14
31-5000483 Rev. 2
• Attach the flare nuts to the indoor coil, using the same
process and precautions as found above for the outdoor
section flares.
• Using a torque wrench and back-up wrench, tighten the
indoor coil flare nuts to match the torque specification
chart.
• With the service valves closed, fill each tube with 500 PSI
of dry nigrogen and check for leaks.
• The indoor coil comes precharged with R410A so there is
no need to purge or evacuate the indoor coil.
• Evacuate the line set to at least 350 microns. From the
final micron level obtained, shut off the vacuum pump. If
the system rises no more than 150 microns within a minute
and stops, the evacuation can be considered sufficient.
• If the system rises more than 150 microns from the
original vacuum, there is either a leak or moisture has
not been removed. Locate and repair leak, or continue
evacuation as needed.
• When the evacuation is complete, replace the service valve
cores through the core removal tool.
• • Add additional refrigerant charge if needed before you
open indoor service valves if indoor coil is so equipped.
• Record the amount of refrigerant added in permanent ink
at the line set length location entered earlier.
Screw on the flare nut of the flaring connecting pipe on the
outdoor unit valve.
Liquid Pipe
Service Valves
Corrugate gas pile
Conventional Line Set Installation: Pipe Connection
Installation Instructions
IMPORTANT:
a 5/16” female by 1/4” male adapter will be required to connect conventional gauge hoses to
the service valves
.
Refrigerant Hose
Manifold Gauge
Low side
High Side
Low Side Valve
High Side Valve
Refrigerant Lines
(to indoor unit)
Liquid Valve
Gas Valve
Service Port
Cap
Refrigerant
Hose
Vacuum Pump
Cap
Service Pipe
Cap
Connection Pipe
Adding Refrigerant
Outdoor Unit Model
Standard Pipe Length
Max Pipe Length
Requiring No Added Charge
Additional Refrigerant
per Line Length
24.6 feet | 7.5m
≤31.2 feet | ≤9.5m
0.58 oz/ft 54 g/m
AUH2436ZGDA
Fig. 2.19
Adding Refrigerant
Outdoor Unit
Standard pipe length
(pre-charge)
Minimum pipe length /
Maximum pipe length
Additional Charge
AHU2436ZGDA
25ft
10ft /
164
ft
0.58 oz per ft
AHU4860ZGDA
25ft
10ft /
98
ft
0.58 oz per ft
NOTE:
It shows the gauge connection will need to have the high side gauge hose connected to the high side liquid valve so both
lines can be evacuated and leak checked.