pu in steps of 0.001
MESSAGE
CT TROUBLE ZONE 1
DELAY: 10.0 s
Range: 1.0 to 60.0 s in steps of 0.1
MESSAGE
CT TROUBLE ZONE 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
CT TROUBLE ZONE 1
EVENTS: Disabled
Range: Disabled, Enabled
842018A2.CDR
AND
AND
AND
SET
dominant
RESET
SET
dominant
RESET
OR
OR
OR
OR
OR
BREAKER FLASHOVER
FUNCTION:
BRK 1 FLSHOVR V PKP:
BRK 1 STATUS CLSD A:
BRK 1 FLSHOVR PKP
DELAY:
BRK 1 FLSHOVR DPO A
BRK 1 FLSHOVR PKP A
BRK 1 FLSHOVR OP
BRK 1 FLSHOVR PKP
BRK 1 FLSHOVR DPO
BRK 1 FLSHOVR OP A
BRK 1 FLSHOVR DPO B
BRK 1 FLSHOVR PKP B
BRK 1 FLSHOVR OP B
BRK 1 FLSHOVR DPO C
BRK 1 FLSHOVR PKP C
BRK 1 FLSHOVR OP C
BRK 1 FLSHOVR SUPV A:
BRK 1 STATUS CLSD B:
BRK 1 FLSHOVR SUPV B:
BRK 1 STATUS CLSD C:
BRK 1 FLSHOVR SUPV C:
BRK 1 FLSHOVR AMP PKP:
BRK 1 FLSHOVR DIFF V
PKP:
BRK 1 FLSHOVR SIDE 1
SRC:
BRK 1 FLSHOVR SIDE 2
SRC:
Enable=1
RUN
RUN
RUN
RUN
RUN
RUN
SRC 1, SRC 2, … , SRC 6
SRC 1 SRC 2
SRC 6
,
, … ,
, none
VB
Vb
IB
Block: OFF=0
VA > PKP
FlexLogic operand: On=1
FlexLogic operand: Off=0
FlexLogic operand: On=1
FlexLogic operand: Off=0
Phase B
logic
Phase B
logic
Phase B logic
Phase B logic
Phase C
logic
Phase C
logic
Phase C logic
Phase C logic
FlexLogic operand: On=1
FlexLogic operand: Off=0
IA > PKP
Δ
VA > PKP
Va > PKP
VA
Va
IA
VC
Vc
Δ
|
|
VA = VA - Va
IC
SETTING
SETTING
SETTINGS
SETTING
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
SETTINGS
SETTING
SETTING
SETTINGS
SETTINGS
0
0
5 cycle
tPKP
0
0
5 cycle
6 cycle
Содержание B30 UR Series
Страница 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Страница 92: ...3 44 B30 Bus Differential System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE ...
Страница 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...